WhisperKOOL copyrights this manual, the product design, and the design concepts, with all rights reserved. Your rights with
regard to the hardware and manual are subject to the restrictions and limitations imposed by the copyright laws of the USA.
Under copyright laws, this manual may not be copied, reproduced, translated, transmitted, or reduced to any printed or electronic
medium or to any machine-readable form, for any purpose, in whole or in part, without the written consent of WhisperKOOL.
Every eort has been made to ensure that the information in this manual is accurate. WhisperKOOL is not responsible for printing
or clerical errors.
WhisperKOOL reserves the right to make corrections or improvements to the information provided and to the related hardware at
any time, without notice.
Vinothèque and WhisperKOOL are registered trademarks, and ECE is a trademark of WhisperKOOL. All rights reserved.
Mention of third-party products is for informational purposes only and constitutes neither an endorsement nor a
recommendation. WhisperKOOL assumes no liability with regard to the performance or use of these products.
REV 02
CWSK.CM8000 051515
TABLE OF CONTENTS
Receiving & Inspecting the System ........................... 3
Before You Start .............................................. 4
Thank you for purchasing a WhisperKOOL Cold Weather Start Kit. We strive to provide the highest quality products and
the best possible customer service. If you have any questions about your system, please call us at 1-800-343-9463 or
visit WhisperKOOL.com.
Using the Manual
This Owner’s Manual is intended to provide detailed instructions for the installation of the Cold Weather Start Kit to
the Platinum Split 4000 cooling system. In order to ensure the proper longevity of your cooling unit, the equipment
should be installed as outlined in this Owner’s Manual. It is also vital to establish a proper care and maintenance
schedule. Please read and review this Owner’s Manual carefully and keep it for future reference.
What is a Cold Weather Start Kit?
The Cold Weather Start Kit is designed to insure the start of your cooling system despite frigid ambient temperature
that may result in failure of unit operation. The Cold Weather Start Kit will provide heat to the condensing unit when
ambient temperature is too low.
How Does the Cold Weather Start Kit Work?
The Cold Weather Start Kit provides heat to specic components in the condensing unit for proper operation when
the cooling system is in a below freezing setting. The Cold Weather Start Kit comes equipped with sensors to enable
an ideal temperature boost every time.
WARRANTY REGISTRATION
In order to activate the warranty of your system, the Verication and Operational
Documentation must be completed by the certied refrigeration technician
installing your system and submitted via mail, fax or e-mail.
Mail to:
WhisperKOOL
ATTN: Warranty Registration
1738 E. Alpine Avenue
Stockton, CA 95205-2505
USA
For the equipment warranty to be valid, WhisperKOOL requires that the installation is performed by a certied HVAC-R technician
(NATE certied technician is recommended) per the specications outlined in this Technician’s Manual. The technician shall be
required to be equipped with the proper tools of the trade including: R-134a, brazing equipment, dry nitrogen, an accurate
manifold gauge set (digital preferred), plus a 4 valve manifold set for evacuation, digital micron gauge, digital scale, deep vacuum
pump and accurate digital thermometers. Without the proper equipment, a professional job cannot be accomplished. Evidence of
the certied tech’s NATE# or other certication is required.
OROR
Fax to:
209-466-4606
Scan and e-mail to:
warranty@whisperkool.com
Page 2 | 1-800-343-9463
CWSK.CM8000 051515
RECEIVING & INSPECTING THE SYSTEM
Receiving and Inspecting the System
• Inspect the packaging for any obvious signs of damage or mishandling before opening the container.
• Note any discrepancies or visual damage on the Bill of Lading before signing.
Review the Packing Slip to Verify Contents
• Check the model number to ensure it is correct.
• Check that all factory options ordered are listed.
If any items listed on the packing slip do not match your order information,
contact WhisperKOOL Customer Service immediately.
Before You Start
1. Inspect the Kit before installation. If damage is found, please contact your distributor or WhisperKOOL
Customer Service at 1-800-343-9463.
2. Verify that you have received all of the items on the “Components Provided” list below and that the Kit
corresponds to your specific WhisperKOOL cooling system.
3. The system is intended for use in properly designed and constructed wine cellars. Hire a professional wine
storage consultant with a valid contractor’s license to build your wine cellar.
4. WhisperKOOL requires that all Systems and Cold Weather Start Kits be installed by a certified HVAC-R technician only.
5. The system is intended for use in properly designed and constructed wine cellars. Hire a professional wine
storage consultant with a valid contractor’s license to build your wine cellar.
6. Warranty is not active until a Warranty Checklist has been received, reviewed, and approved.
Condensing Unit Components Provided:
• (1) Omron relay Assembly
• (1) Bypass timer
• (1) Thermal Switch Assembly
• (1) Blue disconnect labeled 3
• (20) small white zip ties
• (1) zip lock bag containing thermal paste
• (2) 40 watt 120v silicone heaters
• (2) hose clamps
• (1) Magnacraft Relay Assembly
• (1) #13 Wire
Tools Needed:
• #1 Philips Head Screw Driver
• #2 Philips Head Screw Driver
• 5/16” Nut Driver
• 1/4” Nut Driver
• Drill
• Wire Cutters
• Wire Strippers
• Crimpers
• Needle Nose Pliers
• Utility Knife
• (1) closed end terminal
• (1) Set of AKA4460 Cold Weather Start Kit
Field Installation Instructions
• (1) Schematic Sticker
• (2) Silicone Heaters
Evaporator Unit Components Provided:
• (4) Lever Connectors
Components Needed (Not provided):
• 2 wire t-stat wire for routing from the
evaporator unit (Air Handler) to the
condensing unit.
• Use 18-20 wire stranded or solid
• (1) 120v/24v Transformers (with double
sided tape on bottom edge for mounting)
• (5) Zip Ties (3 for install and 2 additional)
• Platinum Split/WM & FD Evaporator Unit
Cold Weather Start Kit Field Installation
Instructions
After verifying that you have received all of the correct components for your specic system, please keep the Cold
Weather Start Kit in its original box until you are ready for installation. This will allow you to move the product safely
without damaging it. When you are ready to remove the product from the box, refer to the installation instructions.
TIP: Save your box and all packaging materials. They provide the only safe means of transporting/shipping the unit.
www.whisperkool.com | Page 3
BEFORE YOU START
Shut O Power going to the Evaporator and Condensing Unit.
Disconnect both the evaporator unit (Air Handler) and the
Condensing Unit from each power source.
WARNING: Failure to do so may cause electrical shock which
can result in injury or death.
A 2 wire 18-20 awg thermostat wire will need to be ran from the evaporator unit
to the condensing unit prior to installing the Cold Weather Start Kit.
Review the Tools Needed and Components Provided document prior to starting.
Page 4 | 1-800-343-9463
CWSK.CM8000 051515
CONDENSING UNIT COLD WEATHER START KIT INSTALLATION INSTRUCTIONS
1
Peel the label o of the receiver.
Peel the backing o one of the silicone heaters.
2
Place one of the silicone heaters on the receiver
3
in the location shown. The heater will not adhere
completely, there are hose clamps installed later in
these instructions that will keep them rmly in place.
NOTE: Line up the heater so the wires are located
at the fan shroud, and the bottom of the heater is
touching the liquid line.
Peel the backing o the other silicone heater.
4
www.whisperkool.com | Page 5
5
Place the other silicone heater on the receiver in
the location shown. The heater will not adhere
completely, there are hose clamps installed later in
these instructions that will keep them rmly in place.
Note: Line up the heater so the wires are directed
toward the fan shroud, and the back edge of the
heater is touching the back edge of the other
heater, as shown.
Slide the hose clamps on the receiver over the
6
silicone heaters. One at the top of the heaters and
one at the bottom. Secure in place as shown.
Wrap the spring from the Thermal Switch Assembly
7
around the liquid line and secure the clasp of the
spring to the thermal switch as shown.
Slide the thermal switch to the location shown
8
Thermal Switch Assembly
Page 6 | 1-800-343-9463
CWSK.CM8000 051515
9
Connect the blue disconnect labeled T to
the bottom terminal on the thermal switch.
10
11
Using a Phillips head screw driver remove the screw
on the front edge of the electrical box.
Using a Phillips head screw driver remove the screw
on the back edge of the electrical box.
12
Lift the top and remove it from the electrical box.
www.whisperkool.com | Page 7
13
Secure both wires into the H1 lever connector.
14
15
Using a at head screw driver loosen the six
terminal screws outlined in red, and remove
the wires from the terminals.
Cut the zip tie holding the high and low
pressure wires.
16
Remove the adhesive backing from the bottom
of the Magnacraft Relay Assembly.
Page 8 | 1-800-343-9463
CWSK.CM8000 051515
17
Place the Magnacraft Relay Assembly inside the
electrical box in the orientation shown. Press the
relay assembly rmly in place.
18
19
Remove the adhesive backing from the
Omron Relay Assembly.
Place the Omron Relay Assembly in the electrical
box in the orientation shown. Press the relay
assembly rmly in place.
20
Using a at head screw driver remove the
cable tie holder.
www.whisperkool.com | Page 9
21
Remove the adhesive backing from the
bypass timer.
22
23
Place the bypass timer inside the electrical box in
the orientation shown. Press the relay assembly
rmly in place.
Route the #10 wire with the blue disconnect
labeled T down through the cord squeeze.
24
Connect the blue disconnect labeled T from the
#10 wire to the top terminal on the thermal switch.
Page 10 | 1-800-343-9463
CWSK.CM8000 051515
25
Route the white wires from the heaters up into
the electrical box through the cord squeeze.
26
27
Pull the slack out of the wires and zip tie them in
the locations shown.
Zip tie the wires to the fan shroud as shown.
28
Connect the #9 wire with the blue disconnect
labeled 6 to the #6 terminal on the Omron Relay.
www.whisperkool.com | Page 11
29
Zip tie one of the high pressure switch wires and
low pressure switch wires together.
Blue Wires: low pressure switch.
Black Wires with butt splice: high pressure switch.
30
31
Secure one low pressure switch wire and one high
pressure switch wire inside the H1 lever connector.
Blue Wires: low pressure switch.
Black Wires with butt splice: high pressure switch.
Zip tie the wires going into the N1 and H1 lever
connectors as shown.
32
Connect the #2 wire with the red disconnect
labeled 1 to the #1 terminal on the bypass timer.
Page 12 | 1-800-343-9463
CWSK.CM8000 051515
33
Connect the #13 wire with the red disconnect
labeled 2 to the #2 terminal on the bypass timer.
6
2
1
34
35
Connect the other end of the #13 wire with the
blue disconnect labeled 4 to the #4 terminal
on the Omron relay.
Connect the #5 wire with the red disconnect
labeled 3 to the #3 terminal on the bypass timer.
4
2
3
36
Using the closed end terminal crimp the #1 wire with
the remaining low pressure switch wire.
www.whisperkool.com | Page 13
37
Secure the #4 wire into the #7 terminal on the
terminal block.
38
39
Secure the white wire from the #3 terminal on the
terminal block inside of the N lever connector.
Remove the blue disconnect from the #3 terminal
on the Delay on Break Timer.
40
Crimp the blue disconnect labeled 3 onto the loose
wire coming from the Johnson control. (It was
disconnected from the terminal block in step 16)
Page 14 | 1-800-343-9463
CWSK.CM8000 051515
41
Connect the blue disconnect labeled 3 from the
previous slide to the #3 terminal on the Delay on
Break Timer.
42
43
Cut the blue disconnect o the wire that was
connected to the #3 terminal of the Delay on Break
Timer. Strip the end of the wire to a length of 3/8”.
Secure the bare end of the wire from the
#1 terminal on the Delay on Break timer inside
of the C lever connector.
44
Secure the bare end of the wire coming from the
#0 terminal on the compressor contactor relay
inside of the C lever connector.
www.whisperkool.com | Page 15
45
Secure the remaining high pressure switch wire
into terminal #2 on the terminal block.
46
47
Route the 24v thermostat wires into the
electrical box through the cord squeeze.
Connect one of the 24v thermostat wires to the
grey #12 wire the using the wire nut provided.
48
Connect the other 24v thermostat wire to the
purple #11 wire the using the wire nut provided.
Page 16 | 1-800-343-9463
CWSK.CM8000 051515
49
Tidy wires and zip tie in locations shown.
Make sure that no wires are touching the
resistor when complete.
50
51
Remove the schematic sticker from the
electrical box top.
Peel the adhesive backing o of the schematic sticker.
52
Apply the schematic sticker to the
electrical box top as shown.
www.whisperkool.com | Page 17
53
Place electrical box top back on the electrical box,
and secure in place using the Phillips head
screws removed.
54
55
Cut the corner of the zip lock bag containing
the thermal paste.
Apply thermal paste to the surface of the
thermal switch.
56
Set thermal switch in location shown, making sure
the surface of the switch is making good contact
with the receiver.
The Cold Weather Start Kit has been successfully
installed on the condensing unit, next proceed to
the evaporator unit instructions.
Page 18 | 1-800-343-9463
CWSK.CM8000 051515
EVAPORATOR UNIT COLD WEATHER START KIT INSTALLATION INSTRUCTIONS
Before beginning the installation process, locate the
1
Evaporator Unit Cold Weather Start Kit. All parts for
the Evaporator Unit are located inside of this box.
Open box and remove the 24v transformer and the zip
2
lock bag.
The kit will include ve zip ties, four lever connectors,
3
one 6/32 kep nut, and one 120v/24v step down
transformer.
Using a Phillips head screw driver remove the 8 screws
4
holding the grill in place. (Set screws aside for later use)
www.whisperkool.com | Page 19
Remove the grill.
5
Locate the electrical panel access door, and remove the
6
two Phillips head screws. (Set screws and panel aside
for later use)
Remove the thumbscrew by rotating it counter
7
clockwise. (Set thumbscrew aside for later use)
Pull electrical panel down as shown.
8
Page 20 | 1-800-343-9463
CWSK.CM8000 051515
Remove the backing from the double sided tape on
9
the transformer.
10
12
Place one edge of the transformer under the control
box and the other edge over the 6/32 stud.
See next step for transformer orientation for units
equipped with the humidity option.
Push transformer against the electrical panel and secure
it in place using the 6/32 nut provided.
Make sure there is a distance of 1/16 “ between the
transformer and the capacitor.
13
Cut the zip tie o the wires entering the control box.
www.whisperkool.com | Page 21
14
Locate the blue wire entering the control box.
15
16
Cut the blue wire and strip each end to a length of 3/8”
Secure the two blues from the unit and the black wire
from the transformer into a lever connector.
17
Locate the white 16awg white wire coming out of the
control box.
Note: There may be other wires with white insulation
around them, they will be a little thicker do not cut
those wires.
Page 22 | 1-800-343-9463
CWSK.CM8000 051515
18
Cut the white wire and strip each end to a
length of 3/8”.
19
20
Secure the two white wires from the unit and the
white wire from the transformer into a lever connector.
Secure one of the thermostat wires and the yellow wire
from the transformer into a lever connector.
Note: The thermostat wire is the wire that was ran
from the evaporator unit to the condensing unit.
21
Secure the other thermostat wire and the blue wire from
the transformer into a lever connector.
Note: The thermostat wire is the wire that was ran
from the evaporator unit to the condensing unit.
www.whisperkool.com | Page 23
22
Zip tie wires in locations shown.
23
24
Tuck lever connectors into location shown.
Push electrical panel back up inside the unit and
reinstall the thumbscrew removed in step #8.
25
Re-install the electrical panel using the 2 Phillips head
screws removed in step #7.
Page 24 | 1-800-343-9463
CWSK.CM8000 051515
26
Install the grill back on the evaporator unit and secure
it to the unit using the 8 Phillips head screws removed
in step #5.
The Cold Weather Start Kit has been successfully installed on the Evaporator Unit. If the
installation process is complete on the condensing unit as well, plug both the condensing unit
and evaporator units back into a power source.
www.whisperkool.com | Page 25