241-2 & 1609 Series
WHITE-RODGERS
Operator: Save these instructions for future use!
FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY BEFORE
INSTALLING OR OPERATING THIS CONTROL COULD CAUSE PERSONAL
INJURY AND/OR PROPERTY DAMAGE.
This hydraulic action temperature control is applicable for all
types of commercial or industrial refrigeration applications. This
control will close contacts on rise in temperature and open them
on a fall in temperature.
The 241-2 control has a two-circuit contact structure which will
simultaneously close two circuits on a rise of temperature and
open them on a fall of temperature.
!
WARNING
FIRE/SHOCK HAZARD
Disconnect power to system at main fuse
or circuit breaker box before installation.
Do not use on circuits exceeding specified voltages.
CAUTION
FREEZE HAZARD
Install low temperature limit device.
System malfunction may cause freeze
damage.
Refrigeration Temperature Controls
INSTALLATION INSTRUCTIONS
DESCRIPTION
This two-circuit control is intended for use on zoning systems
where all controls operate a common compressor but operate a
separate solenoid refrigerant valve in each zone.
PRECAUTIONS
THIS CONTROL MUST BE INSTALLED BY A QUALIFIED
INSTALLER.
All wiring must conform to local and national electrical codes and
ordinances.
This control is a precision instrument, and should be handled
carefully. Rough handling or distorting components could cause
the control to malfunction.
This control has been accurately calibrated at the factory. Any
attempt to re-calibrate this control will void the White-Rodgers
warranty.
If in doubt about whether your wiring is millivolt, low or line
voltage, have it inspected by a qualified heating and air conditioning contractor or a licensed electrician.
Label all wires prior to disconnection when servicing controls.
Wiring errors can cause improper and dangerous operation.
Following installation or replacement, follow appliance manufacturers’ recommended installation/service instructions to insure proper operation.
The switch mechanism of this control may be mounted in any
location, provided that the temperature and humidity of the air in
which it is located do not cause a condensation on the switch
parts.
The sensitive element, or “bulb”, should be located in the
average temperature of the controlled area.
Capillary tubing should be led over a path that protects it from
damage from blows, cuts, etc., and should be installed without
kinking or twisting. The tubing should be attached to some
surface at frequent intervals along its length, and should not
WHITE-RODGERS DIVISION
EMERSON ELECTRIC CO.
9797 REAVIS RD., ST. LOUIS, MO. 63123-5398
(314) 577-1300, FAX (314) 577-1517
9999 HWY. 48, MARKHAM, ONT. L3P 3J3
(905) 475-4653, FAX (905) 475-4625
Printed in U.S.A.
INSTALLATION
hang loosely. Excess tubing should be coiled and secured at a
convenient protected location close to the switch mechanism.
The bulb should be handled with reasonable care, as a dent or
sharp bend may change the calibration and cause the control to
cycle at a temperature different from the dial setting.
PART NO. 37-1104F
Replaces 37-1104E
9909
WIRING
Temperature
control
Low temperature
limit
Suction
pressure
control
High side
pressure
control
Motor
starter
Solenoid
refrigerant
valve
To
Compressor
Motor
Line
L1
L2
Note:Make L1 “HOT” on
120V installation
240V
22.2A
22.2A
LOAD CONDITIONS
MAXIMUM ALLOWABLE RATING
Full Load Locked Rotor
120V
7.4A
7.4A
120V
44.5A
44.5A
240V
3.7A
3.7A
Load between Blue and Red
terminals must not exceed:
Load between Blue and White
terminals must not exceed:
All wiring must conform to local and national electrical codes and ordinances.
Connect in accordance with wiring diagrams provided by the equipment manufacturer. If none are provided, the following
represents a typical installation.
Controls with one circuit (two terminals)
Low
temperature
limit
Temperature
control
L1
Line
L2
Note:Make L1 “HOT” on
120V installation
Circuit showing temperature control controlling compressor directly.
High side
pressure control
(if used)
To
Compressor
Motor
Circuit showing temperature control to open and close
refrigerant valve. Suction pressure control starts and stops
compressor through motor starter.
Controls with two circuits (three terminals)
This diagram shows a typical two-circuit application. Several zones receive refrigeration from the
same compressor, but each zone requires its
own solenoid refrigerant valve and temperature
control.
SETTING THE DIAL
The movable indicator (D) points to the temperature at which the
compressor starts. The fixed indicator (B) points to the temperature at which the compressor will stop. The difference between
these two indicators is the differential. Follow these instructions
to set the dial:
1. Insert a screwdriver in the adjusting slot (A) and turn the dial
until the fixed indicator (B) points to the temperature at which
the compressor is to stop.
BLUE
RED
WHITE
Note:Make L1 “HOT” on
120V installation
Compressor
Motor
2
The blue terminal is common. The table below shows the
maximum load allowed between terminals.
L1
Line
L2
R
B
W
Valve
No. 1To
R
B
W
To
Additional
Units
Valve
No. 2
2. Turn the differential adjusting screw (C) until the movable
indicator (D) points to the temperature at which the compressor is to start.
“B” Fixed indicator
(cut-out point)
“C” Differential
adjusting screw
“D” Movable indicator
(cut-in point)
“A” Adjusting
slot