White Rodgers 21V51U-843 Specification

rsa
l
1D6
4-2
Universal Two-Stage HSI Integrated Variable-Speed (ECM) Circulator Furnace Control Kit
21V51U-843
Replaces:
All White-Rodgers 50V51-XXX’s and 50V61-XXX’s Two-Stage HSI Systems with 80V or 120V Ignitor
INCLUDED
HotRod™ Universal Ignitor Kit – 21D64-2
Replace the Original with the Original.
21V51U-843 simplifies stocking, installation and ensures peak system performance.
Easy-Install Kit includes everything you need for quick and accurate replacement:
• Ignition Control Module
• Wiring Harnesses for Amana/Goodman
• HotRod
• Installation Instructions and OEM Cross-Reference
Universal Ignitor Kit – 21D64-2
50V51-843
Universal Integrated Furnace Module 50V51-843
Universal Two-Stage HSI Integrated Variable-Speed (ECM) Circulator Furnace Control Kit
Replaces:
All White-Rodgers 50V51-XXX’s and 50V61-XXX’s Two-Stage HSI Systems with 80V or 120V Ignitor
21V51U-843
Features
• 120 VAC Ignitor Output
• 120 VAC Two-Speed Inducer Output
• 120 VAC Humidifier Output
• 120 VAC Electronic Air Cleaner Output
• 2-Stage Gas Valve Output
• 16-Pin Variable Speed Circulator Output
• OEM Application – Dipswitch Selectable
• Fuse Protection – 3 Amp
• Furnace Status LED – Tri-Color (Green, Red and Amber)
• CFM LED – (Green)
• Heat Fan OFF Delay (Dipswitch Selectable)
• Fan ON Delay for Cooling
• Auto Second Stage Delay (Dipswitch Selectable Mode)
• Historical Fault Retrieval by Pushbutton
• YLO, Y, W, W2, R, G, C, O, BK/DS/ Dehum Terminals
• Pressure Switch Inputs and Monitoring
• Flash Microprocessor with Non-Volatile Memory
• Flame Current Measurement Points
Specifications
Electrical Ratings [@ 77°F (25°C)]
Input Voltage: 24 VAC, 60 Hz (Class II transformer required) Nom. Input Current @ 24 VAC: 595 mA + MV
Relay Load Ratings
Gas Valve Relays: 1.5 amps @ 24 VAC, 60 Hz Inducer Relays: 2.2 FLA – 3.5 LRA @ 120 VAC, 60 Hz Humidifier Load: 1.0 amp max. @ 120 VAC, 60 Hz Electronic Air Cleaner Load: 1.0 amp max. @ 120 VAC, 60 Hz Ignitor Relay: 4.0 amps max. @ 132 VAC, 60 Hz
Flame Current Requirements
Minimum current to insure flame detection: 0.3 µa DC* Maximum current for non-detection: 0.1 µa DC* Maximum allowable leakage resistance: 100 M ohms
*Measured with a DC microammeter in the flame probe lead
Operating Temperature Range
-40° to 175°F (-40° to 80°C)
Humidity Range
5% to 93% relative humidity (non-condensing)
Timing Specifications (@ 60 Hz)
Flame Failure Response Time: 2.0 sec. max.
Gases Approved: Natural, Manufactured, Mixed, Liquefied Petroleum and LP Gas/Air Mixtures are all approved for use.
Dimensions
5.25" W x 8" H x 1.25" D
For Additional Information
Visit www.white-rodgers.com
Timing Specifications
(All times are in seconds unless noted otherwise)
21V51U-843
Pre-purge 15 Ignitor warm-up 17 Trial for ignition period 4 Ignition activation period 3 Retries 2 times Valve sequence period 12 Interpurge 60 Post-purge 15 Lockout time 300 Heat delay to fan ON 45 Heat delay to fan OFF* 90/120/150/180 Cool delay to fan ON 5 Cool delay to fan OFF 60 Delay to fan ON 0 Auto reset 60 minutes Electronic air cleaner Yes Humidifier Yes
* These times will vary depending on option switch position. See OPERATION section for further information.
21V51U-843 Cross Reference Application Data:
Module Model # Furnace Model Harness Ignitor Furnace OEM
18M9901 G60DFV (X) or None 21D64-2* Lennox G60UHV required
20300002 N/A Amana 20300004 N/A Goodman 20300006 Same as 50V61-289 49M5901 G60UHV or G61MPV Lennox 50V51-243 FC8V, FC9V, FL8V, FL9V, GM8V, Use existing Coleman
GM9V, LC8V, LL8V, LM8V, or 21D64-2 Evcon/Luxaire PV8A, PV9A or PV9B York
50V51-288 N/A A,B Amana 50V51-289 N/A Goodman 50V51-290 N/A 50V51-507 XV80 or XV80i None 21D64-2* American
required required Standard/ Trane
50V61-120 G60DFV (X), G60UHV Lennox or G61MPV
50V61-143 CDX1-75N, CDX1-100N, Thermo Pride CDX1-125N, CHX1-75N, CHX1-100N or CHX1-125N
50V61-288 N/A Amana 50V61-289 AMV91155DXA Goodman 50V61-289 AMV81155CXA 50V61-289 ADV80703BXA 50V61-289 ADV80905CXA 50V61-289 AMV90453BXA
Note: The installer may have to modify existing ignitor hole to accommodate the new 21D64-2, with ceramic diameter (0.394").
*21D64-2 Ignitor Note: In these applications, the existing 80V ignitor must be replaced by the 120V 21D64-2 ignitor.
Module Model # Furnace Model Harness Ignitor Furnace OEM
50V61-289 AMV90704CXA None 21D64-2* Amana required Goodman
50V61-289 AMV90905DXA 50V61-289 AMV80703BXA 50V61-289 AMV80905CXA 50V61-289 AMV80704BXA 50V61-289 ADV81155CXA 50V61-289 AMV90704CXA 50V61-507 XV80 or XV80i American Standard
Trane B1809925 N/A A,B Use existing Amana/
or 21D64-2 Goodman B1809927 N/A B1809927S N/A CNT03078 XV80 or XV80i None 21D64-2* American Standard
required Trane D156245P01 XV80 or XV80i
D34142P01 XV80 or XV80i PCB00106 N/A A,B Use existing Amana
or 21D64-2 Goodman PCB00106S N/A
PCBBF106 N/A PCBBF106S N/A PCBBF107S N/A X13650840010 XV80 or XV80i None 21D64-2* American Standard
required Trane
Saint Louis, Missouri Markham, Ontario
314-553-3600 905-948-3411
www.white-rodgers.com
www.emersonclimate.com