Whirlpool WAHMS, WAHME Installation Instructions And Owner's Manual

AIR HANDLER INSTALLATION INSTRUCTIONS
Table of Contents
AIR HANDLER SAFETY................................................................. 1
INSTALLATION REQUIREMENTS................................................ 2
Tools and Parts............................................................................ 3
System Requirements ................................................................. 3
Location Requirements................................................................ 3
Electrical Requirements............................................................... 4
Ductwork Requirements.............................................................. 4
INSTALLATION INSTRUCTIONS.................................................. 4
Inspect Shipment......................................................................... 4
Installation Configurations ........................................................... 5
Install Condensate Drain.............................................................. 7
AIR HANDLER SAFETY
Install Ductwork ........................................................................... 8
Verify Orifice Size......................................................................... 8
Connect Refrigerant Lines........................................................... 8
Make Electrical Connections....................................................... 9
Complete Installation................................................................. 17
SEQUENCE OF OPERATION...................................................... 19
Cooling—Cooling Only or Heat Pump ...................................... 19
Heating—Electric Heat Only...................................................... 19
Heating—Heat Pump................................................................. 19
AIR HANDLER MAINTENANCE.................................................. 19
ASSISTANCE OR SERVICE ........................................................ 20
Accessories................................................................................ 20
Recognize this symbol as a safety precaution.
Recognize Safety Symbols, Words and Labels
The following symbols and labels are used throughout this manual to indicate immediate or potential hazards. It is the owner’s responsibility to read and comply with all safety information and instructions accompanying these symbols. Failure to heed safety information increases the risk of serious personal injury or death, property damage and/or product damage.
WARNING
Hazards or unsafe practices could result in property damage, product damage, severe personal injury or death.
Goodman 1
CAUTION
Hazards or unsafe practices may result in property damage, product damage, personal injury or death.
CAUTION
Hazards or unsafe practices may result in property or product damage.
Goodman 9
WARNING
Installation and repair of this unit should be performed ONLY by individuals meeting the requirements of an “Entry Level Technician” as specified by the Air-Conditioning, Heating and Refrigeration Institute (AHRI). Attempting to install or repair this unit without such background may result in product damage, personal injury or death.
Goodman 7
WARNING
HIGH VOLTAGE!
Disconnect ALL power before servicing.
Multiple power sources may be present.
Failure to do so may cause property damage, personal injury or death.
Goodman 6
Whirlpool® Models WAHMS, WAHME
WPIO-355B
WARNING
This product is factory-shipped for use with 208/240/1/60 electrical power supply. DO NOT reconfigure this air handler to operate with any other power supply.
Goodman 33
WARNING
To avoid property damage, personal injury or death due to electrical shock, this unit MUST have an uninterrupted, unbroken electrical ground. The electrical ground circuit may consist of an appropriately sized electrical wire connecting the ground lug in the unit control box to the building electrical service panel. Other methods of grounding are permitted if performed in accordance with the National Electric Code (NEC) /American National Standards Institute (ANSI) /National Fire Protection Association (NFPA) 70 and local/state codes. In Canada, electrical grounding is to be in accordance with the Canadian Electric Code (CSA) C22.1.
Goodman 34
CAUTION
When installing or servicing this equipment, safety clothing, including hand and eye protection, is strongly recommended. If installing in an area that has special safety requirements (hard hats, etc.), observe these requirements.
Goodman 35
WARNING
Do not connect to or use any device that is not design­certified for use with this unit. Serious property damage, personal injury, reduced unit performance and/or hazardous conditions may result from the use of such non-approved devices.
Goodman 36
DANGER
CARBON MONOXIDE POISONING HAZARD
Special Warning for Installation of Furnace or Air Handling Units in Enclosed Areas such as Garages, Utility Rooms or Parking Areas.
Carbon monoxide producing devices (such as an automobile, space heater, gas water heater, etc.) should not be operated in enclosed areas such as unventilated garages, utility rooms or parking areas because of the danger of carbon monoxide (CO) poisoning resulting from the exhaust emissions. If a furnace or air handler is installed in an enclosed area such as a garage, utility room or parking area and a carbon monoxide producing device is operated therein, there must be adequate, direct outside ventilation. This ventilation is necessary to avoid the danger of CO poisoning which can occur if a carbon monoxide producing device continues to operate in the enclosed area. Carbon monoxide emissions can be (re)circulated throughout the structure if the furnace or air handler is operating in any mode.
CO can cause serious illness including permanent brain damage or death.
Goodman 38
Goodman 37
WARNING
To prevent the risk of property damage, personal injury, or death, do not store combustible materials or use gasoline or other flammable liquids or vapors in the vicinity of this unit.
INSTALLATION REQUIREMENTS
These instructions are intended as a general guide only for use by qualified persons and do not supersede any national or local codes in any way. Compliance with all local, state, or national codes pertaining to this type of equipment should be determined prior to installation.
Read this entire instruction manual, as well as the instructions supplied in separate equipment, before starting the installation.
All models are designed for indoor installation only. The installation of the air handler, field wiring, warm air ducts, etc.
must conform to the requirements of the National Electrical Code, ANSI/NFPA No. 70 (latest edition) in the United States, and any state laws, and local ordinances (including plumbing or wastewater codes). Local authorities having jurisdiction should be consulted before installation is made. Such applicable regulations or requirements take precedence over the general instructions in this manual.
IMPORTANT: The United States Environmental Protection Agency (EPA) has issued various regulations regarding the introduction and disposal of refrigerants in this unit. Failure to follow these regulations may harm the environment and can lead to the imposition of substantial fines. These regulations may vary by jurisdiction. A certified technician must perform the installation and service of this product. Should questions arise, contact your local EPA office.
This product is designed and manufactured to permit installation in accordance with national codes. It is the installer’s responsibility to install this unit in accordance with national codes and/or prevailing local codes and regulations.
Install the conditioned air plenum, ducts and air filters (not provided) in accordance with NFPA 90B Standard for the Installation of Warm Air Heating and Air-Conditioning Systems (latest edition).
The air handler is provided with flanges for the connection of the plenum and ducts.
Air filters (not provided) must be listed as Class 2 furnace air filters.
The air handler can be used with R-410A from the factory. The air handler is shipped from the factory completely
assembled. Some models are configured for upflow air discharge only, and some models are configured for upflow or horizontal left-hand air discharge. The air handler cabinet conforms to 2 percent or less air leakage.
2
Do not remove the cabinet knockouts until it has been determined which knockouts will need to be removed for the installation.
Select the final installation position which best suits the site conditions. Consider required clearances, space, routing requirements for refrigerant line, condensate disposal, filters, ductwork, wiring, and accessibility for service. Refer to the air handler rating plate on the air handler for specific information.
Tools and Parts
Gather the required tools and parts before starting installation. Read and follow the instructions provided with any tools listed here.
Tools Needed
¹⁄₄" nut driver
Level
Screwdriver
Adjustable wrench
Tape measure
Hammer
Sealant
Parts Needed
Check local codes, check existing electrical supply, and read “Ductwork Requirements” and “Electrical Requirements” before purchasing parts.
UL-Listed wire connectors
Replacement orifice (if needed). See “Verify Orifice Size.” The
correct orifice size may be contained in the replacement orifice package located inside the control box of the outdoor unit. If this package does not contain the correct orifice for your air handler, you must purchase the correct orifice size.
System Requirements
The air handler is designed to match, and must be used with outdoor units as rated. The indoor units are manufactured with an interchangeable refrigerant metering orifice to provide optimum refrigerant control and system performance with a variety of different capacities of outdoor units.
In some cases, the rating of the outdoor unit may require that the air handler coil assembly orifice be changed to obtain rated performance.
Location Requirements
NOTE: When used on cooling applications, excessive sweating may occur when the air handler is installed in a very humid space.
If the air handler is installed in an unconditioned space,
sealant should be applied around the electrical wires, refrigerant tubing, and condensate lines where they enter the cabinet.
Electrical wires should be sealed on the inside where they exit
the conduit opening. Sealant is required to avoid air leakage and condensate from forming inside the air handler, control box, and on the electrical controls.
The air handler must be installed in such a way as to allow
free access to the coil/filter compartment and blower/control compartment.
The air handler must be installed in a level position to ensure
proper condensate drainage.
Installation Clearances
Non-Duct Return Closet Installation
The air handler can be installed in a closet with a false bottom to form a return air plenum or be installed with a return air plenum under the air handler.
Louvers or return air grilles are field supplied. Local codes may limit the application of systems without a duct return to single­story buildings.
For an air handler installed in a closet with a louvered return
opening, the minimum open area for the louvers will be as shown below.
2
18" and 24" (45.7 cm and
320 sq. in. (2,065 cm
61 cm) models
30" and 36" (76.2 cm and
360 sq. in. (2,323 cm
91.4 cm) models
42", 48" and 60" (106.7 cm,
450 sq. in. (2,903 cm
121.9 cm and 152.4 cm) models
If the free area is not known, assume a 25% free area for
wood louvers or a 75% free area for metal louvers or grilles.
Using the louver dimensions and the 25% or 75%
assumption, determine if the louver open area meets the minimum open area listed in the previous chart.
If the return air plenum is used, the return air grille should be
immediately in front of the opening in the plenum to allow for the free flow of return air.
When the air handler is not installed in front of the opening,
there must be adequate clearance around the air handler to allow for the free flow of return air.
The unit clearance from a combustible surface may be 0".
Allow a minimum of 24" (61 cm) in front of the unit for service
clearance.
Do not install the air handler in a location that violates the
instructions provided with the condenser.
If the unit is located in an area with high ambient temperature
and/or high humidity, the air handler may have condensation on the casing. On these installations, a wrap of 2" (5.1 cm) fiberglass insulation with a vapor barrier is recommended.
Consult all appropriate regulatory codes prior to determining
final clearances.
When installing this unit in an area that may become wet,
elevate the unit with a sturdy, non-porous material.
In installations that may lead to physical damage (for
example. in a garage) it is recommended that a barrier be installed to avoid such damage.
)
2
)
2
)
3
Electrical Requirements
WARNING
To avoid the risk of injury, electrical shock or death, the furnace must be electrically grounded in accordance with local codes or, in their absence, with the latest edition of the National Electric Code (NEC).
NOTES:
Use copper conductors only.
All field wiring must be done in accordance with National
Electrical Code, applicable requirements of UL and local codes where applicable.
Electrical wiring, disconnect means and overcurrent
protection are to be supplied by the installer. Refer to the air handler rating plate for maximum overcurrent protection, minimum circuit ampacity, as well as operating voltage.
The power supply must be sized and protected according to
the specifications supplied on the product.
This air handler is factory-configured for 240-volt, single
phase, 60 cycles. For 208-volt applications, see “208-Volt Conversion” in the “Make Electrical Connections” section.
For optional electric heater applications, see “Accessories.”
Refer to the instructions provided with the accessory for proper installation.
Goodman 31
Ductwork Requirements
Install the conditioned air plenum, ducts and air filters (not
provided) in accordance with NFPA 90B Standard for the Installation of Warm Air Heating and Air-Conditioning Systems (latest edition).
The air handler is provided with flanges for the connection of
the plenum and ducts.
The air handler is equipped with flanges that can form a filter
rack for the installation of the air filter, or the filter may be installed as part of the return air duct system.
Air filters must be listed as Class 2 furnace air filters.
CAUTION
Do not operate this product without all the ductwork attached.
Supply and return ductwork must be adequately sized to
Supply plenum should be the same size as the flanged
Goodman 39
meet the system’s air requirements and static pressure capabilities. To ensure correct system performance, the ductwork is to be sized to accommodate 375 to 425 CFM per ton of cooling with the static pressure not to exceed 0.5" W.C. Ductwork should be insulated with a minimum of 1" (2.5 cm) thick insulation with a vapor barrier in conditioned areas or 2" (5.1 cm) minimum in unconditioned areas.
opening provided around the blower outlet and should extend ideally at least 36" (91.4 cm) from the air handler before turning or branching off plenum into duct runs. The plenum forms an extension of the blower housing and minimizes air expansion losses from the blower.
INSTALLATION INSTRUCTIONS
Inspect Shipment
These air handlers are completely factory assembled, and all components are performance tested. Each air handler consists of a blower assembly, refrigerant coil, and controls, in an insulated galvanized steel factory finished enclosure. Knockouts are provided for electrical wiring entrance.
Check the air handler rating plate to confirm specifications
are as ordered.
Upon receipt of air handler, thoroughly inspect it for possible
shipping damage. Closely examine the air handler inside the carton if the carton is damaged.
If damage is found, it should be noted on the carrier’s freight
bill. Damage claims should be filed with the carrier immediately. Claims of shortages should be filed with the seller within 5 days.
NOTE: If any damages are discovered and reported to the carrier, do not install the air handler because your claim may be denied.
Return Air Filters
Each installation must include a return air filter. This filtering may be performed at the air handler or externally such as a return air filter grille. Air handlers mounted in the downflow orientation, including “B” series, require external filtering. A washable filter is available as an accessory. To ensure optimum performance, frequent filter cleaning is advised.
WVAHM WAHMS
1729 1824
3030 1931 3636
3642 3743 4860
WAHME Filter
Number
N/A FIL 18-32 1
1830 FIL 36-42 1
3036 3137 4260
FIL 48-61 1
Quantity Required
4
Installation Configurations
C
A
For ease in installation, it is best to make any necessary coil configuration changes before setting the air handler in place. See “Installation Configuration Options.”
Upflow air discharge contains only 1 drain pan.
Upflow or horizontal airflow contains 2 drain pans.
Vertical Installations
Upflow
The air handler must be supported on the bottom only and set on a field-supplied supporting frame with an air return opening. Securely attach the air handler to the supporting frame.
Horizontal Installations
Horizontal installations can be left-hand or right-hand air supply. Adequate support must be provided to ensure cabinet integrity. Ensure that there is adequate room to remove, service and access panels if installing in the horizontal position. For the correct horizontal coil installation, see “Installation Configuration Options” later in this section.
IMPORTANT:
This coil is provided with a secondary drain that should be
trapped and piped to a location that will give the occupant a visual warning that the primary drain is clogged. See “Install Condensate Drain.”
When an evaporator coil is installed in an attic or above a
finished ceiling, an auxiliary drain pan should be provided under the air handler as specified by most local building codes.
A B
A. Horizontal drain connections
(left or right hand)
B. Upflow drain connection C. Bottom/filter frame
Installation Configuration Options—Horizontal Right
NOTES:
Left to right airflow
As shipped from the factory
Drains
Suspended Cabinet Installation
NOTE: Air handlers cannot be installed horizontally lying on or
suspended from either the front or back of the air handler. It must be positioned with one side parallel to the floor when in the horizontal position.
The suspending means must be field fabricated, and should consist of 2 “cradles” made by attaching 2 rods to a length of angle iron or suitable gauge steel.
Installation Configuration Options—Upflow
NOTES:
As shipped from the factory.
Return in bottom.
Shading indicates proper line connections.
A
A. Drain connections B. Coil access cover C. Blower access cover
CB
Installation Configuration Options—Horizontal Left
Right to left airflow
Requires drain pan location change
A. Blower access cover B. Coil access cover C. Drain connections
.
Drains
BA
C
5
Downflow Conversion
C
D E
F
A B
C D
E
“D” nomenclature models are factory equipped for dedicated downflow operation and no field conversion is required. Conversion to downflow must be performed in an area that allows access to all sides prior to placing the air handler in its final location. To keep the evaporator coil pan from sweating, the DPI accessory insulation kit is to be used when performing this conversion.
NOTE: The DPI kit is not supplied with this product and is to be purchased separately. See the following chart for the correct DPI kit.
WVAHM or WAHMS Model Insulation Kit
1824 DPI18-30/20
3030/1931/3636 DPI36-42/20
3642/3743/4860/4961 DPI48-61/20
1. Before inverting the air handler, remove all access panels, the
coil rear channel bracket, and the filter close-off panel.
2. Remove the evaporator coil and the horizontal drain pan.
3. Discard the horizontal drain pan.
4. Install the plastic plug (provided) into the vacated access
panel.
5. Remove the 2 zee coil support brackets and insulation
retaining brackets.
6. Remove the tie bracket.
7. Install the DPI Insulation Kit onto the bottom of the drain pan.
Evaporator Coil Pan
A
A. 3" (7.6 cm) flat insulation retainer (both sides)
To complete the conversion, slide the evaporator coil into the chassis and attach the 3 access panels.
Evaporator Coil
Invert Air Handler
B
A
A. Access panel B. Return air side of unit C. Rear channel bracket
8. Install the zee coil supports and the wrapper stiffeners.
9. Install the tie bracket.
10. Install the rear channel bracket.
11. To avoid possible condensate “blow off,” the insulation
retainers are to be laid into the evaporator coil pan as shown in the “Evaporator Coil Pan” illustration.
D. Zee coil support bracket
E. Coil retaining bracket F. Tie b r ac k e t
F
A. Wrapper B. Insulation jacket C. Zee coil support
D. Wrapper stiffener
E. Drain pan insulation kit F. Blower assembly
NOTE: When the air handler is converted to the downflow position, the coil may protrude above the cabinet on some models.
Horizontal Conversion
Dedicated downflow models are not suitable for horizontal application and must not be used for this type of installation. The only field modification required for conversion to “Horizontal Right-Hand” is the removal of the plastic knockouts in the horizontal panel drain connections. To keep the horizontal drain pan from sweating in high humidity applications, it is recommended that a DPIH insulation accessory kit be used.
6
Loading...
+ 14 hidden pages