WhisperKool InCellar 8000 Low Speed, InCellar 8000 High Speed, InCellar 8000 User Manual

InCellar
OWNER’S MANUAL
The Coolest Thing In Wine Storage
We manufacture, test and certify 100% of our wine cooling units in
the USA. By sourcing the best components and closely controlling our
manufacturing processes, we can assure the highest-quality, lowest
defect manufacturing rates in the industry.
Copyright © 2011. WhisperKOOL. All rights reserved.
This manual, the product design, and the design concepts are copyrighted by WhisperKOOL, with all rights reserved. Your rights with regard to the hardware and manual are subject to the restrictions and limitations imposed by the copyright laws of the United States of America. Under copyright laws, this manual may not be copied, reproduced, translated, transmitted, or reduced to any printed or electronic medium or to any machine-readable form, for any purpose, in whole or in part, without the written consent of WhisperKOOL.
Every eort has been made to ensure that the information in this manual is accurate. WhisperKOOL is not responsible for printing or clerical errors.
WhisperKOOL reserves the right to make corrections or improvements to the information provided and to the related hardware at any time, without notice.
Vinothèque and WhisperKOOL are registered trademarks, and ECE is a trademark of WhisperKOOL. All rights reserved.
Mention of third-party products is for informational purposes only and constitutes neither an endorsement nor a recommendation. WhisperKOOL assumes no liability with regard to the performance or use of these products.
Page 2 | 1-800-343-9463
05.24.13
InC 052413
TABLE OF CONTENTS
Quick Reference Guide
Unit .....................................................
Controller ................................................
Fan Speed & Specications ...............................
2 3 4
Introduction ................................................
Receiving & Inspecting The Unit ............................
Quick Start Guide ...........................................
Preparing the Wine Cellar ...................................
Through-the-Wall Installation
Pre-Installation ...........................................
Preparing the Installation Location .......................
Installing the Cooling Unit ................................
Installing the Drain Line ..................................
Drain Line Pump System .................................
Installing the Liquid Measuring Thermostat ...............
Ducted Installation
Duct Work Option 1 ......................................
Duct Work Option 2 ......................................
Ducting Overview ........................................
Multi Speed Fan Control ....................................
5
6
7
8
11 12 13 15 16 18
19 20 21
22
Unit Operation ..............................................
Control Functions ...........................................
InCellar 8000 Wire Diagram .................................
Maintenance Schedule .....................................
Troubleshooting Guide .....................................
Technical Assistance & Accessories .........................
Installation Terms and Conditions ..........................
23
24
26
27
28
31
32
www.whisperkool.com | Page 1
QUICK REFERENCE GUIDE
Front / Side View
Exhaust Collar
Supply
Probe Input
Controller
Return
Rear Intake Plenum
Power Inlet
Fan Speed Control
Condensate Pump Access Panel
Rear / Side View
Exhaust Plenum
Filter
Page 2 | 1-800-343-9463
Unattached
Intake Plenum
Register
Drain Port
Rear Intake Plenum
Power Inlet
InC 052413
Menu Navigation
& Value Increase
QUICK REFERENCE GUIDE
Controller Layout
Refer to page 24 for complete listing of buttons and symbols.
*Press and hold
to manually enter
anti-frost mode.
Menu Navigation & Value Decrease
Compressor On
Unit is in Anti-Frost Mode
Alarm is Present
Temperature Measurement
Fans are On
INCELLAR UNIT SPECIFICATIONS
Model
InCellar 8000
Low Speed
Cellar Size (cu. ft.) 2000 2000
InCellar 8000
High Speed
Power On/O
(hold for approx. 3 seconds)
& Escape
Probe Values &
Alarm Folder
*Press and hold to
enter the parameter
menu.
Dimensions 15 1/4”w x 36.25”h x 16”d
BTUh with 90° air entering the Condenser Coil
CFM
275 Evaporator Side 257 Condenser Side 303 Evaporator Side 279 Condenser Side
5610 6206
Refrigerant R-134a
Compressor HP 1/2+ 1/2+
Voltage Rating
dedicated circuit required)
(20 amp
120V
Weight (lbs) 131 131
AMPS
(Starting/Running) 38.6 Starting 9.2 Running 40 Starting 9.5 Running
dBA 65
Evaporator Side 54 Condenser Side 68 Evaporator Side 56 Condenser Side
Drainline 1/4” I.D
Installation Partially Ducted System. Maximum Ducted feet: 15’
Thermostat Digital Control Display
Temp. Delta 55°F
Temperature dierential between the cellar temperature and condenser air intake temperature.
Warranty 2 year parts and labor
www.whisperkool.com | Page 3
FAN SPEED REFERENCE
Your fan speed selection will depend on the amount of heat that needs to be removed from the cellar. Fan speed selection will depend on the cellar size, insulation factor, door seal and desired wine temperature. When initially installing the unit, set the fan speed to High setting for a quick chill down. Once the temperature of the cellar reaches the desired temperature, you may be able to select a lower fan speed to handle the normal load. In the event the temperature outside goes above 90 degrees, (when exhausting to the outside) you may need to select the higher fan speed.
Model
Speed Selection
Air Flow
(CFM)
Sound
(dBA)
Cooling Capacity
(BTU/h)
* To get a feeling for decibels, a food blender at 3ft is 90 dBA, garbage disposal at 3ft is 85 dBA, vacuum cleaner at
10ft is 75 dBA, normal speech at 3ft is 79 dBA, dishwasher in the next room is 55dBA, Quiet night is 35dBA
8000 8000
Low High
275 Evaporator Side 257 Condenser Side 303 Evaporator Side 279 Condenser Side
65 Evaporator Side 54 Condenser Side 68 Evaporator Side 56 Condenser Side
5610 6206
Page 4 | 1-800-343-9463
InC 052413
INTRODUCTION
Customer Service
Thank you for purchasing a WhisperKOOL InCellar Series cooling unit. We strive to provide the highest quality products and the best possible customer service. If you have any questions about your WhisperKOOL unit, please call us at 1(800) 343-9463 or visit whisperkool.com.
Using the Manual
This User’s Manual is intended to assist in the proper installation and maintenance of the WhisperKOOL cooling unit. In order to ensure the longevity of your cooling unit, the equipment should be installed properly and have a proper care and maintenance schedule. Please read and review this manual carefully and keep it for future reference.
What Is the WhisperKOOL Cooling Unit?
The WhisperKOOL unit is a specialized refrigeration unit designed for one purpose only: to maintain the optimal temperature and humidity levels conducive to the proper storage and aging of ne wines. It is a self-contained cooling unit designed to be used as a forced-air partially ducted system.
How Does the WhisperKOOL InCellar Series Work?
The WhisperKOOL unit is epecially designed for the use and application to maintain optimal conditions for wine storage and aging. The unit is fully self-contained and is designed to be installed completely inside the wine cellar. The unit draws air in from an adjacent room and exhausts heat via duct work to an acceptable area. This provides the ease of installation of a through the wall system, while keeping unwanted noise and heat to a minimum. All InCellar units are temperature controlled via a bottle probe and come standard with an advanced digital thermostat.
Temperature Setting
The WhisperKOOL InCellar unit can be set at any temperature within the acceptable wine-aging range of 50°F to 70°F. It is designed to cool up to 55°F cooler than the ambient temperature of the space to which it is exhausting.
www.whisperkool.com | Page 5
RECEIVING & INSPECTING THE UNIT
Receiving and Inspecting the Unit
Lift only at the designated hand hold locations on the shipping container or fully support the unit from
underneath. A shipment may include one or more boxes containing accessories.
Before opening the container, inspect the packaging for any obvious signs of damage or mishandling.
Write any discrepancy or visual damage on the Bill of Lading before signing.
Place the box containing the WhisperKOOL unit on a tabletop to prepare it for testing prior to installing.
Sit upright for 24 hours.
Note: WhisperKOOL InCellar units are manufactured in the USA and tested prior to shipment.
Review the Packing Slip to Verify Contents
Check the model number to ensure it is correct.
If any items listed on the packing slip do not match your order information,
contact WhisperKOOL Customer Service immediately.
Check the Box for the following contents:
InCellar Cooling Unit
InCellar Intake Plenum
Accessory Kit One:
InCellar Register
Filter
WhisperKOOL InCellar Series Owner’s Manual
8’ Power Cord
Bottle Temperature Probe (Standard Unit)
10’ Drain Line
Anti-Siphon device
Tubing adapter
Please leave the WhisperKOOL unit in its original box until you are ready for installation. This will allow you to move the product safely without damaging it. When you are ready to remove the product from the box, refer to the installation instructions.
TIP: Save your box and all packaging materials. They provide the only safe means of transporting/shipping the unit.
Page 6 | 1-800-343-9463
InC 052413
QUICK START GUIDE
This guide is meant to serve as a quick reference for installation of the WhisperKOOL unit. The remainder of this
Owner’s Manual will provide more detailed information and instructions.
Upon receiving the WhisperKOOL unit:
1. Inspect the unit before installation. If damage is found, please contact your distributor or WhisperKOOL Customer Service at 1.800.343.9463 ext 799.
2. The unit should remain in an upright position for 24 hours prior to operation.
3. The WhisperKOOL unit requires a dedicated 115-volt 20-amp circuit. Use a surge protector with the WhisperKOOL unit. Do not use a GFI (Ground Fault Interrupter) line.
4. The unit is designed to gently cool down the temperature of the cellar over time by cycling cooler and cooler air throughout. Test the unit prior to installation. Operate unit for twenty minutes. While the unit is running and working properly, the air discharged from the front should be 10 - 15°F cooler than the air in the room. This means that in an environment where the air is 80°F, the unit will discharge air that is 65-70°F.
5. It is REQUIRED to install a drain line to remove condensation from the unit.
6. The WhisperKOOL unit is intended for use in properly designed and constructed wine cellars. Hire a professional wine storage consultant with a valid contractor’s license to build your wine cellar. Refer to the “How to Build a Wine Cellar” video available on the WhisperKOOL website at www.whisperkool.com.
7. Install the Intake Plenum as shown on (page 13).
8. Install duct work as shown on (pages 17-19).
9. Install Drain Line as shown on (page 15).
10. Plug in the cooling unit.
Never try to open the WhisperKOOL unit, repair it yourself, or use a service company
without WhisperKOOL’s authorization. This will void your warranty.
If you encounter a problem with your WhisperKOOL unit, please refer to the Troubleshooting Guide. If you have any further questions, concerns, or need assistance, please contact WhisperKOOL Customer Service at 1.800.343.9463 ext. 799. Please be sure all testing has been completed prior to contacting Customer Service. Please have your results ready for your representative.
www.whisperkool.com | Page 7
PREPARING THE WINE CELLAR
The performance and life of your WhisperKOOL unit is contingent upon the
steps you take in preparing the wine cellar.
Note: Improperly preparing your enclosure or incorrectly installing your WhisperKOOL
unit may cause unit failure, leaking of condensation, and other negative side eects.
IT IS HIGHLY RECOMMENDED THAT YOU OBTAIN THE ASSISTANCE
OF A WINE STORAGE PROFESSIONAL.
Wine storage professionals work with licensed contractors, refrigeration technicians, and racking companies to build well-insulated, beautiful, and protective wine cellars. WhisperKOOL has put together some useful tips to assist in the installation process. Our recommendations are meant to act as a guide in the process of building a proper enclosure. Your intended location may have specic needs that we do not address.
How to Build a Wine Cellar Instructional Video
WhisperKOOL has a construction tutorial available on line at our website: www.whisperkool.com. This tutorial will walk you through the steps of constructing a properly built wine cellar and the installation of our WhisperKOOL product line.
Wall & Ceiling Framing
Build wine cellar walls using standard 2x4 or 2x6 construction methods and ceiling joists following the guidelines of local and state codes in your area. As a general rule, the thicker the walls and the higher the insulation value in your cellar, the better it will be at maintaining a consistent temperature.
Insulation
Insulation is REQUIRED with the use of the WhisperKOOL product. Standard berglass or rigid foam insulation is nor­mally used in cellar construction or, in some cases, “blown-in” insulation is used. It is very important that all walls and ceilings are insulated to keep the cellar temperature as consistent as possible during the summer and winter months. The R-value, or quality of insulation, is determined by the rate at which heat passes through the insulation. The higher the R-value, the more resistant the insulation is to conducting heat. Using higher R-values in insulation will lower your operating costs and unit run time. (R-13 minimum, R-19 recommended, R-30 for ceiling and exterior walls.)
Vapor Barrier
A vapor barrier is REQUIRED to prevent the intrusion of water vapor so that the cellar can be kept at the correct temperature and humidity. 6 mm plastic sheeting (recommended) should be applied to the warm side of the cellar walls. The vapor barrier must also be applied to the outside walls and ceiling. If it is impossible to reach the outside, then the plastic must be applied from within the cellar. The most common method is to wrap the entire interior, leaving the plastic loose in the stud cavity so the insulation can be placed between each stud. All of the walls and ceiling must be wrapped in plastic for a complete vapor barrier.
In areas of high humidity, such as Southern and Gulf States, the vapor barrier will prevent inltration of warm moist air. The moist air can cause mold to form, and standing water in drain pans promote microbial and fungal growth that cause unpleasant odors and indoor air quality problems. If mold is found, remove it immediately and sanitize that portion of the unit.
Page 8 | 1-800-343-9463
InC 052413
Cooling Unit
Keep Clear
Unobstructed Airow
Unobstructed airflow to and from the unit is critical for the unit’s overall performance and life-span. A minimum three-foot clearance (five foot is ideal) area is crucial. The air the fans blow needs to circulate and either dissipate or absorb heat from the space, the more air to exchange the more efficient the unit will operate.
Note: Avoid attempting to camouflage the unit. This will restrict airflow and thus the unit’s ability to work efficiently.
Door and Door Seal
An exterior grade (1 3/4”) door must be installed as a cellar door. It is very important that weather stripping is attached to all 4 sides of the doorjamb. A bottom “sweep” or threshold is also required. The door must have a very good seal to keep the cool cellar air from escaping out of the cellar. One of the most common problems with cooling units running continually is due to the door not sealing properly. In cases where glass doors are used
and the room size is close to the recommended unit size, the next larger size WhisperKOOL should be used.
This will compensate for the insulation loss due to the lower insulating rating of glass.
www.whisperkool.com | Page 9
Ventilation
The necessity of dissipating heat away from the unit is critical to the unit’s performance and cannot be overstated. As the unit operates and cools, a greater amount of heat is generated on the exhaust side of the unit. Adequate ventilation is required in order to dissipate heat away from the unit. If ventilation is inadequate, the exhaust will heat up the area or room and adversely aect the unit’s ability to cool. In some cases, it may be advisable to install a vent fan to dissipate heat within the exhaust area on the backside of the unit. However, you must have a fresh air inlet as well.
Note: If you are unsure about having adequate ventilation in your install location, please
contact us to assess your specic installation at support@whisperkool.com or 1.800.343.9463.
Ambient Temperature Factor
The cooling unit has the ability to cool a wine cellar eciently to 55°F as long as the ambient temperature of the area that it is exhausting to does not exceed 110°F. Therefore, you want to exhaust the unit in a room which will not exceed 110°F. Otherwise the unit will not have the capacity to keep the wine at a desirable 55°F.
Warning, allowing your unit to operate in high ambient temperatures for extended
periods of time will greatly decrease the life of your unit and void your warranty.
Page 10 | 1-800-343-9463
InC 052413
PRE-INSTALLATION
TEST THE UNIT PRIOR TO INSTALLATION
To prepare it for testing before installation in wall:
Unit needs to be in the upright position for 24 hours before starting.
Remove unit from box
Plug in unit to electrical outlet
Plug in bottle probe
Turn on to test (see #4 on the Quick Start Guide for details).
Turn o after test
Remove Bottle Probe
Electrical Needs
The WhisperKOOL InCellar Unit requires a dedicated 115-volt 20-amp circuit. The unit draws a large amount of
amps at initial start up. By designating a dedicated circuit breaker, you will guarantee the unit has enough power to run eectively. Contact an electrician for assistance with the installation of this dedicated electrical circuit:
Match the electrical outlet to the plug provided on the WhisperKOOL unit.
Provide a dedicated circuit and wiring for the unit.
Plug your WhisperKOOL unit into a surge protector or power conditioner. As with any sensitive electrical equipment, the WhisperKOOL electrical equipment may be damaged by power surges and spikes. Power surges and spikes are not covered under warranty.
WE RECOMMEND THAT YOU DO NOT USE A GROUND FAULT INTERRUPTER (GFI) WITH THIS PRODUCT.
Electrical Inlet
The unit is equipped with a power inlet which is located on the right side of the cooling unit and is labeled in the Quick Reference Guide on page 2. The power inlet is to be connected inside of the cellar.
In case the unit should lose power, check the home/main circuit breaker. If the unit does not respond properly, refer to the Troubleshooting section.
www.whisperkool.com | Page 11
PREPARING THE INSTALLATION LOCATION
12 1/4”
12 1/4”
Through-the-Wall
Minimum Tools Needed
Level
Hammer SawScrewdriver
Locate the desired installation location. Using a stud nder, locate the studs on either side.
Place the unit against the wall to determine the height of the Intake Plenum on the rear of the Cooling Unit.
Using a level and a pencil, make an outline of a 12 1/4” square in between the two studs to provide an entry for the two Intake Plenums pieces.
Using a saw, cut out the outlined square. Be careful not to cut into any studs, electrical, or plumbing.
If present, only remove the insulation covering the area of the cut-out.
Now you have to make the same hole on the other side of the wall. Since you already have one hole, this is an easy process. Using a nail, mark all four corners of the rst hole by making nail holes through the sheetrock. Then on the other side of the wall, connect the holes with a pencil mark and cut.
Though there are still steps prior to the installation of the unattached Intake Plenum, check to see that the Plenum ts snugly through the cut-out area.
Place the Register on the unattached Intake Plenum. Mark the holes that will be drilled.
Pre-Drill the holes on the unattached intake Plenum.
Page 12 | 1-800-343-9463
InC 052413
INSTALLING THE UNIT
From outside the cellar:
1. Apply air-tight sealant or caulking on the area of the unattached Intake Plenum that will contact the wall (as shown in Figure 1).Make sure to seal all cracks and gaps. This will prevent heat transfer between the cellar and the adjacent area.
2. Slide in and secure the unattached Intake Plenum to the wall from out side of the cellar using sheetrock anchors or wood screws when going into a stud.
FIGURE 2FIGURE 1
From inside the cellar:
3. Position the Rear Intake Plenum through the cellar wall. This will provide the intake on the condenser side of the unit with fresh air. It is not required to place the cooling unit directly against the cellar wall, however, having the unit as close to the wall as possible is recommended.
FIGURE 3
www.whisperkool.com | Page 13
INSTALLING THE UNIT
From outside the cellar:
Make sure to remove all insulation or debris left inside either Plenum prior to sliding the cooling unit against the cellar wall and connecting the Intake Plenum and the rear unattached Intake Plenum.
4. From outside the cellar seal all cracks and gaps where the two Intake Plenums meet on the inside of the unattached Intake Plenum with an air-tight sealant or caulking to prevent heat transfer between the cellar and the adjacent area (as shown in Figure 4).
5. Attach the Register to the unattached Intake Plenum.
6. Insert the Filter into the Register.
7. Plug in the Cooling Unit when nished ducting the exhaust on the condenser side of the unit.
FIGURE 4
Note: If you use decorative moulding, it should be attached to the walls and never to the cooling unit itself.
The moulding itself should be removable incase the unit needs servicing.
Page 14 | 1-800-343-9463
InC 052413
DRAIN LINE
Condensation Drain Line Tube
The condensation drain line tube is used to remove excess condensation from the unit to a proper discharge location. It is important that the drain line tube is properly connected and used to prevent leakage and other problems associated with excess condensation.
Failure to use the condensation drain line tube will void the warranty on the unit.
Drain Line
During operation, the cooling unit will strip excess condensate from the air in order to maintain the proper level of humidity within the cellar. Thus the drain line will prevent overflow and leaking by allowing for discharge of the additional condensate.
Connect the Drain Line Tube to the Drain Port on the Top of the Cooling Unit. Routing the Drain Line to the attic and then to a dispense area is recommended. The InCellar Cooling Unit will Pump the excess condensate through the Drain Line Tube.
Do not rout the drain line more than 30 vertical ft.
If the outlet of the drain line is below the base of the unit, install the anti-siphon device as shown in (Figure 5).
Anti-Siphon Device
FIGURE 5
Failure to install the drain line voids the warranty.
To prevent mold from growing, allow the drain line to hang above the water line.
WRONG: Drain line is under water.
www.whisperkool.com | Page 15
DRAIN LINE PUMP SYSTEM
CORRECT: Typical sequence of operation for correct Discharge Hose installation with Anti-Siphon Device
1. Drain pan lls with water which ows into reservoir. Intake hose between reservoir and pump is empty (lled with air).
2. Raising water lifts oat, activating pump, which self primes by drawing water up from reservoir. During this period the pump is operating hot and dry and will click loudly. Once the air in the intake hose has been purged, water entering the pump cools and lubricates it so that the clicking noise becomes a low hum. Water ows through the pump and out of the discharge hose.
3. Water level in the reservoir has now receded enough to lower the oat which deactivates the pump, however, since an Anti-Siphon Device is included in the discharge hose, atmospheric pressure is equalized at both ends of the hose system so the siphoning eect cannot occur and THE INTAKE HOSE REMAINS FILLED WITH WATER.
4. The drain pan again lls up with water which ows into the reservoir and activates the pump. THE INTAKE HOSE
IS ALREADY FILLED WITH WATER so no air is sucked in, and the pump is immediately cooled and lubricated. NO CLICKING NOISE IS HEARD.
PUMP PUMP
1
DRAIN PAN DRAIN PAN
RESERVOIR RESERVOIR
BREATHER TUBE BREATHER TUBE
3
ATMOSPHERE
PRESSURE
MINIMUM 6” MINIMUM 6”
AIR GAP AIR GAP
3/4” PVC OR COPPER PIPE
AIR GAP
ATMOSPHERE
PRESSURE
MAXIMUM 2” MAXIMUM 2”
3/4” PVC OR COPPER PIPE
2
4
DRAIN PANDRAIN PAN
RESERVOIRRESERVOIR
THE PUMP IS NOW OPERATING ENTIRELY WITHIN NORMAL PARAMETERS AND IS IN NO DANGER OF OVERHEATING OR FAILING.
MAXIMUM 2”MAXIMUM 2”
MINIMUM 6”MINIMUM 6”
NOTE: THIS APPLIES ONLY TO INSTALLATIONS WHERE THE POINT AT WHICH THE CONDENSATE WATER
3/4” PVC OR COPPER PIPE
EMERGES FROM THE DRAIN HOSE OR PIPE IS BELOW THE DRAIN PAN IN THE EVAPORATOR.
IF THE END OF THE PUMP DISCHARGE HOSE OR PIPE IS ABOVE THE LEVEL OF THE DRAIN TRAY IN
PUMPPUMP
THE EVAPORATOR NO SIPHONING CAN OCCUR AND AN ANTI-SIPHON
AIR GAP
3/4” PVC OR
BREATHER TUBEBREATHER TUBE
COPPER PIPE
DEVICE IS NOT REQUIRED.
Page 16 | 1-800-343-9463
InC 052413
DRAIN LINE PUMP SYSTEM
INCORRECT: Failure to follow correct Discharge Hose installation will damage pump.
1. Drain pan lls with water which ows into reservoir. Intake hose between reservoir and pump is empty (lled with air).
2. Raising water lifts oat, activating pump, which self primes by drawing water up from reservoir. During this period the pump is operating hot and dry and will click loudly. Once the air in the intake hose has been purged, water entering the pump cools and lubricates it so that the clicking noise becomes a low hum. Water ows through the pump and out of the discharge hose.
3. Water level in the reservoir has now receded enough to lower the oat, deactivating the pump. However, the weight of the water in the discharge hose plus atmospheric pressure at the drain pan outlet forces the water remaining in the intake hose to continue owing out through the pump until the reservoir, intake hose, pump and discharge hose are completely empty, at which point the siphoning stops.
4. As the evaporator produces more condensate, the drain pan again lls up with water which ows into the reservoir. Since the intake hose is lled with air again, the cycle repeats itself.
RESULT: EVERY TIME THE PUMP RUNS HOT AND DRY, IT SUSTAINS A SMALL AMOUNT OF DAMAGE
PUMP
PUMP
WHICH CAUSES PREMATURE WEAR.
1
DRAIN PAN
RESERVOIR
3
ATMOSPHERE
PRESSURE
BREATHER TUBE
2
DRAIN PAN
RESERVOIR
4
DRAIN PANDRAIN PAN
RESERVOIRRESERVOIR
BREATHER TUBE
BREATHER TUBEBREATHER TUBE
THE NEXT TIME THE PUMP STARTS UP DRY, IT MAY RUN FOR 11 SECONDS BEFORE IT COOLS DOWN THE NEXT TIME 12 SECONDS AND SO ON. ALSO WHILE THIS IS OCCURRING, THE PUMP IS CLICKING LOUDLY. THIS IS ACCEPTABLE DURING THE INITIAL START UP PHASE, BUT NOT ACCEPTABLE DURING SUBSEQUENT OPERATIONS OF THE PUMP.
WHEN YOU CONSIDER THAT THIS WILL OCCUR A NUMBER
PUMPPUMP
OF TIMES EVERY DAY OF THE COOLING SEASON IT IS EASY TO SEE THAT THE DAMAGE WILL RAPIDLY ACCUMULATE. IF THE PUMP IS ALLOWED OPERATE IN THIS CONDITION REPEATEDLY, THE NOISY PERIOD WILL GET LONGER AND LONGER OVER THE COOLING SEASON UNTIL THE CUSTOMER COMPLAINS OR THE PUMP EVENTUALLY FAILS.
THIS CAN EASILY BE AVOIDED BY INSTALLING THE DISCHARGE HOSING CORRECTLY WITH AN ANTI-SIPHON DEVICE WHICH WILL EQUALIZE THE ATMOSPHERIC PRESSURE AND ELIMINATE THE SIPHONING.
www.whisperkool.com | Page 17
LIQUID MEASURING THERMOSTAT
The WhisperKOOL Series cooling units come equipped with a liquid temperature measuring thermostat. This incorporates the following advantages:
Self-Calibrating Probe
The probe contains a sensor chip, which actually communicates back and forth to the thermostat. This results in a consistent temperature setting and accuracy.
Measuring liquid temperature has a few unique advantages:
1. Wine temperature is kept in a very precise controlled environment. This assures a consistent temperature.
2. By measuring the liquid temperature rather than air, the unit will operate 75- 80% of the time.
Liquid Measuring Thermostat
To assure a consistent temperature, place bottle probe approximately 3 feet away from the air output and not in the flow of the air.
To Use the thermostat:
1. Locate an empty wine bottle.
2. Fill 3/4 full with room temperature tap water.
3. Place bottle probe securely into bottle.
4. Place bottle with probe level and to the side of the unit in your wine cellar. It is recommended that it is placed in a central location of your wine cellar. Avoid pulling too much on the probe cord. It may become disconnected resulting in non-operation of the unit.
Note: The thermostat can be set between 50°F and 70°F.
Remember: The WhisperKOOL unit operates based on the temperature of the water. Do not be misled by thermostats reading air temperature. The air temperature in the cellar will be cooler than the liquid temperature of the wine while it is coming to optimum balanced temperature.
Page 18 | 1-800-343-9463
InC 052413
INSTALLING THE DUCT WORK
Building a Facade
The InCellar Cooling Unit is set up to have a variety of Ducting Installation Options. The exhaust may be ducted into the attic or out to the exterior of the house through the attic. The rst option to consider is using a standard 6”x14” Duct Boot and 8” diameter duct work for the exhaust followed by building a facade around the duct work.
Figure 5 below is an example that may be followed to create a facade to extend to the Ceiling using: 1/2” Plywood, 1/2” Drywall (2) 2x2, (2) 3x3.
Measure the space between the
cooling unit and the wall and add the distance to these dimensions for
the total length.
FIGURE 5
www.whisperkool.com | Page 19
INSTALLING THE DUCT WORK
Custom Duct Work
Another Option that might be considered is building Insulated Custom Duct Work. Figure 6 below is an example that may be followed to create Insulated Custom Duct Work to extend to the attic using 1/2” Plywood, 1/2” Insulation Board and (24) Angle Brackets.
Ducting Information
When Ducting the Exhaust away from the Cooling Unit, custom Ducting will be sucient if it follows these recommendations:
Custom Ducting is insulated so that the warm exhaust air in the duct does not aect the air in the Cellar.
The surface area of inside the duct is greater than or equal to 51 sq. in.
The Duct Work follows the General Duct Recommendations on page 21.
Measure the space between the cooling unit and the wall and add the distance to these dimensions for the total length.
FIGURE 6
Page 20 | 1-800-343-9463
InC 052413
DUCTING OVERVIEW
Use of Ductwork
Use ductwork to connect the Exhaust Collar on the top of the cooling unit to the desired exhaust area. Use only insulated ductwork to minimize cooling losses and reduce noise.
Note: Do not exceed a total of 15’ for the length of ductwork.
Avoid crimping the exible ducts. This chokes down the inside area and reduces the airow causing the unit to operate improperly. Be sure all duct work is insulated.
DO NOT ALLOW FLEXIBLE DUCTING TO GET SQUEEZED OR ALLOW THE INSIDE
DIAMETER TO DECREASE DUE TO VERY SHARP TURNS.
General Duct Recommendations
Use a 6”x14” duct boot to connect to the Exhaust Collar (when using standard duct work).
Provide support for the exible duct to prevent sags and bends.
InCellar 8000 Duct Size: 8” dia.
Stretch out the duct to make a smoother interior which reduces air resistance.
Maximum duct length is 15’.
For 90° bends, use a 90° adjustable elbow.
No more than two 90° bends. Sweep 90° bends are recommended rather than sharp 90° bends.
Generously apply duct sealant to all metal seams to ll in gaps that can leak air. Allow sealant to dry until rm
to the touch before applying berglass insulation.
Do not squeeze or reduce the inside diameter of the ducts as this will reduce airow.
Use short and straight ductwork where possible.
Check that all fan blades move freely.
Keep air paths free of loose foreign objects and debris.
Do not: Locate the Exhaust where it will be blocked for any reason.
www.whisperkool.com | Page 21
MULTI SPEED FAN CONTROL
Designed for wine cellars up to 2000 cubic feet, the InCellar 8000 features multi-speed fans with a “high” setting for maximum performance in high-temperature (+110°F) environments and a “low” setting for super-quiet operation.
Fan Speed Selector Switch (Low/High): The cooling unit fans may operate on two speed settings: Low and High. For optimum sound and energy eciency, select the lowest fan speed that will maintain the desired cellar temperature. If the relative humidity is low, a higher fan speed will cause less moisture to be removed during cooling. High speed is recommended for initial cellar cool down.
Your fan speed selection will depend on the amount of heat that needs to be removed from the cellar and the application of the unit. Fan speed selection will depend on the cellar size, insulation factor, door seal and desired wine temperature. When initially installing the unit, set the fan speed to the Highest setting for a quick chill down. Once the temperature of the cellar reaches the desired temperature, you may be able to select the lower fan speed to handle the normal load. In the event the temperature of the intake air on the condenser side goes above 90 degrees, you may need to select the higher fan speed.
Model
Speed Selection
Air Flow
(CFM)
Sound
(dBA In Cellar / Out of Cellar)
Cooling Capacity
(BTU/h)
275 Evaporator Side 257 Condenser Side 303 Evaporator Side 279 Condenser Side
65 Evaporator Side 54 Condenser Side 68 Evaporator Side 56 Condenser Side
8000 8000
Low High
5610 6206
Page 22 | 1-800-343-9463
InC 052413
Initial Start-Up:
UNIT OPERATION
When power is applied to the unit, the control will briey display all symbols, and the Compressor symbol will be displayed (if unit is calling for cooling). There may be a brief delay prior to the evaporator and condenser fans turning on.
Set Point:
The set point is set from the factory (WhisperKool) at 55°. It can be adjusted by the customer between 50° and 70° in one degree increments.
Cooling Operation:
Cooling is activated once the bottle probe senses a temperature that is 1° greater than the set point. The controller then energizes the compressor relay which activates the compressor. The evaporator and condenser fans operate with the compressor. The unit provides cooling until the bottle probe senses the set point. At this point the compressor relay is de-energized which stops the compressor. The evaporator and condenser fans will continue to run for 1 minute to re-evaporate any moisture from the evaporator coil and reduce the head pressure.
Humidity Features:
The FDC parameter can be increased to allow the evaporator and condenser fans to run for a longer period of time after the compressor turns o, allowing more moisture to be re­evaporated into the cellar.
Defrost/Anti-frost:
When the evaporator probe senses a temperature of 26 degrees for 5 minutes, the unit will go into Anti-frost mode. This will shut down the compressor and allow the evaporator and condenser fans to run to evaporate any frost accumulation on the coil. The compressor will remain o until the evaporator coil reaches 40°, or for a maximum of 10 minutes. The unit will then return to normal operation.
If the evaporator is not above 26 degrees after the anti-frost sequence has ended, the red error light will display in the upper right corner. Alarm “Ad3” will be recorded in the alarm folder, meaning that the anti-frost sequence ended based on time. The unit will run for 5 minutes and then enter another Anti-Frost cycle. This sequence will continue until the evaporator temperature increases above 26°.
Display:
The bottle probe temperature is displayed by default. “Def” is displayed during anti-frost. The bottle probe and evaporator probe temperatures can be accessed by pushing the set button and scrolling through PB1 (bottle probe) and PB2 (evaporator probe).
Safety Features:
Once the compressor relay is de-energized the controller must wait 5 minutes before re-energizing the relay. This prevents the compressor from repeatedly turning o and on. If the unit is calling for cooling during this time, the compressor symbol will blink indicating that cooling is needed but the control is waiting for the anti-short cycle delay. In the event of a faulty bottle probe, the compressor will cycle o for 10 minutes and on for 40 minutes. E1 will be displayed on the screen.
Alarms:
If the bottle temperature reaches 4 degrees above the set point, a red light will blink in the upper right corner of the display. The set button can then be pressed to reach the alarm menu. The menu will display “AH1” indicating a high bottle temperature. The same thing will happen if the bottle temperature reaches 4 degrees below the set point, except the alarm will read “AL1”. These alarms will not display for the rst 10 hours after the unit is turned on to allow the cellar to reach temperature. They will also wait one hour after an anti-frost cycle before displaying.
In the event of a faulty evaporator probe E2 will ash on the screen intermittently. The red alarm light will be displayed in the upper right corner. The unit will go through one anti­frost sequence every 24 hours.
Press the set button and enter the Al folder to view any current alarms that are not ashing on the display.
In the event of a high water alarm the compressor will turn o, the alarm will sound and “Opd” will be displayed in the alarm folder. The unit will continue normal operation once the pump has removed enough water to clear the high water alarm.
“Def” will be displayed during anti-frost. If the anti-frost sequence is less than 5 minutes, the control will not allow the compressor to start until 5 minutes has elapsed. This is to prevent short cycling of the compressor.
Holding down the up button for approximately ve seconds manually starts the Anti-frost sequence, but only if the evaporator is below 40 degrees (defrost end temperature). If the evaporator is above 40 degrees, the display will blink three times and continue normal operation.
www.whisperkool.com | Page 23
CONTROLLER FUNCTIONS
Button/Symbol Normal Functions
ON/OFF
Press and hold the on/o button for approximately 3 seconds to turn the unit on or o.
Note: This does not disconnect power from the unit. In order for the power to be shut o from
the unit, the power cord must be unplugged from the wall receptacle.
This button also serves as an escape button.
Up and Down
SET
Snowake
Use these buttons to scroll up or down a menu.
Press and hold the up button for approximately ve seconds to manually start the Anti-frost
sequence. The Anti-frost sequence will begin, but only if the evaporator is below 40 degrees. If the evaporator is above 40 degrees, the display will blink three times, signalling that an Anti-frost cycle is not needed, and the unit will continue normal operation.
Press the set button once to view the set point, temperature of the evaporator and actual bottle temperature as well as any alarms.
Once the set button is pressed “SEt” will be displayed. Press the up or down arrows to scroll through Pb1, Pb2.
SEt Set Point
Pb1 Liquid Temperature
Pb2 Evaporator Coil Temperature
Press the set button again to view any of these values.
To change the set point, press the set button when “SEt” is displayed on the screen. The current
set point will be displayed. Use the up or down arrows to change the set point to the desired temperature. Press the set button again once the desired temperature is reached.
Hold the set button for approximately 5 seconds to enter the CPSM (Customer Preference Selection Mode) menu. (CPSM detail on next page)
Constant - Unit is in cooling mode and the compressor is running.
Blinking - The unit is calling for cooling, but must wait 5 minutes before restarting the compressor. This 5 minute delay serves as an anti-short cycle for the compressors protection.
Dripping Snowake
Alarm
Page 24 | 1-800-343-9463
Unit is in Anti-frost mode. The evaporator and condenser fans are running to evaporate any frost which may have formed on the evaporator coil.
The evaporator and condenser fans are on.
Fan
The Alarm symbol is shown and a audible buzzer will sound when the unit encounters an issue that needs attention, the displayed alarm codes are explained below. To silence the buzzer press any button, the alarm code will remain displayed until corrected.
InC 052413
Alarm Codes
Message Cause Solution
Bottle Probe is Unplugged Attach Bottle Probe to Unit.
“E1”
“E2”
“AH1”
“AL1”
“Ad3”
“Opd”
“CA1”
Faulty Bottle Probe Connection
Defective Bottle Probe Replace the Bottle Probe.
Faulty Evaporator Probe Connection
Defective Evaporator Probe Replace the Evaporator Probe.
The bottle probe is sensing a temperature that is 4° above the set point
The bottle probe is sensing a temperature that is 4° below the set point
Anti-frost ended on time-out 1. Check the evaporator coil for ice buildup. Unplug the unit and allow coil to thaw
Water level is too high 1. Check drain line for debris & kinks
Use this parameter to calibrate the bottle probe to a known temperature. This parameter can be adjusted between
°F and 12°F.
-12
Example: Bottle temperature reading = 58°F Known temperature reading = 55°F CA1 parameter setting to match known temperature = -3
1. Check Bottle Probe attachment at circular connector.
2. Check Bottle Probe connection at the back of controller.
Check Evaporator Probe connection at the back of controller.
1. Allow time for the wine to reach the desired temperature.
2. Make sure all windows and doors are closed and have a proper seal.
3. Follow the procedures in the pre-installation instructions to test the unit for proper cooling.
1. Make sure unit is not in cooling mode. (the snowake symbol will not be lit)
2. Add heat to the room until the wine reaches the desired temperature.
before re-starting.
2. Make sure the room to which the unit is exhausting is not less than 60°.
3. If unit continues to go into continuous anti-frost cycles (every 5 minutes), call customer service for more troubleshooting information.
2. Check power supply to pump
3. Make sure pump & oat are level
CPSM (Customer Preference Selection Mode)
Press and hold the set button for approximately 5 seconds to enter the CPSM menu.
“Fdc” will be displayed on the screen. Use the down arrow to access the following parameters.
This parameter is set to 1 from the factory which should provide adequate relative humidity for the
Fdc
Humidity Management/
Enhancement
cellar. An increase in this parameter will increase the Humidity Enhancement (%RH). This parameter should not be adjusted below 1. Adjustments should be made in increments of 5, with a maximum of 15 and a minimum of 1. After any adjustment to Humidity Enhancement you should wait a minimum of three days before making any additional adjustments. This will allow the cellar sucient time to acclimate to the new setting.
PA2 No adjustable settings in this parameter.
tab No adjustable settings in this parameter.
Rel No adjustable settings in this parameter.
loc Change this parameter from “n” to “y” to lock the keyboard from changes to the set point.
Select one of these numbers to display your preference:
ddd
0 = Set Point 1 = Bottle Probe Temperature 2 = Evaporator Probe Temperature 3 = Condenser Probe Temperature
www.whisperkool.com | Page 25
White
INCELLAR 8000 WIRING DIAGRAM
Green
Black
1 2 3 4 5 6
Orange
Green
Black
Condensate
Pump
Purple
Gray
Red
Green
Green
Green
(+)
(-)
White
Black
Blue
Crankcase
Heater
Blue
Black
Black
White
Black
Blue
White
0
COMP
NC C NO
7 8 6
3
4 2
Blue
1
Eliwell 974
8 9 10
7
11
Cond.
Fan
Black
Brown
White
Capacitor
Gray
Red
Page 26 | 1-800-343-9463
Fan
White
Capacitor
Evap.
Brown
Red
Black
3
2
Gray
2 Way F.S.
1
Neutral
Ground
Hot
Compressor
InC 052413
Monthly 1. Check Coils
2. Check for unusual noise or vibration
3. Check the drain line to see if it is above the waterline if draining into a vessel.
MAINTENANCE SCHEDULE
Quarterly 1.
2. Replace Filters on the duct work.
3. Check the drain line pump and thoroughly clean the reservoir, lter and oat with an antibacterial cleansing solution.
4. All drain line hoses should be checked for leaks.
Annually
1. Replace lters if worn or plugged beyond cleaning.
2. Use a vacuum with brush attachment to clean coils. Be careful not to crush coil ns when cleaning.
3. Inspect for corrosion.
4. Check wiring connections and integrity of cords.
5. Examine duct work for cracks or possible leaks.
6. Pour a 50/50 bleach solution into the drain line every spring.
Clean Coils
www.whisperkool.com | Page 27
TROUBLESHOOTING GUIDE
Unit has ice forming on the Evaporator
Possible Cause Solution
Evaporator coil is dirty.
There is something blocking the supply and or return air Remove blockage
The evaporator fan is not turning on. Call a service tech to troubleshoot
The Unit has not gone through its anti-frost sequence, yet. Check for ice in the depth of the coil. Melt with blow drier
If Unit continues to ice. Observe ice formation pattern. If only part way up the coil
Unit does not run/power up
Possible Cause Solution
Unit is not plugged in Make sure the unit is plugged into an outlet
Power switch not on Turn unit on by pressing the power button on the control
Line voltage is incorrect rating for the system Check line voltage to make sure there is 110v/120v
Bottle at set point Lower set point
Thermostat not calling for cooling Lower set point
Faulty thermostat or wiring Call Customer Service at 1-800-343-9463
Clean coil with a vacuum. If coil is very dirty, use a small hand spray with a small amount of liquid dish washer detergent. Spray coil, let set for 5 min, then ush with fresh water.
until coil is warm to the touch. Soak up water with a towel.
face, the system could be low on refrigerant. If all the way up, the coil may be dirty or airow is blocked.
Cellar Temperature is to Warm
Possible Cause Solution
The temperature of the room supplying the condenser side of the unit has exceeded 110°F
The unit is undersized for the cellar. Order correct size system
There is something blocking the supply and/or return air, on the Evaporator or the Condenser side of the Unit.
One or more of the fans are not turning on. Please contact the installing technician to troubleshoot.
Compressor is not turning on. Please contact the installing technician to troubleshoot.
Compressor keeps cycling on overload Make sure all fans are working and there are no airow
Poor seal around door or other areas requiring a seal (around the unit, wall joints, etc)
Controller Set Point set too high Lower the set point.
Evaporator coil is frosted or iced up Observe ice formation pattern. If only part way up the coil
Intake temperature needs to drop below 110°.
Remove air ow obstruction
obstructions.
Make sure there are no air gaps around the door. If door seal is damaged, replace it.
face, Unit could be low on refrigerant. If so, contact your installing technician to assist with troubleshooting.
System Runs Constantly
Possible Cause Solution
Leaky door seal or poorly insulated cellar. Fix leaky door seal and insulate cellar in accordance with
this manual. (Page 9)
Page 28 | 1-800-343-9463
InC 052413
TROUBLESHOOTING GUIDE
Unit leaks water
Possible Cause Solution
Unit is not level
Drain line clogged or kinked Check drain line to make sure water can ow freely.
Drain is clogged preventing water form escaping
Coil is iced causing drain pan ice and water overowing Melt ice with blow drier. Soak up with a towel
Unit runs but does not cool
Possible Cause Solution
Lack of air ow
Compressor not running Contact Customer Service at 800-343-9463
Unit undersized Contact Customer Service at 800-343-9463
Compressor is overheating
Evaporator fan runs but compressor does not
Possible Cause Solution
Running an Anti-Frost Cycle
Compressor and/or starting components faulty Please contact the installing technician to troubleshoot.
System may be performing the WHM function Allow cooling system to revert back to cooling mode.
Compressor may have overheated.
Unit should be level to prevent leaking.
Disconnect drain and clear out, open access door and check drain for blockage
Make sure fan is unobstructed; clean evaporator if necessary.
Shut system o for 1 hour to allow compressor to cool. Turn back on and check for cooler air ow out. If compressor runs, check and clean condenser coil as possible cause of compressor overheating. If problem repeats, contact you installing technician to assist with troubleshooting.
Shut system o for 1 hour to allow compressor to cool. Turn back on and check for cooler air ow out. If compressor runs, check and clean condenser coil as possible cause of compressor overheating. If problem repeats, contact you installing technician to assist with troubleshooting.
Compressor runs but evaporator fan does not
Possible Cause Solution
Faulty fan motor Please contact the installing technician to troubleshoot.
Faulty Controller Please contact the installing technician to troubleshoot.
Compressor short cycles
Possible Cause Solution
Unit blows on bottle probe Move bottle probe to a more central location.
Unit low on refrigerant charge Please contact the installing technician to troubleshoot.
Condensing fan motor/capacitor faulty Please contact the installing technician to troubleshoot.
Compressor and /or starting components faulty Please contact the installing technician to troubleshoot.
Humidity in cellar too low
Possible Cause Solution
Not enough moisture Raise the Fdc setting to increase the humidity level
www.whisperkool.com | Page 29
TROUBLESHOOTING GUIDE
Pump runs all the time
Possible Cause Solution
Float is positioned with the magnet facing downwards. Reposition the oat with the magnet facing up wards.
The oat is not in the correct location. Check that the oat is located inside the reservoir around
the sensor column.
The top is not secured properly to the reservoir. Make sure that the top is clipped rmly on to the reservoir.
Sludge has built up and is preventing the oat to rest on the bottom of the reservoir.
The evaporator produces more condensate than the pump can handle.
Pumps runs but does not pump any water
Possible Cause Solution
Evaporator has been disconnected from reservoir. Connect the evaporator’s drain outlet hose onto the drain
Reservoir has been disconnected pump. Connect the reservoir outlet to the pump inlet.
Restriction in one of the hoses. Remove all kinks and debris from the drain hose
Reservoir, lter and discharge hose are being restricted by sludge and debris.
Clean with anti bacterial solution. Note: The pump will only switch o when the oat is actually resting on the bottom of the reservoir.
The pump is too small and must be replaced with a dierent type.
inlet on the reservoir.
Clean with anti bacterial solution.
Pump does not operate
Possible Cause Solution
Power is not reaching the Pump Contact Customer Service at 800-343-9463
Pump is not wired correctly Contact Customer Service at 800-343-9463
The pump was too hot and the thermal cut out has been activated.
The pump will automatically reset once the pump has cooled down.
Page 30 | 1-800-343-9463
InC 052413
TECHNICAL ASSISTANCE & ACCESSORIES
WhisperKOOL Customer Service is available Monday through Friday from 8:00 a.m. to 4:00 p.m. Pacic Time.
The customer service representative will be able to assist you with your questions and warranty information more eectively if you provide them with the following:
The model and serial number of your WhisperKOOL Series Unit.
Location of unit and installation details, such as ventilation, ducting, construction of your wine cellar, and
room size.
Contact WhisperKOOL Customer Service
1738 E. Alpine Avenue Stockton, CA 95205
www.whisperkool.com Email: support@whisperkool.com Phone: (209) 466-9463 US Toll Free (800) 343-9463 Fax (209) 466-4606
ACCESSORIES FOR COOLING UNITS
WhisperKOOL offers accessories to enhance and customize your InCellar wine cooling unit.
-
Casters
Accessories can be purchased at www.whisperkool.com
www.whisperkool.com | Page 31
InCellar Series
The Coolest Thing In Wine Storage
WhisperKOOL Product Terms and Conditions
Including Product Limited Warranty And Product Installation Requirements
For WhisperKOOL InCellar Series
ATTENTION: PLEASE READ THESE TERMS OF USE CAREFULLY BEFORE INSTALLING YOUR WHISPERKOOL COOLING SYSTEM. INSTALLING YOUR WHISPERKOOL COOLING SYSTEM INDICATES THAT YOU ACCEPT AND AGREE TO EACH OF THE TERMS AND CONDITIONS SET FORTH HEREIN (“TERMS OF USE”). IF YOU DO NOT ACCEPT THESE TERMS OF USE, YOU RISK VOIDING YOUR WARRANTY AND ASSUMING ADDITIONAL REPAIR AND REPLACEMENT COSTS.
1. Purchase of a WhisperKOOL Cooling System assumes that the Purchaser (“End User”) fully accepts and agrees to the Terms and Conditions set forth in this document. The Terms and Conditions of Sale and Owner’s Manual are shipped with each unit and, if another copy is needed, replacement copies can be downloaded from the company website (whisperkool.com) or by contacting WhisperKOOL directly for a new copy. WhisperKOOL reserves the right, in its sole discretion, to change its Terms and Conditions at any time, for any reason, without notice.
2. WhisperKOOL Product Limited Warranty:
A. Two (2) Year Limited Warranty. For the period of TWO (2) YEARS (the “Limited Warranty Period”) from the date
of original sale of a Product by WhisperKOOL, if a WhisperKOOL Product is found to be defective in material or workmanship after undergoing WhisperKOOL’s customer service troubleshooting, then, subject to the WhisperKOOL Product Limited Warranty Limitations and Exclusions as well as the other Terms and Conditions stated herein, WhisperKOOL will do the following, as appropriate, for the end user (“End User”) who has installed and is actually using the Product, with regard to LABOR, PARTS and FREIGHT:
1. LABOR - repair or replace (at WhisperKOOL’s sole option) the Product. If WhisperKOOL determines that Product is to be REPLACED, there will be no labor reimbursement. If WhisperKOOL chooses to REPAIR the Product, WhisperKOOL will consider possibility of maximum reimbursement of $350.00 in labor for REPAIRING Product on site and supplying all parts at no charge. Invoice for service must be forwarded to WhisperKOOL for assessment and processing.
2. PARTS – supply, at no charge, new or rebuilt replacement parts for the Product in exchange for the return of defective parts. WhisperKOOL, at its option, will assess possibility to replace unit that is at the original site with a warranty replacement unit OR consider possibility of supplying all parts at no charge.
3. FREIGHT – cover normal ground freight charges for parts, and, in the event the Product is not repairable in the eld, WhisperKOOL, at its option, will pay freight charges to return original Product to WhisperKOOL for evaluation. End User is responsible for freight charges of replacement Product being shipped to End User.
B. Five (5) Year Compressor Limited Warranty. WhisperKOOL Product’s compressor only will be covered for ve (5)
years from date of purchase. Labor and freight of compressor is the End Users responsibility.
C. Product Warranty Limitations and Exclusions:
1. This limited warranty does not cover cosmetic damage caused during installation, damage due to acts of God, commercial use, accident, misuse, abuse, negligence, or modication to any part of the Product. Delivery and installation of the Product, any additional parts required, as well as removal of the Product if warranty work is required, are all at the sole cost, risk and obligation of the End User.
2. This limited warranty does not cover damage due to improper installation or operation or lack of proper maintenance of the Product, connection of the Product to improper voltage supply, or attempted repair of the Product by anyone other than a technician approved by WhisperKOOL to service the Product.
3. This limited warranty does not cover any Product sold “AS IS” or “WITH ALL FAULTS.”
4. Product that has been replaced during warranty period does not extend the warranty period past the original date of purchase.
Product Warranty Information
Page 32 | 1-800-343-9463
InC 052413
1. This limited warranty is valid only in the continental United States. Sales elsewhere are excluded from this warranty.
2. Proof of purchase of the Product in the form of a bill of sale, receipted invoice or serial number, which is evidence that the Product is within the Limited Warranty Period, must be presented by the End User to WhisperKOOL in order to obtain limited warranty service.
3. This limited warranty is void if the factory applied serial number has been altered or removed from the Product.
4. This limited warranty is voided if installed in an enclosure of insucient design that does not follow the Product installation requirements stated herein and in the owner’s manual.
5. Removing the rivets from the Product’s unit housing without prior authorization from WhisperKOOL voids this limited warranty.
6. The End User must rst contact WhisperKOOL Customer Service by telephone (at 1-800-343-9463) prior to attempting service on any Product still under the limited warranty; else the limited warranty is voided.
7. This limited warranty does not cover Product being concealed by, but not limited to, vegetation, fabric, shelving, mud, snow, or dirt. Product must not be painted or limited warranty will be void.
8. This limited warranty does not cover exposure to corroding environments such as, but not limited to, petroleum and gasoline products, cleaning solvents, caustic pool chemicals, and marine air.
9. This limited warranty does not cover any cause not relating to Product defect.
10. THE REPAIR OR REPLACEMENT OF THE PRODUCT AS PROVIDED UNDER THIS LIMITED WARRANTY IS THE EXCLUSIVE REMEDY OF YOU, THE END USER, AS WELL AS ANYONE ELSE IN THE CHAIN OF TITLE OF THE PRODUCT, DOES NOT START A NEW LIMITED WARRANTY TIME PERIOD, AND IS IN LIEU OF ALL OTHER WARRANTIES (EXPRESS OR IMPLIED) WITH REGARD TO THE PRODUCT. IN NO EVENT SHALL WHISPERKOOL BE LIABLE FOR INCIDENTAL, CONSEQUENTIAL, SPECIAL OR CONTINGENT DAMAGES FOR BREACH OF ANY EXPRESS OR IMPLIED WARRANTY ON THIS PRODUCT. THE IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE ARE HEREBY EXPRESSLY DISCLAIMED. Some states do not allow the exclusion or limitation of incidental or consequential damages, or allow limitations on how long an implied warranty lasts, so the above limitations or exclusions may not apply to you. This limited warranty gives you specic legal rights, and you may have other rights, which vary from state to state.
11. Failure of the End User to comply with all of the Product Installation Requirements, Maintenance Requirements and End User Requirements may, at WhisperKOOL’s sole discretion, void this limited warranty.
12. No one has any authority to add to or vary the limited warranty on this Product.
3. Product Installation Requirements:
A. Prior to installing a WhisperKOOL Product, the End User must read the WhisperKOOL Owner’s Manual and
thereafter the End User must follow the required installation, use and maintenance procedures set forth by WhisperKOOL in WhisperKOOL’s Owner’s Manual. The Owner’s Manual is shipped with each Product and if another copy is needed, replacement copies can be downloaded from WhisperKOOL’s website (www.
whisperkool.com) or by contacting WhisperKOOL directly for a new copy of the Owner’s Manual. B. It is highly recommended that the End User obtain the assistance of a wine storage professional. C. Failing to address all of the variables associated with proper installation will cause the Product to operate
incorrectly and limit both the Product’s ability to cool and the longevity of the Product itself. D. The End User is responsible for all risks and costs of installation of the Product, including but not limited to
all labor costs as well as cost of any additional parts required for the proper and complete installation of the
Product. The End User is responsible for all risks and costs of removing the Product if limited warranty work is
required. E. The Product cannot operate at its optimum capacity if airow is constricted by ducting or venting the exhaust
side of the Product into a location with inadequate ventilation.
4. Maintenance Requirements
www.whisperkool.com | Page 33
It is the End User’s responsibility to clean o any accumulated dust, lint, or other debris from the front and rear intake grills; failure to do this on a regular basis will restrict the airow and may aect the Product’s ability to function properly. Periodically cleaning the Product’s vents will help assure maximum cooling eciency. The drain tube must also be checked and kept clean and free of debris and mold to maintain proper performance.
Mold is a natural living organism in the environment. It exists in the air in the form of microscopic spores that move in and out of buildings through doors, windows, vents, HVAC systems and anywhere else that air enters. Once it is discovered, mold must be addressed quickly and appropriately. Delayed or improper treatment of mold issues can result in costly and reoccurring repairs. If the End User suspects a mold problem, it is always best to hire a qualied and experienced mold remediation specialist.
5. Additional End User Costs And Responsibilities
The following items are not covered under any warranty and are the sole responsibility of the End User: A. End Users should satisfy themselves that the Product they are purchasing is suitable for their particular needs
and requirements, and thus no responsibility will be placed with WhisperKOOL for the End User’s decisions in this regard.
B. It is the End User’s responsibility to secure safe haven/storage for ANY AND ALL items that are being kept and
stored in the End User’s wine cellar, including any Product. WhisperKOOL takes no responsibility for the safety and preservation of the aforementioned items in the event that the environment becomes unsuitable to maintain a proper storage environment.
C. End User is responsible for initial installation costs, including, but not limited to, labor costs and the cost of any
additional parts necessary to complete the installation.
D. End User is responsible for all costs incurred for the installation and/or removal of the Product, or any part
thereof, unless such cost has been agreed by WhisperKOOL to be a warranty repair prior to the work being performed.
6. Sales and Use Tax
WhisperKOOL only collects California sales tax for orders shipped within the State of California; WhisperKOOL does not collect sales tax for orders shipped to other states. However, the Purchaser and the End User may be liable to the taxing authority in their state for sales tax and/or use tax on the Product. The Purchaser and the End User should each check with their state’s taxing authority for sales and use tax regulations.
7. Customer Service and Troubleshooting
WhisperKOOL’s customer service department is available to answer any questions or inquiries for End Users regarding a WhisperKOOL Product, as well as to assist in performing basic troubleshooting, Monday through Friday, from 6:30 a.m. to 4:00 p.m. PST, at telephone number 1-800-343-9463. WhisperKOOL Corporation is located at 1738 East Alpine Avenue, Stockton, California 95205.
8. Miscellaneous Terms and Conditions
A. Return Policy. All return inquiries must be made within thirty (30) calendar days of the original purchase of a
Product and are subject to a twenty ve percent (25%) restocking fee. Shipping costs are not refundable and the
Purchaser is responsible for all return shipping costs (including customs fees and duties, if applicable). B. Security Interest. WhisperKOOL retains a security interest in each Product until payment in full. C. Construction and Severability. Every provision of these Terms and Conditions shall be construed, to the extent
possible, so as to be valid and enforceable. If any provision of these Terms and Conditions is held by a court of
competent jurisdiction to be invalid, illegal or otherwise unenforceable, such provision will, to the extent so held,
be deemed severed from the contract of sale between Purchaser and WhisperKOOL, and all of the other non-
severed provisions will remain in full force and eect. D. Governing Law/Choice of Forum. The laws of the State of California (without regard for conicts of law) shall
govern the construction and enforcement of the these Terms and Conditions of Sale (Sections 1 through 9
inclusive, including Product Limited Warranty And Product Installation Requirements), and further these Terms
and Conditions of Sale shall be interpreted as though drafted jointly by WhisperKOOL and Purchaser. Any
Page 34 | 1-800-343-9463
InC 052413
dispute will be resolved by the courts in and for the County of San Joaquin, State of California, and all parties,
WhisperKOOL, Purchaser and End User, hereby irrevocably submit to the personal jurisdiction of such courts for that purpose. No waiver by WhisperKOOL of any breach or default of the contract of sale (including these Terms and Conditions of Sale) concerning a Product will be deemed to be a waiver of any preceding or subsequent breach or default.
E. Correction of Errors and Inaccuracies. These Terms and Conditions may contain typographical errors or other
errors or inaccuracies. WhisperKOOL reserves the right to correct any errors, inaccuracies or omissions, and to change or update these Terms and Conditions, at any time without prior notice.
9. Questions, Additional Information And Technical Assistance
A. Questions. If you have any questions regarding these Terms and Conditions or wish to obtain additional
information, contact us via phone at 1-800-343-9463 or please send a letter via U.S. Mail to:
Customer Service WhisperKOOL Corporation 1738 E Alpine Ave Stockton, CA 95205
Email: support@whisperkool.com Web: www.whisperkool.com
B. Technical Assistance. WhisperKOOL Customer Service is available Monday through Friday from 6:30 a.m. to
4:00 p.m. PST. The Customer Service representative will be able to assist you with your questions and warranty information more eectively if you provide them with the following:
1. The model and serial number of your WhisperKOOL UNIT.
2. The location of the system and installation details, such as ventilation, construction of your wine cellar, and room size.
Model ______________________________________ Serial Number __________________________
Installed by __________________________________________ Date __________________________
AInCellar
www.whisperkool.com | Page 35