WHITECROFT LIGHTING ACL INDUSTRY Installation Leaflet

Page 1
GENERAL INFORMATION
1. A qualified electrician, in accordance with IEE wiring regulations, should carry out connection to mains wiring.
2. Ensure mains power is turned off during maintenance.
3. Ensure that the rated voltage and frequency requirements are compatible with the
available mains supply.
4. This unit must be EARTHED.
5. Cleaning of reflectors and lenses should be carried out using clean, soft and lint free cloths and anti-static cleaning fluid.
6. Do not carry out high voltage insulation test, i.e. 500/1000v this may damage
internal components.
7. Replacing the light source within this luminaire shall only be carried out by the manufacturer, service agent or a similar qualified person.
SPECIFICATION
Lamp type: LED 4000°K Control Gear: Fixed Output / DALI
Body Material: Light Grey PC
Diffuser material: Supply: 220-240V AC, 50Hz
Operating temp:
Conductor: 2.5mm2 max
Rating: IP66 / IK08
Weight: 1283mm 1578mm
Opal High Impact PC with internal prisms
Standard -20°C to 25°C
Emergency -5°C to 25°C
Std 2.75 kg Em. 3.25 kg Std 3.4 kg Em. 3.9 kg
FURTHER INFORMATION
In common with all IP66 rated fittings the ACL Industry luminaire is protected against ingress of dust and water projected from a nozzle. However care must be taken in the siting of these luminaires. They can be mounted outdoors under
a canopy or covered environment but should not
be in direct sunlight or open areas exposed to adverse weather conditions. In particular they should not be installed in an environment liable to produce standing water on the fitting or IP glands.
ACL INDUSTRY
Installation Leaflet
PLEASE NOTE: In
freezer applications product must be mounted a minimum of 1M from any ventilation including the freezer door.
All measurements in mm unless stated otherwise, see website for product codes and
lumen outputs
Variant Length Cable Entry
Points
0.6m 663 530 390 266
1.2m 1283 1050/1170 800 676
1.5m 1578 1345/1170 1100 976
TECHNICAL SUPPORT Tel: 0161 331 5700
e-mail: technical@whitecroftlight.com
Mount Bracket
Centres
Surface Mount
Centres
PK/LEAFLETACLLED
Feb 2019 - Rev G
Whitecroft Lighting Limited
Bu r l i ngton S treet , Asht o n - u nder- L y ne, La n c ashire O L7 0A X Telephone +44 (0)870 5 087 087 Facsimile: +44 (0)870 5 084 210
Registered No. 3848973 England Registered Office: As above
Page 2
LED INSTALLATION SEQUENCE
1. Remove the luminaire from the packaging, lift the diffuser and set it to one side.
2. Remove the gear tray from the housing by squeezing the plastic clips together at both ends. (Fig.1)
3. Remove the plastic bag containing the
ceiling fixing kit, diffuser retention clips,
sealing grommets.
4. There are 2 mounting options with the supplied components - surface mounted or suspended (Fig. 2).
5. For secure suspension i.e. in an area with a high risk of lateral movement use the ACFHOOKKIT (supplied separately ­additional rubber washer required for IP seal not included).
6. For direct surface mounting use suitable screws and washers (supplied by others) through the same mounting bosses as the hook kit. Ensure that washers are correctly fitted to the inside of the bosses to maintain the IP rating.
ELECTROSTATIC SENSITIVE DEVICE
Page 1
HIGH VOLTAGE LEDs
Fig. 2
Fig. 1
DETECTION AREA
Detection area can be reduced by selecting the combination on the DIP switches to fit precisely for each specific application.
HOLD TIME
Hold-time means the time period you would like to keep
the lamp on 100% after the
person has left the detection area.
DAYLIGHT SENSOR - NOT USED
DEFAULT SETTING I - DISABLED
STAND-BY PERIOD (CORRIDOR FUNCTION)
This is the time period you would like to keep at the low light output level before it is completely switched off in the long absence of people.
Note: “0s” means on/off control; “+ ∞” means bi-level dimming control, fixture never switches off.
STAND-BY DIMMING LEVEL
This is the dimmed low light output level you would like to have after the hold-time in the absence of people.
Page 6
Page 3
COMMAND 5 SENSOR WITH SETBACK DIP SWITCH CONFIGURATION
Model: HCD418
The sensor is a motion switch. It turns the light ON after detection of moving objects and turns the light OFF after a pre-selected hold-time when there is no motion detected.
7. Bring the incoming supply wires into the luminaire body through the knock-outs at the end of the body or on the rear (Fig.3) using the supplied sealing grommets. Seal any unused cable entry holes with the closed grommets supplied.
Fig. 4
DALI
MAINS
DALI EM / COMEPS
INSTALLATION OF LUMINAIRE
Note: Important to consider
The sensor provides DALI output to the driver to perform on / off / setback
control only. The sensor must not be connected to a DALI network.
The sensor can detect movements though thin walls and glass; detection
range (sensitivity) should be adjusted in accordance with site conditions.
Luminaire must be fixed to a solid surface to avoid false-triggering caused by
vibration.
Large metal surfaces can cause unwanted detection. Ventilation shafts and airflow can cause unwanted detection. Luminaires mounted within each other’s detection range may need their
sensitivity reduced to avoid possible nuisance switching.
DETECTION AREA PATTERN
Fig. 5
CLICK!
Fig. 6
10. Clip the gear tray back into the housing. (Fig.5)
11. Set sensor dip switch configuration if applicable. (see pages 3-6)
12. Remove the two anti tamper screws from the gear tray for fixing diffuser clips. (Fig. 6)
8. Lift the gear tray back into position and hook onto the plastic retention clips within the housing. (Fig.4)
9. Make all electrical
connections to the
terminal blocks (Fig.4) and connect the emergency batteries if applicable.
13. Fit the diffuser back into position using all of the retention clips and secure two plastic clips on opposite sides with the anti-tamper screws provided. (Fig.6)
Page 2 Page 5
Page 4
COMMAND 5 ECO SENSOR DIP SWITCH CONFIGURATION
Model: HC005s
The sensor is a motion switch. It turns the light ON after detection of moving objects and turns the light OFF after a pre-selected hold-time when there is no motion detected.
INSTALLATION OF LUMINAIRE
Note: Important to consider
The sensor can detect movements though thin walls and glass; detection
range (sensitivity) should be adjusted in accordance with site conditions.
Luminaire must be fixed to a solid surface to avoid false-triggering caused by
vibration.
DETECTION AREA
Detection area can be reduced by selecting the combination on the DIP switches to fit precisely for each specific application.
HOLD TIME
Hold-time means the time period you would like to keep the lamp on 100% after the person has left the detection area.
DAYLIGHT SENSOR -
Large metal surfaces can cause unwanted detection.
Ventilation shafts and airflow can cause unwanted detection.
Luminaires mounted within each other’s detection range may need their
sensitivity reduced to avoid possible nuisance switching.
DETECTION AREA PATTERN
Page 3
NOT USED
DEFAULT SETTING I -
DISABLED
Page 4