White Rodgers 241-2, 1609 User Manual

241-2 & 1609 Series
WHITE-RODGERS
Operator: Save these instructions for future use!
FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY BEFORE INSTALLING OR OPERATING THIS CONTROL COULD CAUSE PERSONAL INJURY AND/OR PROPERTY DAMAGE.
This hydraulic action temperature control is applicable for all types of commercial or industrial refrigeration applications. This control will close contacts on rise in temperature and open them on a fall in temperature.
The 241-2 control has a two-circuit contact structure which will simultaneously close two circuits on a rise of temperature and open them on a fall of temperature.
!
WARNING
FIRE/SHOCK HAZARD
Disconnect power to system at main fuse or circuit breaker box before installation.
Do not use on circuits exceeding speci­fied voltages.
CAUTION
FREEZE HAZARD Install low temperature limit device. System malfunction may cause freeze
damage.
Refrigeration Temperature Controls
INSTALLATION INSTRUCTIONS
DESCRIPTION
This two-circuit control is intended for use on zoning systems where all controls operate a common compressor but operate a separate solenoid refrigerant valve in each zone.
PRECAUTIONS
THIS CONTROL MUST BE INSTALLED BY A QUALIFIED INSTALLER.
All wiring must conform to local and national electrical codes and ordinances.
This control is a precision instrument, and should be handled carefully. Rough handling or distorting components could cause the control to malfunction.
This control has been accurately calibrated at the factory. Any attempt to re-calibrate this control will void the White-Rodgers warranty.
If in doubt about whether your wiring is millivolt, low or line voltage, have it inspected by a qualified heating and air condi­tioning contractor or a licensed electrician.
Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and dangerous operation.
Following installation or replacement, follow appliance manu­facturers’ recommended installation/service instructions to in­sure proper operation.
The switch mechanism of this control may be mounted in any location, provided that the temperature and humidity of the air in which it is located do not cause a condensation on the switch parts.
The sensitive element, or “bulb”, should be located in the average temperature of the controlled area.
Capillary tubing should be led over a path that protects it from damage from blows, cuts, etc., and should be installed without kinking or twisting. The tubing should be attached to some surface at frequent intervals along its length, and should not
WHITE-RODGERS DIVISION
EMERSON ELECTRIC CO. 9797 REAVIS RD., ST. LOUIS, MO. 63123-5398 (314) 577-1300, FAX (314) 577-1517
Printed in U.S.A.
INSTALLATION
hang loosely. Excess tubing should be coiled and secured at a convenient protected location close to the switch mechanism.
The bulb should be handled with reasonable care, as a dent or sharp bend may change the calibration and cause the control to cycle at a temperature different from the dial setting.
PART NO. 37-1104F
Replaces 37-1104E
9909
WIRING
Temperature
control
Low temperature
limit
Suction
pressure
control
High side
pressure
control
Motor
starter
Solenoid
refrigerant
valve
To Compressor Motor
Line
L1
L2
Note:Make L1 “HOT” on
120V installation
240V
22.2A
22.2A
LOAD CONDITIONS
MAXIMUM ALLOWABLE RATING
Full Load Locked Rotor
120V
7.4A
7.4A
120V
44.5A
44.5A
240V
3.7A
3.7A
Load between Blue and Red terminals must not exceed:
Load between Blue and White terminals must not exceed:
All wiring must conform to local and national electrical codes and ordinances.
Connect in accordance with wiring diagrams provided by the equipment manufacturer. If none are provided, the following represents a typical installation.
Controls with one circuit (two terminals)
Low
temperature
limit
Temperature
control L1 Line L2
Note:Make L1 “HOT” on
120V installation
Circuit showing temperature control con­trolling compressor directly.
High side
pressure control
(if used)
To Compressor Motor
Circuit showing temperature control to open and close refrigerant valve. Suction pressure control starts and stops compressor through motor starter.
Controls with two circuits (three terminals)
This diagram shows a typical two-circuit applica­tion. Several zones receive refrigeration from the same compressor, but each zone requires its own solenoid refrigerant valve and temperature control.
SETTING THE DIAL
The movable indicator (D) points to the temperature at which the compressor starts. The fixed indicator (B) points to the tempera­ture at which the compressor will stop. The difference between these two indicators is the differential. Follow these instructions to set the dial:
1. Insert a screwdriver in the adjusting slot (A) and turn the dial until the fixed indicator (B) points to the temperature at which the compressor is to stop.
BLUE
RED
WHITE
Note:Make L1 “HOT” on
120V installation
Compressor
Motor
2
The blue terminal is common. The table below shows the maximum load allowed between terminals.
L1 Line
L2
R
B
W
Valve No. 1To
R
B
W
To
Additional
Units
Valve No. 2
2. Turn the differential adjusting screw (C) until the movable indicator (D) points to the temperature at which the com­pressor is to start.
“B” Fixed indicator
(cut-out point)
“C” Differential
adjusting screw “D” Movable indicator
(cut-in point)
“A” Adjusting
slot
Loading...
+ 4 hidden pages