Whirlpool WFE500M4HS, YWFE50M4HS Installation Instructions

INSTALLATION INSTRUCTIONS 24" (61.0 CM)
FREESTANDING ELECTRIC RANGES
INSTRUCTIONS D’INSTALLATION
POURCUISINIÈRES ÉLECTRIQUES
AUTOPORTANTES DE 24PO(61,0CM)
Table of Contents / Table des matières
RANGE SAFETY .............................................................................2
INSTALLATION REQUIREMENTS .................................................3
Tools and Parts .............................................................................3
Location Requirements ................................................................3
Electrical Requirements ...............................................................5
INSTALLATION INSTRUCTIONS ...................................................7
Unpack Range..............................................................................7
Backguard Assembly ...................................................................7
Install Anti-Tip Bracket .................................................................8
Electrical Connection - U.S.A. Only .............................................9
Verify Anti-Tip Bracket Is Installed
and Engaged ..............................................................................13
Level Range ................................................................................14
Storage Drawer ..........................................................................14
Complete Installation .................................................................14
Moving the Range ......................................................................15
SÉCURITÉ DE LA CUISINIÈRE ...................................................16
EXIGENCES D’INSTALLATION ...................................................17
Outils et pièces ...........................................................................17
Exigences d’emplacement .........................................................17
Spécications électriques ..........................................................19
INSTRUCTIONS D’INSTALLATION .............................................21
Déballage de la cuisinière ..........................................................21
Dosseret .....................................................................................21
Bride antibasculement ...............................................................22
Raccordement électrique – É.-U. seulement .............................23
Vérier que la bride antibasculement est bien installée et en-
gagée ..........................................................................................27
Réglage de l’aplomb de la cuisinière .........................................28
Tiroir de remisage .......................................................................28
Terminer l’installation .................................................................. 28
Déplacement de la cuisinière .....................................................29
IMPORTANT:
Save for local electrical inspector’s use.
Conserver ces instructions à l’usage de l’inspecteur des installations électriques local.
W11169656B
RANGE SAFETY
WARNING
Tip Over Hazard
A child or adult can tip the range and be killed.
Install anti-tip bracket to floor or wall per installation instructions.
Slide range back so rear range foot is engaged in the slot of the anti-tip bracket.
Re-engage anti-tip bracket if range is moved.
Do not operate range without anti-tip bracket installed and engaged.
Failure to follow these instructions can result in death or serious burns to children and adults.
Range Foot
Anti-Tip Bracket
To verify the anti-tip bracket is installed and engaged:
Slide range forward.
Look for the anti-tip bracket securely attached to floor or wall.
Slide range back so rear range foot is under anti-tip bracket.
See installation instructions for details.
2
INSTALLATION REQUIREMENTS
A
B
Tools and Parts
Gather the required tools and parts before starting installation. Read and follow the instructions provided with any tools listed here.
Tools needed
■ Tape measure
■ Flat-blade screwdriver
■ Phillips screwdriver
■ Level
■ Hammer
■ Hand or electric drill
■ Wrench or pliers
■ Marker or pencil
■ Masking tape
■ 3/8" (1 cm) and 5/16" (7.9 mm) nut driver
■ 1/8" (3.2 mm) drill bit (for wood oors)
Parts Supplied
Check that all parts are included.
C
A. Anti-tip bracket B. #12 x 1" screws (2) C. Plastic Anchors (2)
■ Anti-tip bracket must be securely mounted to oor or wall.
Thickness of ooring may require longer screws to anchor bracket to oor.
Parts needed
If using a power supply cord kit:
■ A UL listed power supply cord kit marked for use with
ranges. The cord should be rated at 250 V minimum, 40A or 50 A that is marked for use with nominal 1³⁄8" (3.5 cm) diameter connection opening and must end in ring terminals or open-end spade terminals with upturned ends.
■ A UL listed strain relief.
Check local codes. Check existing electrical supply. See “Electrical Requirements” section.
It is recommended that all electrical connections be made by a licensed, qualied electrical installer.
Location Requirements
IMPORTANT: Observe all governing codes and ordinances.
■ It is the installer’s responsibility to comply with the installation
clearances specied in this installation instructions. The model/serial/rating plate is located under the storage drawer. See the installation instructions on instructions on how to remove the storage drawer.
■ Cabinet opening dimensions that are shown must be used.
Given dimensions are minimum clearances.
■ The anti-tip bracket must be installed. To install the anti-tip
bracket shipped with the range, see “Install Anti-Tip Bracket” section.
■ Grounded electrical supply is required. See “Electrical
Requirements” section.
IMPORTANT: To avoid damage to your cabinets, check with your builder or cabinet supplier to make sure that the materials used will not discolor, delaminate or sustain other damage. This oven has been designed in accordance with the requirements of UL and CSA International and complies with the maximum allowable wood cabinet temperatures of 194°F (90°C).
Mobile Home - Additional Installation Requirements
The installation of this range must conform to the Manufactured Home Construction and Safety Standard, Title 24 CFR, Part 3280 (formerly the Federal Standard for Mobile Home Construction and Safety, Title 24, HUD Part 280). When such standard is not applicable, use the Standard for Manufactured Home Installations, ANSI A225.1/NFPA 501A or with local codes.
In Canada, the installation of this range must conform with the current standards CAN/CSA-Z240-latest edition, or with local codes.
Mobile home installations require:
■ When this range is installed in a mobile home, it must be
secured according to the instructions in this document.
■ Four-wire power supply cord or cable must be used in a
mobile home installation. The appliance wiring will need to be revised. See “Electrical Connection - U.S.A. Only” section.
3
Product Dimensions
SURFACE
A
OVEN
Cabinet Dimensions
Cabinet opening dimensions shown are for 25" (64.0 cm) countertop depth, 24" (61.0 cm) base cabinet depth and 36" (91.4 cm) countertop height.
A freestanding range may be installed next to combustible walls with zero clearance.
A
B
B
C
D
C
XX
E
F
D
A. 28" (71.1 cm) maximum depth with handle B. 377/8" (96.2 cm) overall height (maximum) with leveling legs
screwed all the way in*
C. 36" (91.4 cm) cooktop height (maximum) with leveling legs
screwed all the way in* D. 24" (60.9 cm) width E. 253/8" (64.4 cm) depth - back of range to front of cooktop** F. Model/serial/rating plate is located under the storage drawer
IMPORTANT: Range must be level after installation. Follow the instructions in the “Level Range” section. Using the cooktop as a reference for leveling the range is not recommended.
*Range can be raised approximately 3/4" (1.9 cm) by adjusting
the leveling legs.
**Front of door and drawer may extend further forward
depending on styling.
E
F
A. 13" (33.0 cm) maximum upper cabinet depth B. 24" (61.0 cm) minimum opening width C. For minimum clearance to top of cooktop, see NOTE* D. 243/16" (61.5 cm) minimum opening width E. Outlet - 3" (7.6 cm) from either cabinet, 8" (20.3 cm)
maximum from oor.
F. Cabinet door or hinges should not extend into the cutout.
*NOTE: 24" (61.0 cm) minimum when bottom of wood or
metal cabinet is covered by not less than 1/4" (0.64 cm) ame retardant millboard covered with not less than No. 28 MSG sheet steel, 0.015" (0.4 mm) stainless steel, 0.024" (0.6 mm) aluminum or 0.020" (0.5 mm) copper.
30" (76.2 cm) minimum clearance between the top of the cooking platform and the bottom of an uncovered wood or metal cabinet.
4
Electrical Requirements
Electrical Requirements - U.S.A. Only
If codes permit and a separate ground wire is used, it is recommended that a qualied electrical installer determine that the ground path and wire gauge are in accordance with local codes.
Do not use an extension cord. Be sure that the electrical connection and wire size are adequate
and in conformance with the National Electrical Code, ANSI/ NFPA 70-latest edition and all local codes and ordinances.
A copy of the above code standards can be obtained from:
National Fire Protection Association
1 Batterymarch Park
Quincy, MA 02169-7471
WARNING: Improper connection of the equipment-grounding conductor can result in a risk of electric shock. Check with a qualied electrician or service technician if you are in doubt as to whether the appliance is properly grounded. Do not modify the power supply cord plug. If it will not t the outlet, have a proper outlet installed by a qualied electrician.
Electrical Connection
To properly install your range, you must determine the type of electrical connection you will be using and follow the instructions provided for it here.
■ Range must be connected to the proper electrical voltage
and frequency as specied on the model/serial rating plate. The model/serial rating plate is located under the storage drawer. See the installation instructions on how to remove the storage drawer. Refer to the gures in “Product Dimensions” in the “Location Requirements” section.
■ This range is manufactured with the neutral terminal
connected to the cabinet. Use a 3-wire, UL listed, 40 or 50A power supply cord (pigtail) (see the following Range Rating chart). If local codes do not permit ground through the neutral, use a 4-wire power supply cord rated at 250 V, 40 or 50 A and investigated for use with ranges.
Specied Rating of
Range Rating*
Power Supply Cord Kit and Circuit Protection
120/240 V 120/208 V A
8.8 - 16.5 kW
16.6 - 22.5 kW
7.8 - 12.5 kW
12.6 - 18.5 kW
40 or 50** 50
*The NEC calculated load is less than the total connected
load listed on the model/serial rating plate.
**If connecting to a 50 A circuit, use a 50 A rated cord with
kit. For 50 A rated cord kits, use kits that specify use with a nominal 1³⁄8" (34.9 mm) diameter connection opening.
■ A circuit breaker is recommended.
■ The range can be connected directly to the circuit breaker
box (or fused disconnect) through exible or nonmetallic sheathed, copper or aluminum cable. See the “Electrical Connection - U.S.A. Only” section.
■ Allow 2 to 3 ft (61.0 cm to 91.4 cm) of slack in the line so that
the range can be moved if servicing is ever necessary.
■ A UL listed conduit connector must be provided at each end
of the power supply cable (at the range and at the junction box).
■ Wire sizes and connections must conform with the rating of
the range.
■ The wiring diagram is located on the back of the range.
If connecting to a 4-wire system:
This range is manufactured with the ground connected to the neutral by a link. The ground must be revised so the green ground wire of the 4-wire power supply cord is connected to the cabinet. See “Electrical Connection - U.S.A. Only” section.
Grounding through the neutral conductor is prohibited for new branch-circuit installations (1996 NEC); mobile homes; and recreational vehicles, or an area where local codes prohibit grounding through the neutral conductor.
When a 4-wire receptacle of NEMA Type 14-50R is used, a matching UL listed, 4-wire, 250 V, 40 or 50 A, range power supply cord (pigtail) must be used. This cord contains 4 copper conductors with ring terminals or open-end spade terminals with upturned ends, terminating in a NEMA Type 14-50P plug on the supply end.
The fourth (grounding) conductor must be identied by a green or green/yellow cover and the neutral conductor by a white cover. Cord should be Type SRD or SRDT with a UL listed strain relief and be at least 4 ft (1.22 m) long.
4-wire receptacle (14-50R)
The minimum conductor sized for the copper 4-wire power cord are:
40 A circuit 2 No.-8 conductors 1 No.-10 white neutral 1 No.-8 green grounding
If connecting to a 3-wire system:
Local codes may permit the use of a UL listed, 3-wire, 250 V, 40 or 50 A range power supply cord (pigtail). This cord contains 3copper conductors with ring terminals or open-end spade terminals with upturned ends, terminating in a NEMA Type 10-50P plug on the supply end. Connectors on the appliance end must be provided at the point the power supply cord enters the appliance. This uses a 3-wire receptacle of NEMA Type 10-50R.
3-wire receptacle (10-50R)
5
WARNING
Electrical Requirements - Canada Only
■ Check with a qualied electrical installer if you are not sure
the range is properly grounded.
Electrical Shock Hazard
Electrically ground range.
Failure to do so can result in death, fire, or electrical shock.
If codes permit and a separate ground wire is used, it is recommended that a qualied electrical installer determine that the ground path is adequate and wire gauge are in accordance with local codes.
Be sure that the electrical connection and wire size are adequate and in conformance with CSA Standard C22.1, Canadian Electrical Code, Part 1 - latest edition, and all local codes and ordinances.
A copy of the above code standards can be obtained from:
Canadian Standards Association
178 Rexdale Blvd.
Toronto, ON M9W 1R3 CANADA
Range Rating*
120/240 V 120/208 V A
8.8 - 16.5 kW
16.6 - 22.5 kW
*The NEC calculated load is less than the total connected load
listed on the model/serial/rating plate.
**If connecting to a 50 A circuit, use a 50 A rated cord with kit.
For 50 A rated cord kits, use kits that specify use with a nominal 13/8" (34.9 mm) diameter connection opening.
■ A time-delay fuse or circuit breaker is recommended.
■ This range is equipped with a CSA International Certied
Power Cord intended to be plugged into a standard 14-50R wall receptacle. Be sure the wall receptacle is within reach of range’s nal location.
■ Do not use an extension cord.
7.8 - 12.5 kW
12.6 - 18.5 kW
Specied Rating of Power Supply Cord Kit and Circuit Protection
40 or 50** 50
6
INSTALLATION INSTRUCTIONS
A
B
Unpack Range
WARNING
Excessive Weight Hazard
Use two or more people to move and install range.
Failure to do so can result in back or other injury.
1. Remove shipping materials, tape and lm from range.
2. Remove oven racks and parts package from inside oven and
on top of range.
3. Do not remove the shipping base at this time.
A. Shipping base
Remove the storage drawer. See the “Storage Drawer” section. Use a wrench or pliers to lower front leveling legs one-half turn.
Backguard Assembly
Tools Required:
Phillips Screwdriver
1. Lower Backguard down while guiding the Backguard slots down between the range top and the locking nuts.
2. Use the two assembly screws to attach the back corners of the Backguard to the side panels.
Parts Supplied:
(2) Assembly Screws# lOA x 1/2 Phillips Pan Hd Screw
A
B
C
B
A
A. Wrench or pliers B. Front leveling leg
A. Backguard slot B. Assembly screw
C. Locking nut
7
Install Anti-Tip Bracket
WARNING
Edge A
3. It is necessary to determine the nal location of the range before you can locate the anti-tip bracket. If the range is going to be located between cabinets, place the bracket so that Edge A sits at against the rear wall. Edge B should just touch the side of the cabinet sitting to the right side of the range.
Tip Over Hazard
A child or adult can tip the range and be killed.
Install anti-tip bracket to floor or wall per installation instructions.
Slide range back so rear range foot is engaged in the slot of the anti-tip bracket.
Re-engage anti-tip bracket if range is moved.
Do not operate range without anti-tip bracket installed and engaged.
Failure to follow these instructions can result in death or serious burns to children and adults.
1. Remove the anti-tip bracket from inside the literature bag assembly located in the oven.
2. Determine which mounting method to use: oor or wall. If you have a stone or masonry oor, you can use the wall mounting method. If you are installing the range in a mobile home, you must secure the range to the oor.
Location C
If there are no adjacent cabinets, align Edge B of the bracket with the edge of the range side. After the bracket has been placed mark the hole locations with a marker.
4. The anti-tip bracket can be attached to the oor or the wall. For wall mount application use Location C. When using location C, the screws must penetrate the wall sill plate located within the wall. For oor mount application use Location D or E. One screw on each side of the bracket is sufcient.
5. To mount anchor bracket to concrete or ceramic oor, use a drill with a 3/16" masonry bit to drill the two holes. Tap plastic anchor into mounting holes in oor with hammer. Line up holes in anti-tip bracket to holes in oor. Use the two screws provided to fasten anti-tip bracket to oor.
6. Unscrew the rear leg levelers approximately 1/2" so that the rear leg levelers will slide in under the anti-tip bracket. Slide range into the nal position after completing the gas and electrical connections to the range.
Anti-Tip Bracket
Location C
Edge B
Location D
Location E
8
B
A
A
Electrical Connection - U.S.A. Only
WARNING
Power Supply Cord
WARNING
Electrical Shock Hazard
Disconnect power before servicing.
Use a new 40 A power supply cord.
Plug into a grounded outlet.
Failure to follow these instructions can result in death, fire, or electrical shock.
1. Disconnect power.
2. Remove the terminal block cover screws located on the back
of the range.
Direct Wire
Electrical Shock Hazard
Disconnect power before servicing.
Use 8 gauge copper or 6 gauge aluminum wire.
Electrically ground range.
Failure to follow these instructions can result in death, fire, or electrical shock.
3. Add strain relie f. Style 1: Power supply cord strain relief
■ Assemble a UL listed strain relief in the opening that is
centered beneath the conduit bracket.
A. Terminal block cover B. Phillips screws (2)
Remove the top 10-31 hex nut and lugs from each of the 3 terminal blocks and set aside.
A. UL listed strain relief
■ Tighten strain relief screw against the power supply cord.
9
Style 2: Direct wire strain relief
A
D
(7.6 cm)
A
C
A
■ When direct wiring, relocate the conduit bracket so the left
hole is centered beneath the terminal block.
■ Assemble a UL listed conduit connector in the opening.
C
E
If your home has: And you will be
connecting to:
3-wire direct A circuit breaker
3/8"
(1.0 cm)
3"
box or fused disconnect
Go to Section:
3-wire connection: Direct wire
B
A. Removable retaining nut B. Conduit C. Conduit bracket D. Direct wire strain relief E. Power cord strain relief
NOTE : When direct wiring, use the hole on the left.
■ Tighten strain relief screw against the exible conduit.
4. Complete installation following instructions for your type of electrical connection:
■ 4-wire (recommended)
■ 3-wire (if 4-wire is not available)
Electrical Connection Options
If your home has: And you will be
Go to Section:
connecting to:
4-wire receptacle (NEMA type 14-50R)
A UL listed, 250 V minimum,
4-wire connection:
Power supply cord 40 A, range power supply cord
4-wire connection: Power Supply Cord
Use this method for:
■ New branch-circuit installations (1996 NEC)
■ Mobile homes
■ Recreational vehicles
■ In an area where local codes prohibit grounding through the
neutral
1. Part of metal ground strap must be cut out and removed.
B
A. Metal ground strap B. Discard C. Ground-link screw
2. Use a 5/16" (7.9 mm) nut driver to remove the ground-link screw from the back of the range. Save the ground-link screw and the end of the ground link under the screw.
3. Feed the power supply cord through the strain relief on the cord/conduit plate on bottom of range. Allow enough slack to easily attach the wiring to the terminal block.
B
4-wire direct A circuit breaker
3/8"
(1.0 cm)
box or fused disconnect
4-wire connection: Direct wire
C
5"
3-wire receptacle (NEMA type 10-50R)
(12.7 cm)
A UL listed, 250 V minimum,
3-wire connection: Power supply cord
D
40 A, range power supply cord
A. Terminal block B. Ground-link screw C. UL listed strain relief D. Power supply cord wires
10
4. Use a 5/16" (7.9 mm) nut driver to connect the green ground
wire from the power supply cord to the range with the ground-link screw and ground-link section. The ground wire must be attached rst.
Loading...
+ 22 hidden pages