Shipping Temperature Range ................................... -40° to +150°F (-40° to +65°C)
Dimensions Interface ................................................ 4-1/2”H x 6”W x 1-1/4”D
Dimensions Control .................................................. 5-1/2”H x 5-3/4”W x 1-1/2”D
Equipment Control
40C01-1400
CAUTION
!
To prevent electrical shock and/or equipment damage,
disconnect electric power to system at main fuse or
circuit breaker box until installation is complete.
IndexPage
Installation2
Wiring Connections2
Wiring Diagrams3
Installer Configuration Menu5
Troubleshooting8
www.white-rodgers.com
www.emersonclimate.com
ATTENTION: MERCURY NOTICE
This product does not contain mercury. However, this
product may replace a product that contains mercury.
Mercury and products containing mercury must not be
discarded in household trash. Do not touch any spilled
mercury. Wearing non-absorbent gloves, clean up any
spilled mercury and place in a sealed container. For proper
disposal of a product containing mercury or a sealed
container of spilled mercury, place it in a suitable shipping
container. Refer to www.white-rodgers.com for location to
send product containing mercury.
PART NO. 37-7215C
Replaces 37-7215B
1110
1
Page 2
INSTALLATION
WARNING
!
Thermostat installation and all components of the
control system shall conform to Class II circuits per
the NEC code.
Control 40C01-1400
Control can be mounted on wall or equipment. Control has
four mounting holes. Wall anchors and screws are provided
for mounting on drywall. Drill 3/16 hole for drywall mounting.
If mounting on equipment Do Not Mount inside HVAC
equipment. Only mount on outside of HVAC equipment.
WIRING CONNECTIONS
Refer to equipment manufacturers’ instructions for specific
system wiring information. After wiring, see CONFIGURATION
section for proper thermostat configuration.
Connect wires as appropriate for HVAC systems (see wiring
diagrams). To power control, connect the 24 V system hot to
R terminal and common to C on left side of control labelled
“Power”. On initial power up the 7 segment LED on the
Thermostat / Interface 1F98-1491
1) Pull the thermostat/interface off the base. Forcing or
prying on the thermostat will cause damage to the unit.
2) Place base over hole in wall and mark mounting hole
locations on wall using base as a template.
3) Move base out of the way. Drill mounting holes. If you are
using existing mounting holes and the holes drilled are
too large and do not allow you to tighten base snugly, use
plastic screw anchors to secure the base.
4) Fasten base snugly to wall using mounting holes and two
mounting screws. Leveling is for appearance only and will
not affect thermostat operation.
5) Connect wires to terminal block on base (see Figure 1).
6) Push excess wire into wall and plug hole with a fire
resistant material (such as fiberglass insulation) to prevent
drafts from affecting thermostat operation.
7) Carefully line the thermostat up with the base and snap
into place.
control will display E (for communication error) until interface
is connected. With power supplied to control, it is normal for
the green system LED to flash periodically.
With interface connected, the 7 segment LED will display
C to indicate the two devices have initiated communication.
C will disappear after approximately 30 seconds when
communication is established.
BLUE EASY INSTALL INPUTS/OUTPUTS
Easy Install 40C01 Operational / Functional
Control Terminals
R ......................................... 24 VAC Transformer
R .......................................... 24 VAC to Interface
1........................................... Data to/from Interface
2........................................... Data to/from Interface
C .......................................... 24 VAC Common to Interface
RJ11 .................................... Field configuration hook-up with RJ11
equipped configuration tool
+ .......................................... Voltage to Outdoor Sensor
S .......................................... Outdoor Sensor Temperature Signal
- ........................................... Voltage to Outdoor Sensor
R
1
2
C
C
40C01Control1F98 Thermostat
2
Page 3
WIRING DIAGRAMS
Fig. 2 - Typical Connection of a Single Stage or Multi-Stage System
*
SYSTEMRRHRCCW/EW2YY2GO/BL
Single
Stage
Multi
Stage
*Factory installed jumper between RH and RC
Fig. 3 - Typical Connection of Heat Pump System up to 4 Stages Heat / 2 Stages Cool
SYSTEMRRHRCCW/E W2YY2GO/BL
Heat
Pump
24 VAC
Powe r
24 VAC
Powe r
24 VAC
Powe r
24 VAC
Powe r
for Heating
24 VAC
Powe r
*
24 VAC
Powe r
for
Heating
24 VAC
for Cooling
24 VAC
24 VAC
Powe r
for
Cooling
Powe r
Powe r
Common
Required
24 VAC
24 VAC
Common
Required
Aux /
Em
stage
HeatN/ACoolN/AFanN/ASystem
Heat
mode
stage
Aux /
Em
st
1
st
1
nd
2
Heat
mode
nd
2
stage
1st stage
Compressor
Cool
mode
st
1
stage
2nd stage
Compressor
Cool
mode
nd
2
stage
Fan Changeover
Valve
stage
Monitor
System
Monitor
NEUTRAL
24 VAC
HOT
120 VAC
CLASS II
Transformer
*Factory installed jumper between RH and RC
Fig. 4 - Typical Connection of Heat Pump / Dual Fuel System up to 4 Stages Heat / 2 Stages Cool
*
SYSTEMRRHRCCW/E W2YY2GO/BL
Heat
Pump
*Factory installed jumper between RH and RC
24 VAC
Powe r
24 VAC
Powe r
for
Heating
24 VAC
Powe r
for
Cooling
24 VAC
Common
Required
Fossil
Fuel
st
1
stage
Fossil
Fuel
nd
2
stage
1st stage
Compressor
2nd stage
Compressor
Fan Changeover
Valve
System
Monitor
NEUTRAL
24 VAC
HOT
NEUTRAL
24 VAC
HOT
120 VAC
CLASS II
Transformer
120 VAC
CLASS II
Transformer
3
Page 4
WIRING DIAGRAMS
Wiring Guide for Equipment Accessories
Fig. 5 - Non-Powered Humidifier. HM terminal provides system 24 V on call for humidification
Transformer
R
C
HM DRY
RHHM2
HM
HM2
Fig. 6 - Powered Humidifier. With HM DRY switch in HM2 position, HM and HM2 provide normally
open dry contact for low voltage (24 V) powered humidifier connection.
HM DRY
RHHM2
HM
HM2
Powered
Humidifier
Fig. 7 - Powered Dehumidifier. With DHM DRY switch in DHM2 position, DHM and DHM2 provide
normally open dry contact for low voltage (24 V) whole house powered dehumidifier connection.
RHDHM2
DHM DRY
DHM
DHM2
Powered
Dehumidifier
Non-Powered
Humidifier
Fig. 8 - System Dehumidification with variable speed blower. For systems where low speed requires connect to normally
open 24 V powered DHM terminal for low speed connection on air handler / furnace (24 V removed on dehumidification call).
RHDHM2
DHM DRY
DHM
DHM2
Low Speed
Fan
Fig. 9 - System Dehumidification with variable speed blower. For systems where low speed requires system 24 V on
dehumidification connect 24 V to DHM2 with DHM DRY switch in DHM2 position and connect DHM to low speed
connection on air handler/ furnace.
Transformer
R
C
RHDHM2
DHM DRY
DHM
DHM2
Low Speed
Fan
4
Page 5
INSTALLER/CONFIGURATION MENU
Entering and Navigating the Advanced Installer Configuration Menu
On the Home Screen Display, touch the Menu key to display additional key choices. Touch and hold the Installer Config key
for approximately 3 seconds to enter the Thermostat Options Configuration Menu. Touch and hold the Installer Config key
again for approximately 3 seconds to enter the Advanced Installer Configuration Menu.
Press or Key
Description of
Features in order when
Ref.
using to choose;
#
(Use to step back)
Outdoor / Condenser
1
2
3
4Heat Cycle RateFASL, FAHEAT CYCLE RATE
5Cool Cycle RateFASL, FACOOL CYCLE RATE
6
7
8
9
ConfigurationAC1AC0, AC1, AC2, HP1, HP2
Indoor Heat
ConfigurationGA2FAN, GA1, GA2, EL1, EL2
B or O terminal
(HP1, HP2 only)OO, bREVERSING VALVE
Auxiliary Cycle Rate
(HP1, HP2 only)FASL, FA
Energy Management
RecoveryOnOFF, On
Outdoor Remote
SensorOFFOFF, OnOUTDOOR REMOTE SENSOR
Auxiliary Off
(HP1, HP2 only)OFF
Displayed in
Clock Digits
(Default)Options
to Select Options
OFF, 35-80 (in steps of 1 degree)
From OFF, value changes to 80AUXILIARY OFF
Displayed in
Message Area
CONDENSER
CONFIG
INDOOR HEAT
CONFIG
AUXILIARY CYCLE
RATE
ENERGY MANAGEMENT
RECOVERY
Dual Fuel Config
10
11DehumidificationOFF
12
13HumidificationOFF
14
15Compressor LockoutOFFOFF, OnCOMPRESSOR LOCKOUT
(HP1, HP2 only)40
Independent
DehumidificationOFFOFF, OnINDEPENDENT DEHUMID
Independent
HumidificationOFFOFF, On
OFF, 0 to 50 (in steps of 1 degree)
From OFF, value changes to 40DUAL FUEL CONFIG
OFF, 40-80 (in 1% steps) - displayed
in the last digits of the Message Area.
From OFF, value changes to 60
OFF, 20-60 (in 1% steps) - displayed
in the last digits of the Message Area.
From OFF, value changes to 40
DEHUM XX% (where XX
is the DEHUM set point)
HUMID XX% (where XX
is the HUM set point)
INDEPENDENT
HUMID
5
Page 6
INSTALLER/CONFIGURATION MENU
W/E
W2YY2GO/B
HM
DHM
Break tab
to have LEDs
on with cover
installed
Configuration
Control can be configured at the equipment by utilizing the configuration plug in tool (F4-1400). The tool mounts to the back
of the interface and plugs into the bottom of the control via the RJ-11 connection. (Note: You cannot have two interfaces
connected to the control at the same time). With control powered, interface is used to configure the application and for
operational checks. Once configured, the interface can be installed in living area.
1) Outdoor / Condenser Configuration. Select the number type A/C (air conditioner) HP Heat Pump and number
of stages. The appropriate Color (A/C= Amber, Heat
Pump=Green) LED will illuminate for the configured Y/Y2
terminals.
2) Indoor / Heat Configuration. Select the number type
GA (Gas) EL (electric) and Fan and number of stages.
The appropriate Color (Amber if gas, Green if electric)
LED will illuminate for the configured W/W2 terminals.
3) B or O Terminal Configuration. If condenser is heat
pump configured then Select either O (default) or B
terminal output configuration. The B/O LED will illuminate
the appropriate color (Amber if B, Green if O)
4) Heat Cycle Rate. Select either FA fast (default) or SL
slow cycle rate. If longer cycles are desired then set to
SL.
5) Cool Cycle Rate. Select either FA fast (default) or SL
slow cycle rate. If longer cycles are desired then set to
SL.
6) Auxiliary Cycle Rate. If condenser is heat pump select
either FA fast (default) or SL slow cycle rate. If longer
cycles are desired then set to SL.
7) Energy Management Recovery. Select either On or Off.
With a selection of On the system will start temperature
setback recovery early to reach the program setpoint at
the program start time. A selection of Off will start the
recovery period at the program start time.
8) Outdoor Remote Sense. A selection of On enables the
display of outdoor temperature with the connection of
F145-1378 outdoor remote sensor to the control.
9) Auxiliary Off. When condenser is heat pump configured
and outdoor sensor is connected, the option of locking
out the auxiliary heat based on outdoor ambient temperature becomes available. Default is Off with a selection range from 80 degrees to 35 degrees in 1 degree
increment. When outdoor ambient is above the selected
temperature the auxiliary stages are disabled.
10) Dual Fuel Config. When condenser is heat pump and
indoor heat is gas and outdoor sensor is connected. A
selection from 0 to 50 in one degree increment is available. The Auxiliary/fossil fuel system is enabled, the heat
pump is disabled when the outdoor ambient temperature
is at or below the selection.
11) Dehumidification. Select from Off (default) to a setting
range from 40% to 80% Rh. If Rh is above setting, a
cooling call is initiated. To turn this feature Off raise setting to its highest level 80%
12) Independent Dehumidification. Selection of Off (default) or On. When On is selected the DHM2 output is
active when humidity level is above the desired dehumidification setting.
13) Humidification. Select from Off (default) to a setting
range from 20% to 60% Rh. If Rh is below setting HM2
output is active with a call for heat. To turn this feature Off
lower setting to its lowest level 20%.
14) Independent Humidification. Selection of Off (default)
or On. When On is selected the HM2 output operates
when humidity level is below the desired humidification
setting.
15) Compressor Lockout. Selection of Off (default) or On.
When On is selected the control will invoke a 5 minute
delay between compressor cycles.
After Advanced Installer Configuration, LEDs on the control
will indicate the selections of the thermostat. The following
tables show the LED indications. Remove control cover to
Fig. 10 - LED locations
W/E
7-Segment
LED for Comfort
Alert and
Communication
Codes
System
6
Configuration Plug-In tool
RJ-11 Connection for
W2
Y
Y2
G
O/B
HM
DHM
view LEDs. To view LEDs with cover installed, break off tab
on inside of cover.
Fig. 11 - Inside of front cover
Break tab
to have LEDs
on with cover
installed
Page 7
INSTALLER/CONFIGURATION MENU
LED Indicator legend:
= Amber
= Green
Off= Off
LED’s will be on constant to show configuration.
LED’s will flash to indicate the terminal output is active.
Table 1 - System Configuration
No. of Stages –
System
Type
Conventional
Heat Pump
Dual Fuel
AC Cool
Gas Heat
Electric Heat
Electric System
HP Only (HO)
Fan Only
Outdoor
Equipment
Type
AC1Gas1OffOff
AC1Gas2Off
AC2Gas1Off
AC2Gas2
HP1Elec1OffOff
HP1Elec2Off
HP2Elec1
HP2Elec2
HP1Gas1Off
HP1Gas2Off
HP2Gas1
HP2Gas2
AC1Elec0OffOffOff
AC2Elec0OffOff
No Outdoor
Unit–Gas1OffOffOff
No Outdoor
Unit–Gas2OffOff
No Outdoor
Unit–Elec1OffOffOff
No Outdoor
Unit–Elec2OffOff
AC1Elec1OffOff
AC1Elec2Off
AC2Elec1Off
AC2Elec2
HP1Elec0OffOffOff
HP2Elec0OffOff
No Outdoor
Unit–Elec0OffOffOffOff
Outdoor
Equipment
Type
Indoor
Equipment
Type
No. of Stages –
Indoor
Equipment
TypeYY2W/EW2G
Table 2 - DHM Bi-Color LED Table
DHM DRY
Switch Position
RH
DHM2
DHM LED
Table 3 - HM Bi-Color LED Truth Table
HM DRY
Switch Position
RH
HM2
HM LED
Table 4 - O/B Bi-Color LED Truth Table
Reversing Valve
Configuration
O mode
B mode
O/B LED
7
Page 8
TROUBLESHOOTING
Reset Operation
If a voltage spike or static discharge blanks out the display or
causes erratic thermostat operation, you can reset the system
by removing batteries for 2 minutes. After resetting the
system, replace the batteries. If the system has been reset
and still does not function correctly perform a power reset.
Note: Be sure to review the installer configuration menu
settings.
Furnace (Air Conditioner)
Cycles Too Fast or Too
Slow (narrow or wide
temperature swing)
1. Blown fuse or tripped circuit breaker.
2. Power switch to OFF.
3. Furnace blower compartment door or
panel loose or not properly installed.
4. Loose connection to system.
1. Pilot light not lit.
2. Furnace Lock-Out Condition. Heat
may also be intermittent.
3. Heat pump system requires service.
See fault code table Comfort Alert.
1. Cooling system requires service.
See fault code table Comfort Alert.
1. Possible short in wiring.
2. Possible short in thermostat.
3. Possible short in heat/cool/fan system.
4. FAN Switch set to Fan ON.
1. Thermostat display setting
requires adjustment.
1. The location of the thermostat and/or
the size of the Heating System may
be influencing the cycle rate.
Note: When thermostat is reset, installer configuration menu
settings and programming will reset to factory settings.
To reset the programming, clock and configuration
settings, press and and the SYSTEM touch keys
simultaneously. The thermostat should go blank and then all
segments will be displayed momentarily.
Replace fuse or reset breaker.
Turn switch to ON.
Replace door panel in proper position to engage safety
interlock or door switch.
Check connections.
Re-light pilot.
Many furnaces have safety devices that shut down when
a lock-out condition occurs. If the heat works intermittently
contact the furnace manufacturer or local HVAC service
person for assistance.
Check each wire connection to verify they are not shorted
or touching together. No bare wire should stick out from
under terminal block. Try resetting the thermostat as
described above. If the condition persists the manufacturer
of your system or service person can instruct you on how
to test the Heat/Cool system for correct operation. If the
system operates correctly, replace the thermostat.
The display can be adjusted +/- 5 degrees. See
Temperature Display Adjustment in the Configuration Menu
section.
Digital thermostats provide precise control and cycle faster
than older mechanical models. The system turns on and off
more frequently but runs for a shorter time so there is no
increase in energy use. If you would like an increased cycle
time, choose SL for slow cycle in the Configuration menu.
White-Rodgers is a division
of Emerson Electric Co.
The Emerson logo is a
trademark and service mark
of Emerson Electric Co.
8
Comfort Alert™ Fault Codes
Number Displayed in
7 Segment LED
PTr i p
1Long Run Time
2System Pressure Trip
3Short Cycling
4Locked Rotor
5Open Circuit
6Open Start Circuit
7Open Run Circuit
8Welded Contactor
9Low Voltage
System Communication Codes
ECommunication Error
CFor 30 seconds after Communication
www.white-rodgers.com
www.emersonclimate.com
Comfort Alert Fault
established, then blank
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.