WhisperKOOL copyrights this manual, the product design, and the design concepts, with all rights reserved. Your rights
with regard to the hardware and manual are subject to the restrictions and limitations imposed by the copyright laws of
the USA. Under copyright laws, this manual may not be copied, reproduced, translated, transmitted, or reduced to any
printed or electronic medium or to any machine-readable form, for any purpose, in whole or in part, without the written
consent of WhisperKOOL.
Every effort has been made to ensure that the information in this manual is accurate. WhisperKOOL is not responsible for
printing or clerical errors.
WhisperKOOL reserves the right to make corrections or improvements to the information provided and to the related
hardware at any time, without notice.
Vinothèque and WhisperKOOL are registered trademarks, and ECE is a trademark of WhisperKOOL. All rights reserved.
Mention of third-party products is for informational purposes only and constitutes neither an endorsement nor a
recommendation. WhisperKOOL assumes no liability with regard to the performance or use of these products.
Installation Terms and Conditions ......................................... 53
Page 4
INTRODUCTION
Customer Service
Thank you for purchasing a WhisperKOOL cooling system. We strive to provide the highest-quality products and the best
possible customer service. If you have any questions about your system, please call us at 1-800-343-9463 or visit
WhisperKOOL.com.
Using the Manual
This manual is intended to assist in the proper maintenance of the cooling system. In order to ensure the longevity of your
cooling unit, the equipment should be installed as outlined in the technician’s manual. It is also vital to establish a proper care
and maintenance schedule. Please read and review this manual carefully and keep it for future reference.
What is the WhisperKOOL Cooling System?
The WhisperKOOL cooling system is a specialized refrigeration system designed for one purpose only: to maintain the optimal
temperature and humidity levels conducive to the proper storage and aging of ne wines. This system produces minimal in-cellar
noise and has the most lenient exhaust requirements. An exterior housing is required for outdoor condensing unit installations.
How Does the Cooling System Work?
Similar to the air conditioning systems used for homes, the evaporator unit and condensing units are installed in separate
locations and are connected by a refrigerant line set. The evaporator portion is commonly installed in the wine cellar, with the
condensing unit is located either outside or in a remote indoor location that is ventilated. An exterior housing is required for
outdoor condensing unit installations.
Temperature Setting
The system is designed to maintain a cellar temperature of 55°F as long as the ambient temperature does not exceed 110°F.
WARRANTY REGISTRATION
In order to activate the warranty of your system, the verication and operational
documentation must be completed by the certied refrigeration technician
installing your system and submitted via mail, fax, or e-mail.
Mail to:
WhisperKOOL
ATTN: Warranty Registration
1738 E. Alpine Avenue
Stockton, CA 95205-2505
USA
Fax to:
209-466-4606
Scan and email to:
warranty@whisperkool.com
Page 2 | 1-800-343-9463
PS 021319
Page 5
Platinum Split
QUICK START GUIDE*
Pump Down Cycle
WhisperKOOL’s split systems operate on a pump down cycle dierent from traditional air conditioners. As such, there is no wiring
between the condensing unit and evaporator unit.
WhisperKOOL units utilize a solenoid valve on the liquid line and a low-pressure switch on the suction line. When the thermostat
calls for cooling, the solenoid valve opens, permitting the ow of refrigerant. The low-pressure switch then signals the compressor
to cycle on.
When the cellar reaches the desired temperature and the thermostat is satised, the solenoid will close, stopping the liquid
refrigerant ow to the TXV valve. The compressor will continue to operate until most of the refrigerant on the low side boils o
and is pumped through the compressor into the condenser coil and receiver. As the suction pressure falls below the pressure
control setting, the low-pressure switch will signal the compressor to cycle o. Most of the refrigerant is now stored between the
condensing unit and receiver.
…………………………………………………………………………………………………
WARNING: Do not utilize a ground fault interrupter, as it will prevent
the unit from drawing the necessary amperage to start the unit.
TXV Adjustments
A. A TXV adjustment may be necessary based on ambient temperatures in the cellar and at the condensing unit.
B. Adjust the TXV until the total superheat measured at the suction line service valve is 20-30°F.
C. Under normal operation, with the wine cellar at 55°F and the ambient temperature at 85°F, the low side pressure should be
between 28-32 PSI and the high side should be between 145-155 PSI.
TXV
The TXV is preadjusted at the factory. If the superheat is not within
20-30° at the service valve, the TXV will need to be adjusted.
ADJUSTING THE TXV
Use a ⁄” hex key to remove the cap from the TXV superheat
adjustment port. With the cap removed, insert the hex key into
the superheat adjustment port. Increase superheat by turning the
hex key clockwise. Decrease superheat by turning the hex key
counterclockwise.
Liquid Line King Valve
This location is used to charge the system with liquid refrigerant
and identify the high side pressure of the system.
Calculating Subcooling
To determine the subcooling of the system, calculate the dierence
between the high side pressure of the system (converted to
temperature) and the temperature of the liquid line. The temperature
of the liquid line will be taken at the outlet of the receiver.
*Saturation temp — liquid line temp
4-6°F SUBCOOLING REQUIRED FOR WARRANTY APPROVAL
*Further system operation information is available on page 39.
www.whisperkool.com | Page 3
Page 6
BEFORE YOU START
1. Inspect all components prior to installation. If damage is found, please contact your distributor or WhisperKOOL Customer
Service at 1-800-343-9463.
2. The evaporator unit requires a dedicated 115V, 15-amp circuit. The 4000 condenser requires a dedicated 115V, 15-amp
circuit. The 8000 condenser requires a dedicated 115V, 20-amp circuit. Use a surge protector with the unit. Do not use a
GFI (ground fault interrupter) line.
3. No communication cable is required between the evaporator and condensing unit.
4. You are REQUIRED to install a drain line to remove condensation from the evaporator unit.
5. The warranty is not active until a warranty checklist has been received, reviewed, and approved.
6. The system is intended for use in properly designed and constructed wine cellars. Hire a professional wine storage
consultant with a valid contractor’s license to build your wine cellar.
7. WhisperKOOL requires that all split systems be installed by a certified HVAC-R technician only. NATE or equivalent is
recommended.
If you encounter a problem with your WhisperKOOL system, please refer to the Troubleshooting Guide. If you have any further
questions or concerns, or need assistance, please contact WhisperKOOL’s Customer Service at 1-800-343-9463. Please be sure all
testing has been completed prior to contacting Customer Service. Please have your results ready for your representative.
1-800-343-9463
Page 4 | 1-800-343-9463
PS 021319
Page 7
Platinum Split
RECEIVING & INSPECTING THE SYSTEM
• Use caution when lifting and check package for damage.
• Lift only at the designated hand-hold locations on the shipping container, or fully support the unit from underneath. A
shipment may include one or more boxes containing accessories.
• Before opening the container, inspect the packaging for any obvious signs of damage or mishandling.
• Write any discrepancy or visual damage on the bill of lading before signing.
• Allow the condensing unit to sit for 24 hours prior to start-up. The condensing unit can be placed in the installation
location, piped, and evacuated during this time.
NOTE: WhisperKOOL units are manufactured in the USA and tested prior to shipment.
• Review the packing slip to verify contents.
• Check the model number to ensure it is correct.
• Check that all factory options ordered are listed.
If any items listed on the packing slip do not match your order information,
contact WhisperKOOL Customer Service immediately.
Check all shipped boxes for the following contents:
Main Evaporator Box
(1) Platinum Split evaporator
unit
Documentation bag:
• Platinum Split Version 3 owner’s manual
• Platinum Split Version 3 technician’s manual
• R-134a split system warranty checklist
Accessory kit bag:
• KDT Plus display cable (50 feet)
• KDT Plus wall mount bracket assembly
• KDT Plus ush mount bracket assembly
• KDT Plus display assembly
• Flush mount template
• Black strain relief bushing
• Evaporator installation hardware bag
• KDT Plus hardware bag
Wall-Mounted Accessory Kit
• Retractable bottle probe
Ducted Accessory Kit
• Stainless steel bottle probe (50-ft cord)
• (2) ½” x ½” nylon barbed tting
• (1) ½” barbed tee
• (1) Double-D strain relief
• (4) ¾” adhesive cable tie mounts
• (2) Small cable ties
• (4) #8 x 1¾” hex-head screws
• (1) ⁄” OD grommet
• (2) ½” nylon hole plugs
• (4) #6 x 1” PHP zinc Type A screws
• (4) 8-10 x ⁄” blue plastic screw anchors
Main Condensing Unit Box
(1) Filter grille
(1) Condensing unit
Condensing unit accessory kit:
• (1) Filter drier
• (1) Sight glass
(1) Duct plenum
(1) Platinum Evaporator Wall-Mounting Template
Please leave the unit in its original box until you are ready for installation. This will allow you to move the product safely without
damaging it. When you are ready to remove the product from the box, refer to the installation instructions.
TIP: Save your box and all packaging materials. They provide the only safe means of transporting/shipping the unit.
www.whisperkool.com | Page 5
Page 8
QUICK REFERENCE GUIDE
Front / Side View
Evaporator unit
Rear / Side View
Filter grille
Mounting keyholes (4)
REAR VIEW
THROUGH THE WALL
Option 1
Knockout for wiring
Line set knockout
Knockout for drain line
Page 6 | 1-800-343-9463
Line set knockout
INSIDE CELLAR
Option 2
Knockout for drain line
Knockout for wiring
PS 021319
Page 9
WALL-MOUNTED UNIT SPECIFICATIONS
Evaporator unit
Platinum Split
Filter grille
Model
Cellar SizeApprox. 1000 cu. ft., provided cellar is fully insulated and sealed with proper vapor barrier*
BTU/h w/85°F air
entering condenser coil
Dimensions16.1”L x 20.5”W x 15.5”H16.08”L x 16.23”W x 12.61”H
RefrigerantR-134a
HP1.43
Voltage Rating115V (15-amp dedicated circuit required)115V (15-amp dedicated circuit required)
Line SetLiquid line: ¼" ; suction line: ½" (less than 50 ft.), ⁄" (greater than 50 ft.)
Duct Size8" supply, 10" return
Drain Line½” ID clear plastic tubing (not provided)
Installation
Evaporator can be installed up to 25 duct feet away from cellar. Condensing unit can be installed up to
100 line feet from evaporator unit.
8000 Evaporator
(Fan Coil Unit)
(Air-Cooled Condensing Unit)
3788
8000 Condenser
ThermostatAdvanced digital display (50-ft. cable), liquid-temperature-measuring bottle probe (50-ft. cable)
Temp. DeltaCan maintain a 55°F temperature dierential with up to 110°F condenser air intake temperature
WarrantyTwo-year limited warranty (parts and labor)
*Each cellar is unique and has specic cooling requirements. Heat load calculations should always be performed prior to selecting a cooling unit.
Page 10 | 1-800-343-9463
PS 021319
Page 13
Platinum Split
SPLIT SYSTEM CHECKLIST
In order to activate the warranty for this product, the information here must be complete and accurate. Any
incorrect or omitted information will result in a return trip by the installing technician at their cost.
DATA RECORDINGS
NOTE: All readings need to be taken while the compressor is running.
Line Set Information
A. Line set length:
B. Suction line OD:
C. Liquid Line OD:
Bottle Probe
A. Install probe in bottle of warm water to keep system operating.
Charging the System
A. Fill system until bubbles dissipate from sight glass.
NOTE: Be careful not to overcharge the system.
Temperature Dierential at the Evaporator
A. Measure return air and supply air temperatures at the evaporator to ensure adequate cooling of air in cellar.
Sub Cooling
A. Measure head pressure at liquid line king valve. Convert pressure to temp using conversion chart.
B. Temp of liquid line at king valve:
C. Complete sub cooling calculation: A – B =
Superheat
A. Measure suction pressure at the suction line service valve, convert to temp.
B. Measure the temperature of the suction line at the outlet of the evaporator.
C. Complete superheat calculation: A – B =
NOTE: There may be a need to adjust the TXV to get the correct superheat levels.
Compressor Temperature
A. Measure temperature at bottom of compressor.
NOTE: Cool temp may indicate liquid in the compressor.
Voltage and Amp Draw
A. Measure voltage to compressor and amp draw.
Condensation Drain Test
A. Pour water into the drain pan to assure it drains properly.
www.whisperkool.com | Page 11
Page 14
ITEMS TO ROUTE BEFORE INSTALLING THE EVAPORATOR UNIT
1. Route the line set from the condensing unit to the desired evaporator unit installation location.
2. Route the display cable from the desired location to the evaporator installation location (see page 20 for more
display information).
3. Route the bottle probe cable from the desired thermostat bottle location to the evaporator unit installation
location (see page 19 for more bottle probe information).
4. Route the drain line from a proper discharge location to the evaporator unit installation location (see page 18 for
more drain line information).
5. Route the power cable wiring to the evaporator unit installation location.
ITEMS TO ROUTE
55°F
LINE SET
BOTTLE PROBE
DISPLAY CABLE
DRAIN LINE
Page 12 | 1-800-343-9463
POWER CABLE
DISCHARGE LOCATION
PS 021319
Page 15
Platinum Split
PREPARING THE WALL-MOUNTED EVAPORATOR (FAN COIL) UNIT
Required Tools:
• Drill
• ⁄” drill bit
• ¼” socket drill bit
• ¼” wrench
• Phillips-head screwdriver
• Tape measure
• Brazing torch
• Drywall saw
• Ladder
• Level
• Pliers
• Pencil
Drain Pan
1. Remove the knockouts that you will be using to route
the line set, power wires, display cable, bottle probe,
and drain line.
Power
Line set
2. Remove the insulation from the knockout holes.
3. For ease of installation, remove the nine (9) screws
securing the top and remove the top.
Drain line
Bottle probe connector routing location
www.whisperkool.com | Page 13
Page 16
INSTALLING THE WALL-MOUNTED EVAPORATOR UNIT
Refer to the Wall-Mounted Evaporator Unit Installation Template for more information about mounting the wall-mounted
evaporator unit.
1. Locate two (2) wall studs in the desired mounting location spaced 16” on center.
2. Mark vertical lines on each stud 16” apart.
3. Mark an intersecting horizontal line at the desired height of the unit.
4. Make a mark on each stud 13½” down from the intersection of the horizontal and vertical lines.
NOTE: The top of the unit must be installed a minimum of 6” and a
maximum of 18” from the ceiling.
1/8”
WALL
5. Install the four (4) supplied 1¾” hex-head
screws into the studs at the locations marked
leaving ⁄” between the wall surface and
screw head.
6. If routing through a wall, cut out an access
hole for the line set, drain line, display cable, and power wires.
7. Raise the evaporator to the installation location. Align the rear
keyholes with the mounting screws and mount the unit.
8. Using a ¼” wrench or socket, tighten the top mounting screws.
9. Using ¼” and ½” copper tubing, route the liquid and suction lines
through the knockouts in the housing. Be sure to extend the
tubing far enough outside of the housing to extend through the
wall if necessary. NOTE: ½” copper tubing will slip over the ⁄”
suction line on the evaporator for an easy connection.
10. Remove the solenoid coil and wrap the solenoid valve in a wet rag
to prevent overheating.
11. To prevent oxidation, purge the system with nitrogen.
12. Braze the copper tubing to the connections on the evaporator
unit.
STUD
Page 14 | 1-800-343-9463
PS 021319
Page 17
Platinum Split
13. Insulate the suction line using Armaex or similar insulation.
14. Using the cable ties and cable tie mounts provided, secure the
drain line to the bottom of the housing to ensure a downward
slope.
15. Route the power wire, bottle probe connector, and display cable
into the unit through the knockouts.
16. Remove the wire nuts from the black, white and green wires
located in the lower left corner of the evaporator unit.
17. Connect the green wire to the green wire, the black wire to the
black wire, and the white wire to the white wire.
18. Install the supplied black strain relief to secure the power supply
wires in the housing.
19. Connect the display cable labeled “UNIT” to the wire labeled
“UNIT” located in the bottom of the evaporator compartment.
UNIT
UNIT
Figure 1
20. Secure all wiring neatly and as close to the left wall as
possible in order to minimize airow obstruction.
21. Attach the supplied bottle probe to the circular
connector on the bottom of the unit (see Figure 1).
Follow the directions on page 19 for correct installation
and placement of the bottle probe.
22. Seal the gaps around the display cable, bottle probe
cable, and power wire knockouts using the supplied
three-inch pieces of cork tape. (For best results, install
the cork tape inside of the unit.)
46375
www.whisperkool.com | Page 15
Page 18
PREPARING THE FULLY DUCTED EVAPORATOR UNIT
1. Remove the knockouts that you will be using
Power
Line set
Drain line
to route the line set, power wires, display cable,
bottle probe, and drain line.
2. Remove the insulation from the knockout holes.
3. For ease of installation, remove the nine (9)
screws securing the top and remove the top.
4. Follow the directions on page 20 to mount the
remote display and run the display cable to the
evaporator unit.
NOTE: For every 90° bend in the ducting,
the system loses 13 CFM of airflow.
Bottle probe connector routing location
Page 16 | 1-800-343-9463
PS 021319
Page 19
INSTALLING THE FULLY DUCTED EVAPORATOR
1. Using ¼” and ½” copper tubing, route the liquid and suction
lines through the knockouts in the housing. Be sure to extend
the tubing far enough outside of the housing to extend
through the wall if necessary. NOTE: ½” copper tubing will
slip over the ⁄” suction line on the evaporator for an easy
connection.
2. Remove the solenoid coil and wrap the solenoid valve in a
wet rag to prevent overheating.
3. To prevent oxidation, purge the system with nitrogen.
4. Braze the copper tubing to the connections on the
evaporator unit.
5. Insulate the suction line using Armaex or similar insulation.
6. Using the cable ties and cable tie mounts provided, secure
the drain line to the bottom of the housing to ensure a
downward slope.
7. Route the power wire, display cable, and the bottle connector
through the knockouts.
8. Remove the wire nuts from the black, white, and green wires
located in the lower left corner of the evaporator unit.
9. Connect the green wire to the green wire, the black wire
to the black wire, and the white wire to the white wire.
10. Install the supplied black strain relief to secure the power
supply wires and bottle probe wire in the housing.
11. Connect the display cable labeled “UNIT” to the wire
labeled “UNIT” located in the bottom of the evaporator
compartment.
UNIT
12. Secure all wiring neatly and as close to the left wall as
possible in order to minimize airow obstruction.
13. Attach the supplied bottle probe to the circular
connector on the bottom of the electrical panel. (See
Figure 1.) Follow the directions on page 19 for correct
installation and placement of the bottle probe.
14. Seal the air gaps around the display cable, bottle probe
cable, and power wire knockouts by installing the
supplied three-inch pieces of cork tape. (For best results,
install the cork tape inside of the unit.)
Platinum Split
UNIT
46375
Figure 1
www.whisperkool.com | Page 17
Page 20
DRAIN LINE
Condensation Drain Line (not provided, but required)
The condensation drain line tube moves excess condensation from the evaporator unit to a proper discharge
location. It is important for the drain line tube to be properly connected in order to prevent leakage and other problems associ-
ated with excess condensation.
Failure to use the condensation drain line tube will void the warranty on the unit.
Drain Line
All systems come with a drain line connection tee and two 90-degree fittings. The unit is equipped with a ½” OD barbed fitting
coming from the drip tray. (NOTE: ½” ID clear PVC tubing will need to be purchased and installed by the installing technician.)
Installation of the drain line is mandatory, whether it leads through the wall and out of the cellar or remains inside the cellar.
During operation, the cooling system will strip excess water from the air in order to maintain the proper level of humidity within
the cellar. However, in extreme humidity, additional condensate will be removed; thus the drain line will prevent overflow and
leakage by discharging the excess condensate.
Routing the tubing out of the unit:
Cut a small piece of ½” tubing and connect one
end to the drip tray port and the other to a
90-degree fitting. (This will direct the tubing
toward the back of the unit where the tube will
exit the unit.) Be sure to extend the tubing far
enough outside the housing to extend through
the wall if necessary.
If routing out of the rear: Cut a piece of tubing
long enough to protrude out of the knockout on
the back side of the unit.
If routing out of the bottom: Cut a piece of
tubing long enough to reach the knockout in
the bottom of the unit and install the supplied
90-degree fitting. (This will direct the tubing out
of the bottom of the unit without the risk of
kinking the tubing.) DO NOT USE TEE WHEN
ROUTING OUT OF THE BOTTOM.
Routing to discharge location if routed out
of the bottom:
Connect the drain line directly to the second
90-degree barb fitting previously installed. Route
the drain line to an appropriate drain location.
No tee is required if draining through the
bottom of the unit.
Routing to discharge location if routed out of the rear:
Insert the middle barb of the barbed tee fitting into the end of the drain
line coming from the evaporator. Rotate fitting so tee is in the orientation
shown in the diagram below. Connect a 3-inch piece of ½” drain line to
the barb on top. Connect the remaining “long” piece of drain tubing to
the bottom barb of the tee. Route the drain line to an appropriate drain
location.
NOTE: The fitting should be placed
vertically with the 3” cutout facing
up.
Failure to install the drain line
voids the warranty.
To prevent mold from growing,
allow the drain line to hang
above the water line.
WRONG: Drain line is under water.
Page 18 | 1-800-343-9463
PS 021319
Page 21
Platinum Split
LIQUIDMEASURING THERMOSTAT SYSTEM BOTTLE PROBE
WhisperKOOL cooling units come with a liquid-temperature-measuring thermostat. The self-calibrating probe contains a sensor chip, which communicates back and forth with the thermostat. This results in a consistent temperature
setting and accuracy. Wine should be kept at a very precise, controlled temperature and humidity. By measuring the
liquid temperature rather than air, the unit will operate 75–80% of the time.
Setting up the Bottle Probe:
1. Locate an empty wine bottle.
2. Fill it 75% full with room-temperature tap water.
3. Place bottle probe securely into bottle as seen in Figure 1.
4. Place bottle off to the side of the unit in your wine cellar, with the probe level.
5. To ensure a consistent temperature, place bottle probe approximately three
(3) feet away from the air output and not in the flow of the air.
It is recommended that the bottle be placed in a central location of your
wine cellar. Avoid pulling too much on the probe cord. It may become
disconnected resulting in limited functionality of the unit.
NOTE: The thermostat can be set between 50–70°F.
Remember: The unit operates based on the temperature of the water.
Do not be misled by thermostats reading air temperature. The air temperature
in the cellar will be cooler than the liquid temperature of the wine while it is
reaching the optimum balanced temperature.
What’s included: Display panel, wall mount bracket, ush mount bracket, ush mount template
55°F
TOP
Display panelWall mount bracketFlush mount bracket
Flush mount template
WALL MOUNT BRACKET INSTALLATION
1. Place the bracket on the wall. Use a level to ensure that the bracket is level. Using a pencil, mark the four screw
holes in the rear of the bracket.
Page 20 | 1-800-343-9463
NOTE: Cut hole in the location shown for routing the display cable.
PS 021319
Page 23
Platinum Split
WALL MOUNT BRACKET INSTALLATION, CONTINUED
2. Using a drill with a ⁄” bit, drill four holes in the drywall for the screws. Insert the four (4) provided drywall anchors
into the drywall, then tap them in with a hammer until they are ush with the wall.
3. Place bracket against wall, aligning screw holes with drywall anchors. Insert the four supplied Phillips-head screws
into the drywall anchors. Tighten the screws to secure the bracket to the wall.
www.whisperkool.com | Page 21
Page 24
WALL MOUNT BRACKET INSTALLATION, CONTINUED
NOTE: Before you continue to Step 4, locate the area where the display will be mounted. You may route the display wire
into the housing one of three ways: either through the wall or through one of the holes on the top or bottom edges of
the wall mount bracket. If you’d like to route the display cable through one of these holes, place a rubber grommet into
the hole and then route the display cable through the grommet and into the wall mount bracket.
4. Connect the end of the display cable labeled “DI S PL AY” to the JST connector on the back of the display.
JST connector
DISPLAY
Display
Wall mount
bracket
5. Place the display on the wall mount bracket as shown, attaching the back of the display panel to the magnets on the
mounting bracket. Make sure that the alignment tab on the back of the display panel sits in the notch on the bottom
of the bracket.
Page 22 | 1-800-343-9463
PS 021319
Page 25
FLUSH MOUNT BRACKET INSTALLATION
Platinum Split
1. Square the ush mount template on the wall
using a level. Then draw a 3” line along the
bottom edge of the template.
TOP
2. Peel the backing o the template and stick it to the wall,
aligning the bottom edge with the line drawn in Step 1.
TOP
Pencil line
3. Use a ⁄” drill bit to drill a hole in the center of
each cross (+).
4. Cut along the perforated lines. When nished, remove
template from wall.
TOPTOP
Saw
www.whisperkool.com | Page 23
Page 26
FLUSH MOUNT BRACKET INSTALLATION, CONTINUED
5. Remove the backing from the double-sided tape on the ush mount bracket.
6. Align magnets with previously drilled holes. Make sure the cut-out portion of the bracket (circled below) is on the
bottom. Press the bracket rmly against the wall.
WALL
HOLE
CUTOUT
Page 24 | 1-800-343-9463
PS 021319
Page 27
FLUSH MOUNT BRACKET INSTALLATION, CONTINUED
7. Connect the end of the display cable to the JST connector on the display panel.
DISPLAY
Platinum Split
DISPLAY
BRACKET
8. Place the display on the ush mount bracket as shown, attaching the back of the display panel to the magnets on
the mounting bracket. Make sure that the alignment tab on the back of the display panel sits in the notch on the bottom of the bracket.
WALL
www.whisperkool.com | Page 25
Page 28
PLATINUM SPLIT EVAPORATOR WIRING DIAGRAM
RED
115V LINE
115V NEUTRAL
GROUND
BLACK
WHITE
GREEN
14
14
WHITE
BLACK
WHITE
WHITE
(1)
(4)
BLUE
WHITE
Solenoid
Ref.
GREEN
14
14
GREEN
BLACK
WHITE
FV-30VQ3
Page 26 | 1-800-343-9463
PS 021319
Page 29
4000/8000 CONDENSING UNIT WIRING DIAGRAM
Platinum Split
www.whisperkool.com | Page 27
Page 30
COPELAND COLD WEATHER START KIT WIRING DIAGRAM
For systems manufactured after October 31, 2018
COPELAND CWSK
N
1234
5
H
1234
Black
Black
HEATER
5
TS
Page 28 | 1-800-343-9463
PS 021319
Page 31
Platinum Split
PREPARING THE CONDENSING UNIT
Electrical Needs
The 4000 condensing unit requires a dedicated 115V, 15-amp circuit. The 8000 condensing unit requires a dedicated 115V, 20amp circuit. The unit draws a large inrush current for about 1 second the instant the compressor starts. With a dedicated circuit
and circuit breaker, the condensing unit will have sucient power for eective operation. (The compressor is controlled by a lowpressure transducer mounted on the condensing unit. This feature eliminates the need for wiring between the evaporator unit
and the condensing unit.)
• Ensure the voltage supplied matches the rating specied on the unit spec label.
• Provide a non-GFI dedicated circuit and an appropriate outlet for the evaporator unit.
• Provide a dedicated circuit and circuit breaker for the condensing unit.
• Provide a weatherproof disconnect for the condensing unit if it is located outside.
Power surges and spikes can damage sensitive electrical equipment. WhisperKOOL recommends plugging the unit into a surge
protector or power conditioner in order to protect your system. As outlined in our terms and conditions, power surges and spikes
are not covered under warranty.
WE RECOMMEND THAT YOU DO NOT USE A GROUND FAULT INTERRUPTER (GFI) WITH THIS PRODUCT.
In case the system should lose power, check the home/main circuit breaker. If the system does not respond properly, refer to the
Troubleshooting Guide on page 47.
www.whisperkool.com | Page 29
Page 32
INSTALLING THE CONDENSING UNIT
The condensing unit can be installed inside a well-ventilated area of the home, but is typically installed outside. Exterior
applications will require the use of a protective housing. The amount of sun exposure should be considered when selecting
the placement of the condensing unit .The 4000 condensing unit requires a dedicated 15-amp circuit (non-GFI). The 8000
condensing unit requires a dedicated 20-amp circuit. Make sure there is a minimum of three (3) feet of horizontal clearance in
every direction around the unit (ve feet is ideal). The unit may either be hard-wired or plug-in, depending on local electrical
codes.
Indoor condensing unit installations: Inside installations require special consideration, as there must be adequate
ventilation to remove the heat created during normal operations. An exhaust port with fan may need to be installed to
ensure that heat is eectively removed from the utility room. There must be a return grille or provision for 500 - 600 CFM
of cool air to enter the room to replace the exhausted air. Unobstructed airow to and from the unit is a critical factor in
the unit’s overall performance. Make sure there is a minimum of three (3) feet of horizontal clearance in every direction
around the unit (ve feet is ideal). This will assure that the unit can move the air around the room in an ecient manner.
Outdoor condensing unit installations: You must utilize the exterior condensing unit housing for outdoor installations.
Place the condensing unit on a solid foundation in a location with adequate ventilation. Make sure there is a minimum
of three (3) feet of horizontal clearance in every direction around the unit (ve feet is ideal). The unit should be
elevated 18 inches in order to avoid any possible ooding or damage by animals, and should be clear of leaves, dirt, and
other debris.
Page 30 | 1-800-343-9463
PS 021319
Page 33
PLATINUM SPLIT WIRING PROCEDURES
Copeland Wiring Procedure
1. Locate or install an electrical outlet near the condensing unit.
2. Follow the instructions listed below to wire the condensing unit.
3. Leave the circuit breaker o until the unit is ready to charge.
NOTE: Do not apply power to a system without refrigerant.
Platinum Split
Use a ¼” nut driver to remove the screw securing the cover to the
compressor electrical compartment.
Step #
0
www.whisperkool.com | Page 31
Page 34
Copeland Wiring Procedure
Step #
1
Remove the cover to expose the internal wires.
Copeland Wiring Procedure
Step #
2
Route the required 115V power wires into the open
clamp on the enclosure.
Page 32 | 1-800-343-9463
PS 021319
Page 35
Platinum Split
Copeland Wiring Procedure
Tighten the screws on the clamp to secure wire casing or
conduit in place.
Step #
3
Copeland Wiring Procedure
Perform the following wire connections:
• Insert the Line 115V wire into the “H” lever connector
• Insert the Neutral 115V wire into the “N” lever connector
• Insert the Ground wire into the “G” lever connector
Step #
4
www.whisperkool.com | Page 33
Page 36
Copeland Wiring Procedure
Step #
5
Push wires back into enclosure.
Copeland Wiring Procedure
Step #
6
Re-install cover.
Page 34 | 1-800-343-9463
PS 021319
Page 37
LINE SET PIPING DIAGRAMS
EXAMPLE
It is required to size the suction line tubing according to this chart.
Platinum Split
Platinum 4000/8000
Suction Line
Liquid Line
Condensing Unit Installed Below Fan Coil
Line Set Length<25ft26-50ft50-100ft
Vertical Rise15ft<3ft3-10ft>10ft<3ft3-10ft>10ft
Horizontal Tubing½”⁄”
Vertical Rise½”½”
Horizontal Tubing¼”⁄”
Vertical Rise¼”
Option 1
Condensing Unit Installed More Than 3’ Above Fan Coil
Option 2
NOTE: If the condensing unit is located
above the fan coil unit, a P-trap must be
used on the suction line at the base of the
vertical lift and an inverted P-trap must be
used at the top of the vertical lift to ensure
proper oil return for the compressor.
www.whisperkool.com | Page 35
Page 38
INSTALLING THE CONDENSING UNIT
DO NOT BLOCK airow through the
exterior housing. This will restrict
Refrigerant Piping Overview
• Using the charts and illustrations found above, route the line set between the evaporator unit and condensing unit. Be sure to
reference the chart for correct line set sizing. All horizontal suction piping should be pitched toward the condensing unit half
an inch for every 10 feet of pipe. When installing and routing the line set, cap both ends of each tube to prevent debris from
entering the tubing.
• Prior to connecting the piping to the evaporator and condensing units, loosely connect a refrigerant manifold to the suction
and liquid line service valves.
• Purge the hoses with dry nitrogen and tighten the hose connections.
• Remove the service valve caps and turn the valve stem clockwise half a turn to unseat the valve and open the service
port. Keep the piping ports sealed until ready to braze.
• Purge the ttings with dry nitrogen at a slow rate to prevent formation of highly abrasive copper oxide.
• Perform all brazes.
• Pressure test the system and check for leaks.
• Insulate the suction line using wall cellular insulation or equivalent. Seal all seams with Armaex 520 Foam Insulation
Adhesive or equivalent. Wrap each seam using line set tape.
Liquid Line Piping Procedure
• Refer to the line set piping chart for liquid line size requirements.
• Braze a short piece of copper tubing to the liquid line service valve.
• Connect the supplied refrigerant drier to the tubing.
• Downstream from the drier, connect the moisture-indicating sight glass in an easily visible location.
• Run the tubing to the evaporator unit and attach to the liquid line connection on the evaporator unit.
airow andvoidthe warranty.
Suction Piping Procedure
• Connect an appropriately sized suction line to the suction line service valve on the condensing unit.
• Run the pre-insulated suction line to the evaporator unit and attach to the suction line connection on the evaporator unit.
Brazing Procedure
• Connect the bottle probe to the evaporator unit.
• Fill a wine bottle 75% full of room-temperature water. Insert the bottle probe into the neck of the bottle as far as possible. It is
important that the bottle probe stopper be compressed by the neck of the bottle to ensure water will not leak.
• Energize the evaporator unit and set the controller to call for cooling.
• Verify that the setpoint on the control is set low enough to allow the unit to run for the entire length of the brazing,
evacuation, and charging procedure.
• Remove the valve depressors from the gauge hoses on a four-valve manifold.
• Connect the manifold to the low-pressure service valve port on the condensing unit and a nitrogen tank.
• Open the suction line service valve and purge the system with nitrogen.
• Braze all connections and cool o quickly.
• Connect the high-pressure hose from the manifold to the liquid line service valve port.
• Pressure test the system at 150 psi for 20 minutes.
• Check all braze joints with leak detector or soap bubbles.
• Release the nitrogen once it is conrmed that there are no leaks.
Evacuation
• Remove the nitrogen tank from the manifold and attach the manifold to the refrigerant tank.
• Mid-seat both service valves.
• Install service caps on the valves.
• Energize the liquid line solenoid valve.
• After conrming that there is fresh oil in the vacuum pump, connect the ⁄” hose from the manifold to the pump.
• Start the pump and run it until the micron gauge on the evaporator unit reads 500 microns or less.
• Disconnect the vacuum pump from the system.
• Break the vacuum by pressurizing the system to approximately 5 PSI with R-134a refrigerant.
• Remove the micron gauge from the access valve.
Page 36 | 1-800-343-9463
PS 021319
Page 39
Platinum Split
INSTALLING THE CONDENSING UNIT (continued)
Charging
• With the power o to the condensing unit, admit liquid refrigerant through the liquid line service valve until the refrigerant
stops owing.
• Turn on the circuit breaker for the condensing unit. The compressor should turn on if the pressure in the suction line is above
25 psi.
• Add refrigerant (in vapor form) to the low side of the system through the suction line service port.
• Observe the sight glass. If bubbles are present, add more refrigerant (in vapor form) to the low side.
• Once the sight glass is clear, check the superheat at the outlet of the evaporator unit. Adjust the TXV until the superheat is
between 20-30°F at the service valve.
• Under normal operation, with the wine cellar at 55°F and the ambient temperature at 85°F, the low side pressure should be
between 28-32 PSI and the high side should be between 145-155 PSI.
Finalizing the Installation
• Conrm that the entire suction line from the TXV to the suction line service valve is insulated using cellular insulation or
equivalent. Seal all seams with Armaex 520 Foam Insulation Adhesive or equivalent.
• Conrm that the control is displaying the correct temperature and that no alarms are present. Refer to page 43 for corrective
action if alarms are present.
Charging Information
A. Energize the solenoid valve on the evaporator unit by plugging the unit in and adjusting the thermostat to call for cooling.
www.whisperkool.com | Page 37
Page 40
INSTALLING THE WALL MOUNT KIT
1. If removed, reinstall the top panel of the unit housing.
2. Connect the red wire from the display cable to the upper (+) terminal on the display located on the front grille.
3. Connect the black wire from the display cable to the lower (-) terminal on the display. NOTE: Display cable is packaged with
the accessory kit, not with the evaporator.
4. Align the front grille with the four (4) ball studs on the housing. Push the front grille onto the ball studs until it snaps into
place.
5. Using a Phillips-head screwdriver, fasten the bottom two (2) screws to fasten the grille to the unit.
DRAIN PAN
INSTALLING THE DUCTED PLENUM
1. If removed, reinstall the top panel of the unit housing.
2. Align duct plenum with the four (4) ball studs on the housing. Push the duct plenum onto the ball studs until it snaps into
place.
3. Using a Phillips-head screwdriver, fasten the bottom two (2) screws to fasten the plenum to the unit.
4. Connect the supply and return duct work to the unit.
5. Using duct tape or foil tape, seal the seam between the plenum and unit.
6. Insulate all exposed metal on the unit to prevent surface condensation.
NOTE: Max ducting length is 25 feet.
NOTE: A 12” x 12” return air lter grille must be installed to prevent contaminants from entering the cooling system. Supply duct
must be insulated so it does not sweat or pick up heat.
Page 38 | 1-800-343-9463
PS 021319
Page 41
SYSTEM OPERATION
Platinum Split
Initial Start-Up
When the unit is plugged in and power is sent to the
controller, a beep will sound, conrming that the controller is
getting power. All LEDs on the display will blink three times.
Three dashes will then appear on the screen. All display LEDs will
then blink three times. Once the controller has gone through
the initial startup process, and all LEDs have cycled, the home
screen will be displayed.
Setpoint
The setpoint is preset at the factory to 55°F. It can be adjusted by
the customer between 50–70°F in one-degree increments.
Indoor Fan Operation
The indoor fan will run when the controller is calling for cooling
and turn o once the cooling cycle has ended. During the
cooling cycle, the system will remove some relative humidity
from the cellar. Some of the humidity that was removed can be
reintroduced into the cellar by adjusting the “fan on” and “fan o”
functions. (The cooling system is not equipped with a humidier
and does not add humidity.)
The FOF cycle should be shortened rst. This will reduce the
amount of time that the fan remains o following a cooling cycle.
When the unit has completed a cooling cycle, the compressor
and the condenser fan will turn o, but the indoor fan will
continue to run for whatever length of time the customer has
set. The Fon function may then be lengthened to allow the fan
to run longer and reintroduce moisture from the evaporator coil
back into the wine cellar.
For more information about fan settings, refer to the User Menu
on page 44.
Anti-Short Cycle
The Anti-Short Cycle ensures that the unit will remain o for a
period of ve minutes after the unit has reached the setpoint.
This allows the pressure in the refrigeration system to equalize
prior to starting the compressor.
The compressor will remain o until the evaporator coil reaches
40°F, or for a maximum of one hour. The unit will then return to
normal operation.
Operation in Low Ambient Temperatures
The condensing unit comes equipped with a LAC (Low Ambient
Control). The LAC is a three-way modulating valve that responds
to discharge pressure. When the discharge pressure falls below
the valve’s dome pressure, the valve modulates open to the
discharge port which allows discharge gas to bypass the
condenser. Mixing the discharge gas with the liquid creates high
pressure at the condenser outlet, reducing the ow and causing
liquid to backup in the condenser. Flooding the condenser
reduces the area available for condensing. This reduction in
condenser surface area results in a rise in condensing pressure
during cold ambient conditions.
The condensing unit controller is preset at the factory. The cutin pressure is preset to 25psi and the cut-out pressure at 15psi.
During low ambient temperatures (40°F or below), it will be
necessary to adjust the cut-in pressure to 10-15psi (15psi is
preferred) and the cut-out to 5psi to ensure compressor startup.
See page 44 for instructions on adjusting the cut-in and cut-out
pressures of the condensing unit.
Digital Display
The display is designed to give the user the ability to adjust
the setpoint, Fon/FOF parameters, and other settings. (See
User Menu on page 43 for more details.) The bottle probe
temperature is displayed by default. “dEF” will be displayed
during an Anti-Frost Cycle. The bottle probe and evaporator
probe temperatures can be accessed by pushing the SET button
and scrolling through “Pb1” (bottle probe) and “Pb2” (evaporator
probe). The light button may be used as an unlock button.
Safety Features
In the event of a faulty bottle probe, the compressor will cycle
o for 10 minutes and on for 40 minutes. “E1” will be displayed
on the screen.
Once the solenoid relay is de-energized, the controller must
wait ve minutes before reenergizing the relay. This prevents
the compressor from repeatedly turning o and on. If the unit
is calling for cooling during this time, the compressor icon will
blink, indicating that cooling is needed but the controller is
waiting for the Anti-Short Cycle delay.
Anti-Frost Cycle
When the evaporator probe senses a temperature of 26°F for
a duration of one minute, an Anti-Frost Cycle will be initiated.
This will shut down the compressor, allowing the evaporator fan
to run and melt any frost accumulation on the coil. While the
Anti-Frost Cycle is running, “dEF” will be displayed on the screen.
Alarms
See “Alarm Codes” in the Controller Functions chart.
www.whisperkool.com | Page 39
Page 42
°
F
°
F
DISPLAY LAYOUT
Return to Previous
Menu
View/Change Setpoint
Enter User Menu
(hold for 3 sec)
Compressor is on
Fan is on
Anti-Frost Cycle running
55°F
Alarm is present
Scroll Button
Change Setpoint
Scroll Button
Change Setpoint
Power On/O
Page 40 | 1-800-343-9463
Unlock Button
(hold for 1 sec)
PS 021319
Page 43
55°F
55°F
55°F
CONTROLLER FUNCTIONS
ButtonNormal Functions
Platinum Split
INITIAL STARTUP
UNLOCKING THE
DISPLAY
ON/OFF
UP/DOWN
SET
When the unit is plugged in and power is sent to the controller, a beep will sound, conrming
that the controller is getting power. All LEDs on the display will blink three times. Three dashes
will then appear on the screen. All display LEDs will then blink three times. Once the controller
has gone through the initial startup process, and all LEDs have cycled, the home screen will be
displayed.
Press and hold any button for one second to unlock the display. (A white LED will appear in the
top left corner of the button being pressed.) A beep will sound, signifying that the
display is unlocked. NOTE: The display must be unlocked before any button functions become
available.
To turn the unit ON, press and hold the ON/OFF button until the red LED turns OFF.
To turn the unit OFF, press and hold the ON/OFF button until the red LED turns ON.
The up and down arrows are used to navigate through menus and adjust parameters such as
setpoint, Fon/FOF, etc.
• To change the setpoint, press the SET button. When “SEt” is displayed on the screen, press
the SET button once more. Use the UP and DOWN ARROW buttons in order to change the
value until the desired setpoint is reached.
• The SET button allows you to view the setpoint, evaporator temperature, bottle temperature, alarms, and the hidden menu.
• Press the SET button once. “SEt” will be displayed. Press the UP or DOWN ARROW buttons
to scroll through ALr, Pb1, or Pb2.
ESC
LIGHT
SetSetpoint
AlrAlarm folder
Pb1Liquid (bottle probe) temperature
Pb2 Evaporator coil temperature
• Press the SET button again to view any of these values.
• Hold the SET button for approximately 5 seconds to enter the User Menu. (More informa-
tion about the User Menu is available on page 44.)
• Other parameters in the User Menu which are not available for adjustment include: idF,
rEL, and LAn.
This button conrms changes made to parameters such as the setpoint and returns you to the
previous menu.
The light function is not in use. However, this button can still be used to unlock the display.
www.whisperkool.com | Page 41
Page 44
ICON GLOSSARY
IconMeaning
SNOWFLAKE
Blinking: The unit is calling for cooling, but must wait ve minutes before restarting the com-
pressor. This ve-minute delay serves as an Anti-Short Cycle for the compressor’s
protection.
Constant: The unit is in cooling mode and the condensing unit is running.
DRIPPING SNOWFLAKE
FAN
ALARM
The unit is undergoing an Anti-Frost Cycle. While the Anti-Frost Cycle is running, “dEF” will be
displayed on the screen. See System Operation page for further details.
The evaporator fan is running.
The alarm icon is shown when the unit encounters an issue that needs attention. Alarm codes
are explained on the following page. All temperature-related alarms are blocked for the rst
10 hours after the unit is plugged in to allow the system to stabilize and acclimate to the new
environment.
Page 42 | 1-800-343-9463
PS 021319
Page 45
WHISPERKOOL CONTROLLER ALARM CODES
CodeCauseSolution
The following alarm codes will be displayed on the screen along with the alarm icon.
Bottle probe is not connectedAttach bottle probe to circular connector
Faulty bottle probe connectionLocate faulty bottle probe connection by inspecting all wiring connections
between the bottle probe and the circuit board. The two-pin connector for the
bottle probe should be connected to the CPB/PB1 terminal on the circuit board.
E1
Defective bottle probeReplace the bottle probe
If it is not connected, plug it in. If a faulty connection has been identied, correct
the issue or contact customer service for further assistance.
NOTE: The E1 code will not appear in the alarms menu. It will be permanently
displayed on the screen.
Platinum Split
E2
E7
E10
EA
AH1
AL1
Ad2
Faulty evaporator probe
connection
Defective evaporator probeReplace the evaporator probe
No communication between
keypad and circuit board for 60
seconds
Clock battery is deadReplace battery
The following alarm codes will not be displayed on the home screen. However, the alarm icon
will be displayed in the event of an alarm. The alarms can be viewed in the Set Menu’s ALr folder.
Unit is not draining properly1. Check to see that the unit is level; if not, level it
The bottle probe is sensing a
temperature that is 8°F above the
setpoint
The bottle probe is sensing a
temperature that is 8°F below the
setpoint
The Anti-Frost Cycle ended on
time-out
Locate faulty evaporator probe connection by inspecting evaporator probe wire.
The two-pin connector for the evaporator probe should be connected to the
CPB/PB2 terminal on the circuit board. If it is not connected, plug it in.
Verify that the display cable is connected to the keypad and the circuit board and
is not damaged, frayed, or kinked. If problem persists, contact Customer Service
for troubleshooting information.
NOTE: A dead clock battery will not aect the operation of your cooling unit.
2. Verify that the drain line is not clogged; if so, clear obstruction
3. Ensure that the condensate pump is operating
4. Verify wire connection at D.I. port of circuit board
NOTE: If the drain line is obstructed or the pump fails for some reason, and the
water level in the drip tray gets too high, the unit will not operate until the water
in the internal drip tray drops back below the proper level.
1. Allow time for the wine to reach the desired temperature
2. Ensure that the cellar is sealed properly
3. Verify that the bottle probe is calibrated correctly (refer to the User Menu on
the following page)
4. Verify that the unit is sized correctly for the cellar
1. Make sure the unit is not in cooling mode (the snowake icon will not be
illuminated)
2. Add heat to the room until the wine reaches the desired temp
3. Verify that the bottle probe is calibrated correctly (refer to the User Menu on
the following page)
1. Check the evaporator coil for ice buildup. Unplug the unit and allow the coil to
thaw before restarting.
2. Make sure the room to which the unit is exhausting is not below 60°F
3. If the unit repeatedly goes into Anti-Frost Cycles (one per minute), call
Customer Service for more troubleshooting information
www.whisperkool.com | Page 43
Page 46
USER MENU
The User Menu is accessed by pressing and holding the SET button for 3 seconds. Use the UP and DOWN ARROW
buttons to navigate to desired parameters. Press the SET button again to view these parameters. Press the UP and
DOWN ARROW buttons to adjust a parameter.
The following parameters are available in the menu:
ParameterDescription
Fdc - humidity enhancementThis parameter is measured in minutes, and is preset at the
factory to 1. An increase in this parameter will increase the humidity
enhancement of your cellar. This parameter should not be adjusted
to zero. Adjustments should be made in increments of 5, with a
maximum of 15 and a minimum of 1. After making any adjustments
to humidity enhancement, you should wait a minimum of 3 days
before making any additional adjustments. This will allow sucient
time for the cellar to acclimate to the new setting.
FOF - “fan o”This setting controls how long the fan stays o after the setpoint
has been reached. It is preset to 15 minutes. This setting should
not be adjusted, as most properly constructed wine cellars retain
an ample amount of humidity during the “fan o” cycle. If, however,
you wish to decrease the duration of the “fan o” cycle (in order to
increase the wine cellar’s relative humidity), you can adjust this
setting in the User Menu.
Fon - “fan on”The “fan on” time is preset to zero minutes. This keeps the relative
humidity of the wine cellar at a stable level. If, however, you wish
to raise the relative humidity of your wine cellar, you can increase
the duration of the “fan on” cycle in increments of ve (5, 10, or 15
minutes). After making any adjustment to the “fan on” cycle, you should wait a minimum of 3 days before making any additional
adjustments. This will allow sucient time for the cellar to acclimate
to the new setting.
CA1 - bottle probe (Pb1) calibrationCA1 - bottle probe (Pb1) calibration: You may use this parameter
to calibrate the bottle probe to a known temperature. This parameter can be adjusted between -12°F and 12°F. For example, if the
bottle probe temperature is 58°F, and the known temperature is
55°F, you can set the CA1 parameter to -3°F to match the known
temperature.
PA2 - installer menuThis menu is only accessible using a password and is not available
for adjustment.
dOA - digital inputThis setting determines which of the unit’s components will be
activated or deactivated when a certain electrical relay is activated
or deactivated in response to an alarm. The controller comes preprogrammed with a factory setting of 2.
Page 44 | 1-800-343-9463
2 = activates the compressor and fans
5 = disables the compressor and fans
NOTE: Setting the dOA to any number other than 2 or 5 will prevent
the unit from operating properly.
PS 021319
Page 47
Platinum Split
Emerson™ Electronic Unit Controller
Quick setup and troubleshooting guide
Adjusting Low Pressure Settings
Hold DOWN and SET simultaneously for 3 seconds
to enter menu (PSI light will ash)
Cycle through menu options – UP/DOWN
Select function – SET
Adjust value – UP/DOWN
Store function - SET
Exit menu - UP and SET
Low Pressure Cut-In Low Pressure Cut-Out
Accessing Alarm Code Information
Press and release ALARM
Cycle through menu options – UP/DOWN
Press SET to see number of alarms
Press SET again to return to menu options
Book of Alarms –
to enter alarm menu
Compressor
Fan light 1 & 2
(Fan cycle units only)
+
Module Restart –
push to reset
the HPL, DLL
lock out faults
(cycle power)
Set – Displays
+
set point. In
programming
mode, it con rms
an operation
When light is on, feature or component is on or active
Alarm
history
Active
alarm
Run
time
Service – to enter
service menu
Service
menu
Accessing Service Menu
Hold SERVICE for 3 seconds
Cycle through menu options – UP/DOWN
Press SET to see number of alarms
Press SET again to return to menu options
Exit menu - UP and SET
AlarmDescription
PoFKeypad locked
PonKeypad unlocked
P1Suction probe failure
P2Condenser probe failure
P3DLT probe failure
HAHigh condenser temperature alarm
dLtDLT temperature alarm
dLLDLT lock alarm
HPHigh pressure trip alarm
HPLHigh pressure trip lock-out alarm
EEModule Failure
LOCNumber of lock-outs
Note: After 15 seconds of inactivity the controller will revert
to the default display.
Example: If StH=12 and StL=500, the total number of compressor starts=12,500
For more information visit
EmersonClimate.com/ElectronicUnitController
or call 1-888-367-9950
www.whisperkool.com | Page 45
Page 48
DisplayLikely CausesOther Possible Causes
Controller display remains
blank after applying power
Controller displays correctly,
but the green compressor
light is off and the
compressor is not running
Controller displays correctly
and the green compressor
light is on and the
compressor is not running
Controller ashes “135” or
“P1”
Controller ashes “P2” on a
unit with fan cycling
Controller ashes “P2” on
a unit without fan cycling
after replacing a controller
Controller ashes “P3” on a
unit with DLT
Controller ashes “P3” on
a unit without DLT after
replacing a controller
Fans not running on a fan
cycling unit and the fan
lights are not on
Fans not running on a fan
cycling unit and the fan
lights are on
Controller ashes “HP” at
power-up
Controller ashes “HP” or
“HPL”
Controller ashes “DLT” or
“DLL”
Controller ashing “HPL”
or “DLL”
• Unit power not properly applied - check for proper applied voltage
• Power cable harness not plugged in properly or securely into the
back of the controller – check connections
• Jumper cable not plugged in properly or securely into the back of
the controller – check connections
• Controller is currently above the cut-in setting – check cut-in and
cut-out settings
• Power cable harness not plugged in properly or securely into the
back of the controller – check connections
• Current system pressure is above 135 PSIG – wait for system to
pull down
• Green harness not plugged in properly or securely into the back
of the controller – check connections
• Cable not connected properly with the pressure transducer –
check connections
• Green harness not plugged in properly or securely into the back
of the controller – check connections
• Controller not programmed properly – check parameters in the
advanced menu
• Jumper cable not plugged in properly or securely into the back of
the controller – check connections
• Controller not programmed properly – check parameters in the
advanced menu
• Condensing temperature is currently below the fan cut-in
• Condensing temperature sensor not properly installed – check
installation
• Power cable harness not plugged in properly or securely into the
back of the controller – check connections
• Jumper cable not plugged in properly or securely into the back of
the controller – check connections
• High pressure switch is seeing above the cut-out pressure
• For a replacing an -00 controller, ensure that the jumper cable is
the latest revision. It should have a blue wire in the harness. See
replacement instructions for more details
• System operation causing high discharge pressures, check
system operations
• System operation causing high discharge line temperatures,
check system operations
• System operation causing high discharge pressures (HPL) or
high discharge line temperatures (DLL) repeatedly, check system
operations
• To clear an “HPL” or “DLL” lockout, you can hold the Restart
button for 3 seconds twice, or cycle power to the unit. If using
the reset button, the alarm condition will have to clear (DLT
temperature drops or Hp switch resets), and any minimum off
time will need to complete (5 minutes for the xed Hp switch)
• Power cable miswired – inspect cable, replace if
needed
Evaporator lter or coil is dirtyRemove the lter and wash it, then clean the coil with a vacuum.
If coil is very dirty, use a spray bottle with a small amount of liquid
dish detergent or coil cleaner. Spray coil, let set for ve minutes, then
ush with fresh water.
There is something blocking the supply and/or return air
The evaporator fan is not turning onCall a service tech to troubleshoot
The evaporator unit has not gone through an Anti-Frost Cycle yetCheck the coil for surface ice. Melt with blow drier until coil is warm
If evaporator unit continues to ice
Unit does not run/power up
Possible causeSolution
Evaporator unit is not plugged inMake sure the unit is plugged into an outlet
Power switch not onTurn unit on by pressing the power button on the control
Line voltage rating is incorrect for the systemCheck line voltage to make sure there is 110V-120V
Bottle at setpointLower setpoint
Thermostat not calling for cooling
Faulty thermostat or wiringCall Customer Service at 1-800-343-9463
Remove blockage
to the touch. Soak up water with a towel.
Observe ice formation pattern. If only part way up the coil face, the
system could be low on refrigerant. If all the way up, the coil may be
dirty or airow is blocked.
Lower setpoint
Cellar temperature is too warm
Possible causeSolution
The temperature of the room to which the condensing unit exhausts
exceeds 110°F
The system is undersized for the cellarOrder correctly sized system
There is something blocking the supply and/or return air on the
evaporator unit or the condensing unit
Evaporator unit is mounted too low in the cellarRelocate unit so the distance from the ceiling and top of the unit is
One or more of the fans is not turning on
Compressor is not turning on
Compressor keeps cycling on overload
Poor seal around door or other areas requiring a seal (around the
unit, wall joints, etc.)
Setpoint too high
Evaporator coil is frosted or iced upObserve ice formation pattern. If only part way up the coil face,
Intake temperature needs to drop below 110°F
Remove airow obstruction
no more than 18”
Please contact the installing technician to troubleshoot
Please contact the installing technician to troubleshoot
Make sure all fans are working and there is no airow obstruction
Make sure there are no air gaps around the door. If door seal is
damaged, replace it.
Lower the setpoint
evaporator unit could be low on refrigerant. If so, contact your
installing technician to assist with troubleshooting.
System runs constantly
Possible causeSolution
Leaky door seal or poorly insulated cellarFix leaky door seal and insulate cellar
www.whisperkool.com | Page 47
Page 50
Unit leaks water
Possible causeSolution
Evaporator unit is not levelEvaporator unit should be level on the wall to prevent leaking
Drain line clogged or kinkedCheck drain line to make sure water can ow freely
Drain is clogged, preventing water from escapingDisconnect drain and clear it out, open access door and check drain
for blockage
Drain line does not have a downward slopeFix drain line so there is a downward slope from the unit to the drain
Coil is iced, causing drain pan to freeze and water to overowMelt ice with blow drier. Soak up water with a towel.
Unit runs but does not cool
Possible causeSolution
Lack of airowMake sure fan is unobstructed and that the evaporator lter,
evaporator coil, and condenser coil are clean and free of debris
System undersizedContact Customer Service at 1-800-343-9463
Compressor is overheatingShut system o for 1 hour to allow compressor to cool. Turn back on
and check for cooler air ow out. If compressor runs, check for and
clean condenser coil as possible cause of compressor overheating.
If problem repeats, contact your installing technician to assist with
troubleshooting.
Evaporator fan runs but compressor does not
Possible causeSolution
Running an Anti-Frost Cycle1) If the system is maintaining the correct cellar temperature and
there is a dripping snowake symbol illuminated on the control, the
system is going through an Anti-Frost Cycle. No action is required.
2) If the system is not maintaining the correct cellar temperature,
this may be due to a dirty evaporator lter or coil.
3) Call installing technician to troubleshoot, as the system may be
low on charge or require an adjustment to the TXV.
Compressor and/or starting components faultyPlease contact the installing technician to troubleshoot
System may be performing the WHM functionAllow cooling system to revert back to cooling mode
Compressor may have overheatedShut system o for 1 hour to allow compressor to cool. Turn back on
and check for cooler air ow out. If compressor runs, check for and
clean condenser coil as possible cause of compressor overheating.
If problem repeats, contact your installing technician to assist with
troubleshooting.
Compressor runs but evaporator fan does not
Possible causeSolution
Faulty fan motorPlease contact the installing technician to troubleshoot
Faulty controllerPlease contact the installing technician to troubleshoot
Compressor short cycles
Possible causeSolution
Evaporator unit blows on bottle probeMove bottle probe to a more central location
System low on refrigerant chargePlease contact the installing technician to troubleshoot
Condensing fan motor/capacitor faultyPlease contact the installing technician to troubleshoot
Compressor and /or starting components faultyPlease contact the installing technician to troubleshoot
Humidity in cellar too low
Possible causeSolution
Not enough moisture Purchase and place a humidier (or a decorative fountain) in cellar
Page 48 | 1-800-343-9463
PS 021319
Page 51
MAINTENANCE SCHEDULE
Platinum Split
Monthly
Quarterly
Annually
*WhisperKOOL recommends lters with a mean eciency reporting value (MERV) of 4 or better. Filters are not included with
the unit.
1. Check coils
2. Check for unusual noise or vibration
3. Check the drain line to see if it is above the waterline (if draining into a vessel)
1. Use a vacuum with brush attachment to clean coils; be careful not to crush coil ns when cleaning
2. Change duct lter if the system is ducted*
1. Inspect for corrosion
2. Check wiring connections and integrity of cords
3. Pour a 50/50 bleach solution into the drain line every spring
www.whisperkool.com | Page 49
Page 52
AE
AE5-1340
Care and Cleaning of
Air Cooled Condensing Units
Introduction
Proper care is essential to assure good life of condensing
units. Dirty or damaged condensers will reduce the
efciency and capacity of the system.
Care must be taken in choosing solutions to be used for
cleaning condensers and condensate pans. Chlorinated
cleaners and anti-bacterial cleaning agents can be
damaging and should be avoided. Caustic and acidic
cleaners should be avoided as well. Failure to do so
may accelerate component corrosion and ultimately
lead to component failure.
Condenser Coils
There are many commercially available condenser coil
cleaners on the market. Coil cleaners should be designed
to remove build-up on ns and coils. Coils should be
thoroughly rinsed of the cleaners once cleaning has
been completed. Follow the manufactures instruction
for proper usage. Preventive maintenance and routine
cleaning of coils is important to assure good life.
When cleaning the coil, an absorbent type material
should be placed under the area to be cleaned in
order to capture most of the cleaning compound, thus
minimizing any type of chemical attack.
Condensate Pans
Condensing units with condensate pans and condensate
tubes are designed to evaporate condensate water
only. Other ingredients introduced into the condensate
pan can accelerate pan and/or tube corrosion. As
foreign agents are introduced into the condensate pan,
condensate water will be evaporated leaving the foreign
agent behind. This can lead to a high concentration of the
agent and possible corrosion of the tubing and/or base.
October 2006
Coil cleaning agents must not be allowed to drain into
the condensate pan as this may cause damage. Upon
completing the coil cleaning, be certain that all residue
is removed from the condensate pan.
Only non corrosive cleaners should be used to assure
good life of the condensing unit components. No
hydrocarbon based cleaners should be used to clean
the unit. Bleach solutions must be avoided due to its
high corrosive nature.
Under no circumstances should cleaning agent
ingredients contain any of the solutions listed below:
Maintenance should be performed at regular intervals.
Coils should be cleaned at least monthly, possibly more
depending on the environment. Condensing units with
condensate pans should also be checked and cleaned
regularly to prevent damaging build up in the pan.
Safety
Please follow all safety recommendations listed by the
manufacturer of the cleaning agent(s), these would
include proper clothing, gloves and eye protection.
Page 50 | 1-800-343-9463
PS 021319
Page 53
Platinum Split
BYPASS TEST PROCEDURE
NOTE: If instructed by a WhisperKOOL representative, follow the directions below to test the cooling unit using the bypass plug
provided in the accessory kit.
1. Disconnect power from the evaporator unit.
2. Loosen the two (2) screws on the front of the grille or duct plenum.
3. Pull the grille or duct plenum away from the evaporator unit.
4. Remove the screw securing the control panel in place.
5. Slide the control panel down, out of the evaporator housing. The control panel has two (2) hooks which allow it to attach to
the evaporator unit for easy serviceability.
6. Disconnect the Molex connector labeled #4.
7. Locate the bypass plug included in the accessory kit.
8. Plug the bypass plug into the male Molex connector.
9. Connect power to the evaporator unit. The unit should immediately turn on. If all the components are not operational,
disconnect power immediately and contact customer service. If all components seem to be operating correctly, allow the unit
to run for four (4) hours. Monitor the temperature of the cellar to determine if the unit is cooling properly.
10. Once the test is complete, remove the bypass plug. Plug the Molex connector back in to the unit’s wiring.
11. Replace the control and faceplate.
www.whisperkool.com | Page 51
Page 54
TECHNICAL ASSISTANCE
WhisperKOOL Customer Service is available Monday through Friday from 6:00 a.m. to 4:00 p.m. Pacic Standard Time.
The appointed customer service representative will be able to assist you with your questions and warranty information more
eectively if you provide them with the following:
• The model and serial number of your WhisperKOOL system(s).
• Location of unit and installation details, such as ventilation, ducting, construction of your wine cellar, and room size.
• Photos of the cellar and installation location may be needed.
Contact WhisperKOOL Customer Service
1738 E. Alpine Ave
Stockton, CA, 95205
www.whisperkool.com
Email: support@whisperkool.com
Phone: 209-466-9463
US Toll Free: 1-800-343-9463
Fax: 209-466-4606
Visit www.emersonclimate.com/electronicunitcontroller for online brochures, bulletins, instruction videos, and general product
information.
Download the Copeland Mobile App on your mobile device for additional troubleshooting and technical information.
ACCESSORIES FOR COOLING UNITS
WhisperKOOL offers accessories to enhance and customize your wine cooling unit:
Condensate Pump Kit
The condensate pump kit automatically removes water that drips out of the evaporator unit’s drain line. The pump is controlled
by a float/switch mechanism that turns the pump on when approximately 2¼” of water collects in the tank, and automatically
switches off when the tank drains to approximately 1¼”. The condensate pump kit allows the excess condensate to be pumped up
to 20 feet away from the unit.
Exterior Housing
If the cooling unit is installed outside, it will need protection from sun, wind, and rain. The exterior housing protects the condensing
unit portion of the split system from the elements when installed outdoors.
Accessories can be purchased at www.whisperkool.com
Page 52 | 1-800-343-9463
PS 021319
Page 55
Split System Series
The Coolest Thing In Wine Storage
PRODUCT WARRANTY INFORMATION
WhisperKOOL Product Terms and Conditions
Including Product Limited Warranty And Product Installation Requirements
For WhisperKOOL Split System Series
ATTENTION: PLEASE READ THESE TERMS OF USE CAREFULLY BEFORE INSTALLING YOUR WHISPERKOOL COOLING
SYSTEM. INSTALLING YOUR WHISPERKOOL COOLING SYSTEM INDICATES THAT YOU ACCEPT AND AGREE TO EACH OF
THE TERMS AND CONDITIONS SET FORTH HEREIN (“TERMS OF USE”). IF YOU DO NOT ACCEPT THESE TERMS OF USE, YOU
RISK VOIDING YOUR WARRANTY AND ASSUMING ADDITIONAL REPAIR AND REPLACEMENT COSTS.
1. Purchase of a WhisperKOOL Cooling System assumes that the Purchaser (“End User”) fully accepts and
agrees to the Terms and Conditions set forth in this document. The Terms and Conditions of Sale and
Owner’s Manual are shipped with each unit and, if another copy is needed, replacement copies can be
downloaded from the company website (whisperkool.com) or by contacting WhisperKOOL directly for a
new copy. WhisperKOOL reserves the right, in its sole discretion, to change its Terms and Conditions at any
time, for any reason, without notice.
2. WhisperKOOL Product Installation and Limited Warranty
A. Purchaser of the product must arrange for the product to be installed by a certified HVAC/R technician in accordance with
procedures set forth by WhisperKOOL and described in the WhisperKOOL Owner’s Manual.
B. The HVAC/R technician installing the product must complete the designated portion of the Split Startup Checklist and
provide licensing or certification identification number information to assist in the warranty registration process.
C. Purchaser must return the completed Split Startup Checklist to WhisperKOOL within thirty (30) days of installation of
Product. The Split Startup Checklist must be approved by WhisperKOOL to activate the Limited Warranty. If the Split
Startup Checklist is approved, Purchaser will be sent activation approval documents and will start receiving the benefits
of the Limited Warranty throughout the warranty period. If the Split Startup Checklist is incomplete, Purchaser will be
informed they have five days to complete the Split Startup Checklist and re-submit to WhisperKOOL. The Split Startup
Checklist will be reviewed again, and if denied, Purchaser will be informed that they have 10 business days for corrective
action. Failure to register the Product may result in loss of warranty.
D. Purchaser is responsible for the full costs of installation and any additional parts required for the proper and complete
installation of the product.
E. For Split Systems returned to WhisperKOOL in accordance with the terms and conditions of the Limited Warranty,
WhisperKOOL warrants against defects in material and workmanship as follows:
1. LABOR — For a period of two (2) years commencing on the date of purchase, WhisperKOOL will, at its option and
discretion, reimburse up to $250 to the End User for cost incurred for servicing, repairing, removing or installing
warranty parts. Invoice for service must be forwarded to WhisperKOOL for assessment and processing. The
Split System warranty is invalid if there is attempted repair by anyone other than an HVAC/R technician approved by
WhisperKOOL to service the Product.
2. PARTS — For a period of two (2) years commencing on the date of purchase, WhisperKOOL will supply, at no charge,
new or rebuilt replacement parts in exchange for defective parts. Replacement parts are warranted only for the
remainder of the original warranty period.
3. FREIGHT — For a period of two (2) years commencing on the date of purchase, if after WhisperKOOL approved
evaluation the original Product failure is determined to be the cause of a manufacturers defect, and not the cause of
an installation error or other cause, WhisperKOOL will cover at its option, freight for the replacement parts or Product.
The following part or cause of failure is not the responsibility of WhisperKOOL:
• Improper voltage supply
• Line set with screw connectors (high end and low end)
• Leaks found at the braze points when performing pressure check
• Unit that has been charged incorrectly
www.whisperkool.com | Page 53
Page 56
• Incorrect tubing diameter used on line set
• A unit that has been wired incorrectly
• Valve stem on condenser side
• Improper installation of P-Trap
• Lack of P-Trap (if required)
• Condensers that are installed outdoors or in elements that would affect operation without proper cover or housing.
(Housing is available from Manufacturer).
Product Warranty Limitations and Exclusions.
1. This limited warranty does not cover cosmetic damage caused during installation, damage due to acts of God,
commercial use, accident, misuse, abuse, negligence, or modification to any part of the Product. Delivery and
installation of the Product, any additional parts required, as well as removal of the Product if warranty work is required,
are all at the sole cost, risk and obligation of the End User.
2. This limited warranty does not cover damage due to improper installation or operation or lack of proper maintenance
of the Product, connection of the Product to improper voltage supply, or attempted repair of the Product by anyone
other than a technician approved by WhisperKOOL to service the Product.
3. This limited warranty does not cover any Product sold “AS IS” or “WITH ALL FAULTS.”
4. Product that has been replaced during warranty period does not extend the warranty period past the original date of
purchase.
5. This limited warranty is valid only in the continental United States. Sales elsewhere are excluded from this warranty.
6. Proof of purchase of the Product in the form of a bill of sale, receipted invoice or serial number, which is evidence that
the Product is within the Limited Warranty Period, must be presented by the End User to WhisperKOOL in order to
obtain limited warranty service.
7. This limited warranty is void if the factory applied serial number has been altered or removed from the Product.
8. This limited warranty is voided if installed in an enclosure of insufficient design that does not follow the Product
installation requirements stated herein and in the owner’s manual.
9. Removing the rivets from the Product’s unit housing without prior authorization from WhisperKOOL voids this limited
warranty.
10. The End User must first contact WhisperKOOL Customer Service by telephone (at 1-800-343-9463) prior to attempting
service on any Product still under the limited warranty; else the limited warranty is voided.
11. This limited warranty does not cover Product being concealed by, but not limited to, vegetation, fabric, shelving, mud,
snow, or dirt. Product must not be painted or limited warranty will be void.
12. This limited warranty does not cover exposure to corroding environments such as, but not limited to, petroleum and
gasoline products, cleaning solvents, caustic pool chemicals, and marine air.
13. This limited warranty does not cover any cause not relating to Product defect.
14. THE REPAIR OR REPLACEMENT OF THE PRODUCT AS PROVIDED UNDER THIS LIMITED WARRANTY IS THE EXCLUSIVE
REMEDY OF YOU, THE END USER, AS WELL AS ANYONE ELSE IN THE CHAIN OF TITLE OF THE PRODUCT, DOES NOT
START A NEW LIMITED WARRANTY TIME PERIOD, AND IS IN LIEU OF ALL OTHER WARRANTIES (EXPRESS OR IMPLIED)
WITH REGARD TO THE PRODUCT. IN NO EVENT SHALL WHISPERKOOL BE LIABLE FOR INCIDENTAL, CONSEQUENTIAL,
SPECIAL OR CONTINGENT DAMAGES FOR BREACH OF ANY EXPRESS OR IMPLIED WARRANTY ON THIS PRODUCT. THE
IMPLIED WARRANTIES OF MERCHANTABILITY
15. AND FITNESS FOR A PARTICULAR PURPOSE ARE HEREBY EXPRESSLY DISCLAIMED. Some states do not allow the
exclusion or limitation of incidental or consequential damages, or allow limitations on how long an implied warranty
lasts, so the above limitations or exclusions may not apply to you. This limited warranty gives you specific legal rights,
and you may have other rights, which vary from state to state.
16. Failure of the End User to comply with all of the Product Installation Requirements, Maintenance Requirements and
End User Requirements may, at WhisperKOOL’s sole discretion, void this limited warranty.
17. No one has any authority to add to or vary the limited warranty on this Product.
Page 54 | 1-800-343-9463
PS 021319
Page 57
3. Maintenance Requirements
The End User is responsible for checking the coils on the condenser unit and vacuuming them every three months to maintain
them free of debris. It is the End User’s responsibility to clean off any accumulated dust, lint, or other debris from the front and
rear intake grills; failure to do this on a regular basis will restrict the airflow and may affect the Product’s ability to function
properly. Periodically cleaning the Product’s vents will help assure maximum cooling efficiency. The drain tube must also be
checked and kept clean and free of debris and mold to maintain proper performance.
Mold is a natural living organism in the environment. It exists in the air in the form of microscopic spores that move in and out
of buildings through doors, windows, vents, HVAC systems and anywhere else that air enters. Once it is discovered, mold must
be addressed quickly and appropriately. Delayed or improper treatment of mold issues can result in costly and reoccurring
repairs. If the End User suspects a mold problem, it is always best to hire a qualified and experienced mold remediation
specialist.
4. Additional End User Costs And Responsibilities
Terms and conditions for replacing the Product that is being evaluated for limited warranty.
1. 1. After evaluation by a certified HVAC/R technician and the Product is found to be irreparable in the field, contact
WhisperKOOL Customer Service to arrange for replacement under the warranty guidelines. When a claim for warranty
is submitted for a condenser skid, the End User must purchase a new condenser skid from WhisperKOOL at retail price.
Upon installation of the new condenser skid by a certified HVAC/R Technician, the HVAC/R Technician must complete
the Installation Checklist and End User must submit the Installation Checklist to WhisperKOOL Customer Service for
approval. The original condenser skid must be returned within 21 days to WhisperKOOL for failure analysis. If the
Installation Checklist is approved and the failure is evaluated as defective and not installation error or other reason,
the End User will be refunded for the cost of the replacement skid.
2. If the Product failure is evaluated and it is determined that it is an installation error or other reason, all costs, including
shipping will be the responsibility of the End User.
The following items are not covered under any warranty and are the sole responsibility of the End User:
A. End Users should satisfy themselves that the Product they are purchasing is suitable for their particular needs and
requirements, and thus no responsibility will be placed with WhisperKOOL for the End User’s decisions in this regard.
B. End Users must assure that the product is installed by a certified HVAC/R technician. Failure to do so will result in
Voiding the Limited Warranty.
C. It is the End User’s responsibility to secure safe haven/storage for ANY AND ALL items that are being kept and stored
in the End User’s wine cellar, including any Product. WhisperKOOL takes no responsibility for the safety and
preservation of the aforementioned items in the event that the environment becomes unsuitable to maintain a proper
storage environment.
D. End User is responsible for initial installation costs, including, but not limited to, labor costs and the cost of any
additional parts necessary to complete the installation.
E. End User is responsible for all costs incurred for the installation and/or removal of the Product, or any part thereof,
unless such cost has been agreed by WhisperKOOL to be a warranty repair prior to the work being performed.
5. Sales and Use Tax
WhisperKOOL only collects California sales tax for orders shipped within the State of California; WhisperKOOL does not collect
sales tax for orders shipped to other states. However, the Purchaser and the End User may be liable to the taxing authority in
their state for sales tax and/or use tax on the Product. The Purchaser and the End User should each check with their state’s
taxing authority for sales and use tax regulations.
6. Customer Service and Troubleshooting
WhisperKOOL’s customer service department is available to answer any questions or inquiries for End Users regarding a
WhisperKOOL Product, as well as to assist in performing basic troubleshooting, Monday through Friday, from 6:00 a.m. to 4:00
p.m. PST, at telephone number 1-800-343-9463. WhisperKOOL reserves the right to have a certified, WhisperKOOL-approved,
HVAC/R technician go on site and inspect the product if the initial trouble shooting warrants further investigation.
WhisperKOOL Corporation is located at 1738 East Alpine Avenue, Stockton, California 95205.
www.whisperkool.com | Page 55
Page 58
7. Request for Product Evaluation and Repair Under Warranty
SPLIT SYSTEM FIELD SERVICE WARRANTY POLICY: This Policy is to clarify what falls under Warranty Service and what
becomes the responsibility of the Owner. WhisperKOOL (“manufacturer”) strives to provide our customers with a superior
Product and we back our Product with a Two Year Limited Warranty. Please review the WhisperKOOL Product Terms and
Conditions including Product Limited Warranty and Product Installation Requirements to ensure you have a complete
understanding of our Policy and coverage of your Split System.
ARBITRATION: Any disputes arising out of or in connection with the installation and warranty of the Split System shall be
referred to and finally resolved by a WhisperKOOL approved Independent Certified HVAC/R Technician. The evaluation of the
Technician on all issues or matters of identifying the responsible party (WhisperKOOL or Installing Technician) shall be
determined in a written report. This report will be made available to all concerned parties. If discovered under warranty,
WhisperKOOL will assume the financial responsibility under their warranty guidelines. If the report finds the Owner’s Installer
as the responsible party, WhisperKOOL will provide all documentation to the customer to substantiate the findings. This will
include the Invoice from the Independent Certified HVAC/R Technician and the written report of the findings. The Owner will
become responsible for payment directly to WhisperKOOL for all charges incurred for repairs (labor, parts and shipping costs)
on the Split System.
8. Miscellaneous Terms and Conditions
A. Return Policy. All return inquiries must be made within thirty (30) calendar days of the original purchase of a Product and
are subject to a twenty five percent (25%) restocking fee. Shipping costs are not refundable and the Purchaser is
responsible for all return shipping costs (including customs fees and duties, if applicable).
B. Security Interest. WhisperKOOL retains a security interest in each Product until payment in full.
C. Construction and Severability. Every provision of these Terms and Conditions shall be construed, to the extent possible, so
as to be valid and enforceable. If any provision of these Terms and Conditions is held by a court of competent jurisdiction
to be invalid, illegal or otherwise unenforceable, such provision will, to the extent so held, be deemed severed from the
contract of sale between Purchaser and WhisperKOOL, and all of the other non-severed provisions will remain in full force
and effect.
D. Governing Law/Choice of Forum. The laws of the State of California (without regard for conflicts of law) shall govern the
construction and enforcement of the these Terms and Conditions of Sale (Sections 1 through 9 inclusive, including Product
Limited Warranty And Product Installation Requirements), and further these Terms and Conditions of Sale shall be
interpreted as through drafted jointly by WhisperKOOL and Purchaser. Any dispute will be resolved by the courts in and
for the County of San Joaquin, State of California, and all parties, WhisperKOOL, Purchaser and End User, hereby irrevocably
submit to the personal jurisdiction of such courts for that purpose. No waiver by WhisperKOOL of any breach or default of
the contract of sale (including these Terms and Conditions of Sale) concerning a Product will be deemed to be a waiver of
any preceding or subsequent breach or default.
E. Correction of Errors and Inaccuracies. These Terms and Conditions may contain typographical errors or other errors or
inaccuracies. WhisperKOOL reserves the right to correct any errors, inaccuracies or omissions, and to change or update
these Terms and Conditions, at any time without prior notice.
9. Questions, Additional Information And Technical Assistance
A. Questions. If you have any questions regarding these Terms and Conditions or wish to obtain additional information,
contact us via phone at 1-800-343-9463 or please send a letter via U.S. Mail to:
Customer Service
WhisperKOOL Corporation
1738 E Alpine Ave
Stockton, CA 95205
B. Technical Assistance. WhisperKOOL Customer Service is available Monday through Friday from 6:00 a.m. to 4:00 p.m. PST.
The Customer Service representative will be able to assist you with your questions and warranty information more
effectively if you provide them with the following:
1. The model and serial number of your WhisperKOOL UNIT.
2. The location of the system and installation details, such as ventilation, construction of your wine cellar, and room size.
Page 56 | 1-800-343-9463
PS 021319
Page 59
Model ______________________________________ Serial Number __________________________
Installed by __________________________________________ Date __________________________
www.whisperkool.com | Page 57
Page 60
WhisperKOOL
1738 E. Alpine Ave
Stockton, CA 95205
1-800-343-9463
www.whisperkool.com
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.