Whirlpool MDE22PDBYW0, MDG22PDBXW0, MDE22PRBYW0, MDE22PDBZW0, MDG22PDBWW0 Installation Instructions Manual

...
0 (0)
INSTALLATIONINSTRUCTIONS
COMMERCIALDRYER- Gas or Electric
INSTRUCTIONSPOUR L'INSTALLATIOND'UNE
SECHEUSECOMMERCIALE- A gaz ou (_lectrique
TABLEOF CONTENTS
DRYER SAFETY ............................................................................ 2
INSTALLATION REQUIREMENTS .............................................. 4
Tools and Parts .......................................................................... 4
Location Requirements .............................................................. 4
Electrical Requirements ............................................................ 6
Gas Supply Requirements ........................................................ 9
INSTALLATION INSTRUCTIONS - COIN SLIDE
AND COIN BOX ...................................................................... 11
INSTALLATION INSTRUCTIONS - GAS DRYER .................. 12
Make Gas Connection .............................................................. 12
Connect Vent ............................................................................ 12
Complete Installation .............................................................. 12
INSTALLATION INSTRUCTIONS- ELECTRIC DRYER ........ 13
Make Electrical Connection ...................................................... 13
Connect Vent ............................................................................ 20
Complete Installation .............................................................. 20
REVERSING THE DOOR SWING ............................................ 21
ELECTRONIC CONTROL SETUP .......................................... 22
MAINTENANCE INSTRUCTIONS ............................................ 22
WARRANTY ............................................................................ 23
TABLEDES MATIERES
SECURITte DE LA SECHEUSE .............................................. 24
EXIGENCES D'INSTALLATION ................................................ 26
INSTRUCTIONS D'INSTALLATION - GLISSI#RE ET
CAISSE ._ MONNAIE ................................................................ 33
INSTRUCTIONS D'INSTALLATION - SECHEUSE A GAZ ...... 33
Achever I'instaltation ................................................................ 34
iNSTRUCTiONS D'INSTALLATION - SECHEUSE ELECTRIQUE....35
Achever I'installation ................................................................ 35
INVERSION DU SENS D'OUVERTURE DE LA PORTE ............ 36
REGLAGE DE LA COMMANDE ELECTRONIQUE ................ 38
INSTRUCTIONS D'ENTRETIEN .................................................. 38
GARANTIE ................................................................................ 39
W10184516A
www.whirlpool.com W10184517A-SP
DRYERSAFETY
Your safety and the safety of others are very important.
We have provided many important safety messages in this manual and on your appliance. Always read and obey all safety
messages.
This is the safety alert symbol. This symbol alerts you to potential hazards that can kill or hurt you and others.
All safety messages will follow the safety alert symbol and either the word "DANGER" or "WARNING."
These words mean:
You can be killed or seriously injured if you don't immediately follow instructions.
You can be killed or seriously injured if you don't follow
instructions.
All safety messages will tell you what the potential hazard is, tell you how to reduce the chance of injury, and tell you what can happen if the instructions are not followed.
WARNING - "Risk of Fire"
- Clothes dryer installation must be performed by a qualified installer.
- install the clothes dryer according to the manufacturer's instructions and local codes,
- Do not install a clothes dryer with flexible plastic venting materials. {f flexible metal (foil type} duct is installed, it must be of a specific type identified by the appliance
manufacturer as suitable for use with clothes dryers. Flexible venting materials are known to collapse, be easily crushed, and trap lint. These conditions will obstruct
clothes dryer airflow and increase the risk of fire.
- To reduce the risk of severe injury or death, follow all installation instructions.
- Save these instructions.
m It is recommended that the owner post, in a prominent location, instructions for the customer's use in the event the customer smells
gas. This information should be obtained from your gas supplier.
m Post the following warning in a prominent location.
I FOR YOUR SAFETYDo not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance. I
WARNING: For your safety, the information in this manual must be followed to minimize the risk of fire or explosion, or to prevent property damage, personal injury, or death.
- Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this
or any other appliance.
- WHAT TO DO iF YOU SMELL GAS:
®Do not try to light any appliance.
Do not touch any electrical switch; do not use any phone in your building.
= Clear the room, building, or area of all occupants. = Immediately call your gas supplier from a neighbor's phone. Follow the gas supplier's
instructions.
= if you cannot reach your gas supplier, call the fire department.
- Installation and service must be performed by a qualified installer, service agency, or the gas supplier.
WARNING: Gas leaks cannot always be detected by smell.
Gas suppliers recommend that you use a gas detector approved by UL or CSA. For more information, contact your gas supplier. If a gas leak is detected, follow the "What to do if you smell gas" instructions.
In the State of Massachusetts, the following installation instructions apply: [] Installations and repairs must be performed by a qualified or licensed contractor, plumber, or gasfitter qualified or licensed by
the State of Massachusetts.
[] if using a ball valve, it shall be a T-handle type. [] A flexible gas connector, when used, must not exceed 3 feet.
IMPORTANT: The gas installation must conform with local codes, or in the absence of local codes, with the National Fuel Gas Code, ANSI Z223.1/NFPA 54 or the Canadian Natural Gas and Propane Installation Code, CSA B149.1.
The dryer must be electrically grounded in accordance with local codes, or in the absence of local codes, with the National Electrical Code, ANSI/NFPA 70 or Canadian Electrical Code, CSA C22.1.
3
iMPORTANT SAFETY iNSTRUCTiONS
WARNING: To reduce the risk of fire, electric shock, or injury to personswhen using the dryer, follow basic precautions,
including the following:
[] Read all instructions before using the dryer. [] Do not place items exposed to cooking oils in your dryer.
Items contaminated with cooking oils may contribute to a chemical reaction that could cause a load to catch fire.
[] Do not dry articles that have been previously cleaned in,
washed in, soaked in, or spotted with gasoline, dry= cleaning solvents, or other flammable or explosive substances as they give off vapors that could ignite or explode.
[] Do not allow children to play on or in the dryer. Close
supervision of children is necessary when the dryer is used near children.
[] Before the dryer is removed from service or discarded,
remove the door to the drying compartment. [] Do not reach into the dryer if the drum is moving. [] Do not install or store the dryer where it will be exposed
to the weather. [] Do not tamper with controls.
SAVE THESE INSTRUCTIONS
[] Do not repair or replace any part of the dryer or attempt
any servicing unless specifically recommended in this Use and Care Guide or in published user-repair instructions that you understand and have the skills to carry out.
[] Do not use fabric softeners or products to eliminate static
unless recommended by the manufacturer of the fabric softener or product.
[] Do not use heat to dry articles containing foam rubber or
similarly textured rubber-like materials.
[] Clean lint screen before or after each load. [] Keep area around the exhaust opening and adjacent
surrounding areas free from the accumulation of lint, dust, and dirt.
[] The interior of the dryer and exhaust vent should be
cleaned periodically by qualified service personnel.
[] See installation instructions for grounding requirements.
INSTALLATIONREQUIREMENTS
Gather the required tools and parts before starting installation. Read and follow the instructions provided with any tools
listed here.
Tools needed
[] 8" or 10" Pipe wrench [] Level [] 8" or 10" adjustable [] 1/4"socket and wrench
wrench [] Vent clamps
[] Flat-blade screwdriver [] Pipe-joint compound [] Phillips screwdriver resistant to LP gas
[] Adjustable wrench that [] Caulk gun and caulk (for
opens to 1" (2.5 cm) or 1" installing new exhaust (25 mm) hex-head socket vent) wrench [] Pliers
[] Security T-20 TORX_'t [] Stiff bladed putty knife
driver
Parts supplied Remove parts bag from dryer drum. Check that all parts were
included.
[] Foot boot (4) [] Dryer foot (4)
[] Service door lock cam
Explosion Hazard
Keep flammable materials and vapors, such as gasoline, away from dryer.
Do not install in a garage.
Failure to do so can result in death, explosion, or fire.
If installing a gas dryer: IMPORTANT: Observe all governing codes and ordinances.
[] Check code requirements: Some codes limit or do not permit
installation of clothes dryers in garages, closets, or sleeping
quarters. Contact your local building inspector.
[] Make sure that lower edges of the cabinet, plus the back and
bottom sides of the dryer, are free of obstructions to permit
adequate clearance of air openings for combustion air. See
"Recessed Area and Closet Installation Instructions" below
for minimum spacing requirements.
NOTE: The dryer must not be installed in an area where it will be exposed to water and/or weather.
1 ® TORX is a registered trademark of Acument Intellectual Properties, LLC.
4
Recessed Area and Closet Installation instructions
Product Dimensions 27" (68.6 cm} dryer
This dryer may be installed in a recessed area or closet. For recessed area and closet installations, minimum clearances
can be found on the warning label on the rear of the dryer. The installation spacing is in inches and is the minimum
allowable. Additional spacing should be considered for ease of installation, servicing, and compliance with local codes
and ordinances. If closet door is installed, the minimum unobstructed air opening
in the top and bottom is required. Louvered doors with equivalent air openings are acceptable.
The dryer must be exhausted outdoors. No other fuel-burning appliance may be installed in the same
closet as the dryer.
Minimum Installation Clearances
(35.6 cm)
max. _ l
Closet _ H / .... 1
15"
(38.1 cm)*
t
o o
_iiiiii-L.
r-mEz3---
I I
T............
0" (Ocm)
H........ II........
Recessed front view Closet side view
Additional clearances for wall, door, and floor moldings may be required or if external exhaust elbow is used.
48 inL (310 cm2)*
Front View O
24in_ -_-
(155 cm2)__j___
0" (Ocm)
closet
door
i
I_ 1" (2.5 cm)
3" (7.6 cm)
_!_
3" (7.6cm)
57/8,, _===
(15.2 cm)__
T'
T"
35"
(88.9 cm)
(2.5 cm)
_.-=--27" (68.8 cm)
=m|
I I
=_|
"_ ELECTRIC
BACK =_= =
VIEW I
13" I I
I I 4" (10.2 cm)
i 1 dis,
t
I
_ 11A"
(3.2 cm)
27_A'' (89.5 cm)
/
I
I
LEFTOR RIGHTSIDE 10W'
EXHAUST I I (26 cm)
1 "
29" (73.6 cm)
SIDE VlEW
|
I I
I f
I
41/4''
(10.8 cm)
(15.9 cm)
61A" l
31/4" I
.....
283/4 ''
(73.3 cm)
*Opening is the minimum for a closet door.
Louvered doors with equivalent air openings are acceptable.
i i
I/I T
31/2"I/I !
(8.9 cm) _'_ I
I"
(34.3 cm)
BOTTOM
EXHAUST
5
Recommended Ground Method
The dryer, when installed, must be electrically grounded in accordance with local codes or, in the absence of local codes, with the National Electrical Code, ANSl/NFPA 70, latest edition, or Canadian Electrical Code, CSA C22.1, and all local codes and ordinances.
_SHHHHHHHHHHHHHHHHHHHHHHHHHHHHHHHHHHHHHHHHHHHHHHH_
GROUNDING INSTRUCTIONS
Electrical Shock Hazard
Plug into a grounded 3 prong outlet. Do not remove ground prong. Do not use an adapter.
Do not use an extension cord. Failure to follow these instructions can result in death,
fire, or electrical shock.
IMPORTANT: The dryer must be electrically grounded in accordance with local codes and ordinances or, in the absence of local codes, with the National Electrical Code, ANSl/NFPA 70,
latest edition, or Canadian Electrical Code, CSA C22.1. If codes permit and a separate ground wire is used, it is
recommended that a qualified electrical installer determine that the ground path is adequate.
A copy of the above code standards can be obtained from:
National Fire Protection Association
One Batterymarch Park, Quincy, MA 02269
CSA international
8501 East Pleasant Valley Road
Cleveland, Ohio 44131-5575
[] A 120 volt, 60 Hz, AC only, 15- or 20-amp, fused electrical
circuit is required. A time-delay fuse or circuit breaker is also recommended. It is recommended that a separate circuit
serving only this dryer be provided.
[] For a grounded, cord-connected dryer: This dryer must be grounded. In the event of malfunction or breakdown, grounding will reduce the risk of electric shock by providing a path of least resistance for electric current.
This dryer is equipped with a cord having an equipment- grounding conductor and a grounding plug.The plug must be plugged into an appropriate outlet that is properly installed and grounded in accordance with all local codes
and ordinances.
WARNING" improper connection of the equipment-
grounding conductor can result in a risk of electric shock. Check with a qualified electrician or service representative or personnel if you are in doubt as to whether the dryer is properly grounded. Do not modify the plug provided with the
dryer: if it will not fit the outlet, have a proper outlet installed by a qualified electrician.
SAVE THESE INSTRUCTIONS
if using a power supply cord:
it is your responsibility
[] To contact a qualified electrical installer. [] To be sure that the electrical connection is adequate and in
conformance with the National Electrical Code, ANSl/NFPA
70-latest edition and all local codes and ordinances.
The National Electrical Code requires a 4-wire power supply connection for homes built after 1996, dryer circuits involved
in remodeling after 1996, and all mobile home installations.
A copy of the above code standards can be obtained from:
National Fire Protection Association, One Batterymarch Park, Quincy, MA 02269.
[] To supply the required 3 or 4 wire, single phase, 120/240 volt,
60 Hz., AC only electrical supply (or 3 or 4 wire, 120/208 volt
electrical supply, if specified on the serial/rating plate) on a separate 30-amp circuit, fused on both sides of the line. A
time-delay fuse or circuit breaker is recommended. Connect to an individual branch circuit. Do not have a fuse in the
neutral or grounding circuit.
[] Do not use an extension cord. [] If codes permit and a separate ground wire is used, it is
recommended that a qualified electrician determine that the
ground path is adequate.
Electrical Connection
Use a UL listed power supply cord kit marked for use with clothes dryers. The kit should contain:
[] A UL listed 30-amp power supply cord, rated 120/240 volt
minimum. The cord should be type SRD or SRDT and be at least 4 ft (1.22 m) long. The wires that connect to the dryer
must end in ring terminals or spade terminals with upturned
ends.
[] A UL listed strain relief.
If your ouUet looks like this:
4-wirereceptacle(14-30R)
Then choose a 4-wire power supply cord with ring or spade terminals and UL listed strain relief. The 4-wire power supply
cord, at least 4 ft (1.22 m) long, must have four 10-gauge copper wires and match a 4-wire receptacle of NEMA Type 14-30R. The
ground wire (ground conductor) may be either green or bare. The neutral conductor must be identified by a white cover.
If your ouUet looks like this:
To properly install your dryer, you must determine the type of electrical connection you will be using and follow the instructions
provided for it here. [] This dryer is manufactured ready to install with a 3-wire
electrical supply connection. The neutral ground conductor is
permanently connected to the neutral conductor (white wire)
within the dryer. If the dryer is installed with a 4-wire electrical supply connection, the neutral ground conductor must be
removed from the external ground connector (green screw),
and secured under the neutral terminal (center or white wire) of the terminal block. When the neutral ground conductor is
secured under the neutral terminal (center or white wire) of the terminal block, the dryer cabinet is isolated from the neutral
conductor.
[] If local codes do not permit the connection of a neutral
ground wire to the neutral wire, see "Optional 3-wire connection" section.
[] A 4-wire power supply connection must be used when the
appliance is installed in a location where grounding through the neutral conductor is prohibited. Grounding through the
neutral is prohibited for (1) new branch-circuit installations, (2) mobile homes, (3) recreational vehicles, and (4) areas where
local codes prohibit grounding through the neutral conductor.
3-wire receptacle (10-30R)
Then choose a 3-wire power supply cord with ring or spade terminals and UL listed strain relief. The 3-wire power supply
cord, at least 4 ft (1.22 m) long, must have three 10-gauge copper wires and match a 3-wire receptacle of NEMA Type 10-30R.
7
If connecting by direct wire: Power supply cable must match power supply (4-wire or 3-wire)
and be: [] Flexible armored cable or nonmetallic sheathed copper cable
(with ground wire), protected with flexible metallic conduit. All
current-carrying wires must be insulated.
[] 10-gauge solid copper wire (do not use aluminum). [] At least 5 ft (1.52 m) long.
GROUNDING INSTRUCTIONS
m For a grounded, cord-connected dryer: This dryer must be grounded. In the event of malfunction or breakdown, grounding will reduce the risk of electric shock by providing a path of least resistance for electric current. This dryer uses a cord having an equipment-grounding
conductor and a grounding plug. The plug must be plugged into an appropriate outlet that is properly installed and grounded in accordance with all local codes and ordinances.
m For a permanently connected dryer: This dryer must be connected to a grounded metal,
permanent wiring system, or an equipment-grounding conductor must be run with the circuit conductors and
connected to the equipment-grounding terminal or lead on the dryer.
WARNING: improper connection of the equipment-
grounding conductor can result in a risk of electric shock. Check with a qualified electrician or service representative or personnel if you are in doubt as to whether the dryer is properly grounded. Do not modify the plug on the power supply cord: if it will not fit the outlet, have a proper outlet installed by a qualified electrician.
SAVE THESE INSTRUCTIONS
[] To supply the required 4 wire, single phase, 120/240 volt, 60
Hz., AC only electrical supply on a separate 30-amp circuit,
fused on both sides of the line. A time-delay fuse or circuit
breaker is recommended. Connect to an individual branch
circuit.
[] This dryer is equipped with a CSA international Certified
Power Cord intended to be plugged into a standard 14-30R walt receptacle. The cord is 5 ft (1.52 m) in length. Be sure watt receptacle is within reach of dryer's final location.
4-wirereceptacle(14-30R)
[]
Do not use an extension cord.
If you are using a replacement power supply cord, it is
recommended that you use Power Supply Cord Replacement
Part Number 9831317. For further information, please
reference the service numbers located in the "Assistance or Service" section.
GROUNDING INSTRUCTIONS
[] For a grounded, cord-connected dryer: This dryer must be grounded. In the event of malfunction or breakdown, grounding will reduce the risk of electric shock by providing a path of least resistance for electric current.
This dryer is equipped with a cord having an equipment- grounding conductor and a grounding plug. The plug must be plugged into an appropriate outlet that is properly installed and grounded in accordance with all local codes
and ordinances.
Electrical Shock Hazard
Plug into a grounded 4 prong outlet, Failure to do so can result in death or electrical shock.
It is your responsibility
[]
To contact a qualified electrical installer.
[]
To be sure that the electrical connection is adequate and in conformance with the Canadian Electrical Code, C22.1-1atest
edition and all local codes. A copy of the above codes standard may be obtained from: Canadian Standards
Association, 178 Rexdate Blvd., Toronto, ON M9W 1R3
CANADA.
WARNING: improper connection of the equipment-
grounding conductor can result in a risk of electric shock. Check with a qualified electrician or service representative or personnel if you are in doubt as to whether the dryer is properly grounded. Do not modify the plug provided with the
dryer: if it will not fit the outlet, have a proper outlet installed by a qualified electrician.
SAVE THESE INSTRUCTIONS
_iiiiiiii_i!:_!!iil;iiii_i:!ii?ili:i::iiiii?¸!i:!_%i?_!/ii:ii::'_!i!:_:_iiii_:_i_i_!!%:i:!!ii_
Explosion Hazard
Use a new CSA International approved gas supply line.
Install a shut=off valve. Securely tighten all gas connections.
if connected to LP, have a qualified person make sure gas pressure does not exceed 13" (33 cm) water
column.
Examples of a qualified person include:
licensed heating personnel, authorized gas company personnel, and
authorized service personnel.
Failure to do so can result in death, explosion, or fire.
Gas Supply Line
Recommended method
[] Provide a gas supply line of 1/2"rigid (IPS) pipe to the dryer
location. Pipe joint compounds that resist the action of LP gas must be used. Do not use TEFLON_'ttape with LP gas.
Minimum tubing diameter for LP gas is 1/2".Usually, LP gas suppliers determine the size and materials used in the system.
Alternate method [] The gas supply may also be connected using %" approved
copper or aluminum tubing. If the total length of the supply line is more than 20 ft. (6.1 m), larger tubing will be required.
If using natural gas, do not use copper tubing. Pipe joint compounds that resist the action of LP gas must be used.
Flexible metal appliance connector:
[] It is recommended that a new flexible stainless steel gas line,
design-certified by CSA International, be used for connecting
the dryer to the gas supply line. (The gas pipe which extends through the lower rear of the dryer is provided with %" mate
pipe thread.)
IMPORTANT: Observe all governing codes and ordinances. This installation must conform with all local codes and ordinances. In the absence of local codes, installation must
conform with American National Standard, National Fuel Gas Code ANSI Z223.1/NFPA 54 or CAN/CSA B149.
A copy of the above code standards can be obtained from:
National Fire Protection Association
One Batterymarch Park, Quincy, MA 02269
CSA International
8501 East Pleasant Valley Road
Cleveland, Ohio 44131-5575
The design of this dryer has been certified by CSA International for use at altitudes up to 10,000 feet (3048 m) above sea level at
the B.T.U. rating indicated on the model/serial plate. Burner input adjustments are not required when the dryer is operated up to
this elevation. When installed above 10,000 feet (3048 m), a four percent (4%)
reduction of the burner B.T.U. rating shown on the model/serial plate is required for each 1,000 foot (305 m) increase in elevation.
For assistance when converting to other gas types and/or installing above 10,000 feet (3048 m) elevation, contact your
local service company.
Type of Gas
This dryer is equipped for use with natural gas. It is design- certified by CSA International for LP (propane and butane) gases
with appropriate conversion. No attempt shall be made to convert the dryer from the gas specified on the serial/rating plate for use
with a different gas without consulting the serving gas supplier. Conversion must be done by a qualified service technician.
Gas conversion kit part numbers are listed on the gas valve burner base.
[] Do not kink or damage the flexible stainless steel gas line
when moving the dryer.
Rigid pipe connection:
The rigid pipe connection requires a combination of pipe fittings to obtain an in-line connection to the dryer.
[] Must include a shutoff valve:
The supply line must be equipped with a manual shutoff
valve installed within 6 ft. (1.8 m) of dryer in accordance with National Fuel Gas Code, ANSI Z223.1. In Canada, an individual manual shutoff valve must be installed in
accordance with the B149 installation codes CAN/CGA B149.1 and CAN/CGA B149.2. This valve should be located
in the same room as the dryer. It should be in a location that allows ease of opening and closing. Do not block access to
shutoff valve. The valve is for turning on or shutting off gas
to the dryer.
B D
\
A. Gas supply line
B. Shutoff valve "open" position C. To Dryer D. NPT fitting
1-®TEFLON is a registered trademark of E.I. Du Pont De Nemours and Company.
9
[] Installed in a confined area:
Ifthe dryer is installed in a confined area such as a bathroom or closet, provision must be made for enough
air for combustion and ventilation. Check governing codes and ordinances or refer to the "Recessed Area
and Closet Installation Instructions" in the Location
Requirements section.
Gas Supply Pressure Testing
A 1/8"NPT minimum plugged tapping, accessible for gauge testing, must be installed immediately upstream of the installed shut-off valve to the dryer.
The dryer must be disconnected from the gas supply piping system during any pressure testing of the system at test
pressures in excess of 1Z2"psig.
Exhaust hood must be at least 12" (30.5 cm) from the ground or any object that may be in the path of the exhaust (such as
flowers, rocks, or bushes). If using an existing vent system, clean lint from the entire length
of the system and make sure exhaust hood is not plugged with lint. Replace any plastic or metal foil vent with rigid metal or
flexible metal vent. Plan installation to use the fewest number of elbows and turns.
ExhaustAir Flow A.Good B.Better
Allow as much room as possible when using elbows or making turns. Bend vent gradually to avoid kinking.
Vent outlet is located at the back of the dryer, at bottom center. The vent can be routed up, down, left, right, behind the dryer,
or straight out the back of the dryer.
Fire Hazard
Use a heavy metal vent, Do not use a plastic vent.
Do not use a metal foil vent, Failure to follow these instructions can result in death
or fire.
WARNING; To reduce the risk of fire, this dryer MUST BE EXHAUSTED OUTDOORS.
[] The dryer vent must not be exhausted into any gas vent,
chimney, wall, ceiling, attic, crawtspace, or a concealed space of a building.
[] Only rigid or flexible metal duct shall be used for exhausting.
[] Do not use an exhaust hood with a magnetic latch. [] Do not install flexible metal vent in enclosed walls, ceilings,
or floors.
[] 4" (102 mm) heavy metal vent and clamps must be used. Do
not use plastic or metal foil vent.
[] Use clamps to seat all joints. The duct shall not be assembled
with screws or other fastening means that extend into the duct and catch lint. Do not use duct tape.
[] The total length of flexible metal vent shall not exceed 8 ft
(2.4 m).
iMPORTANT: Observe all governing codes and ordinances. Rigid metal vent is recommended to prevent crushing and
kinking. Flexible metal vent must be fully extended and supported when
the dryer is in its final position. Remove excess flexible metal vent to avoid sagging and kinking that may result in reduced airflow
and poor performance. An exhaust hood should cap the vent to prevent rodents and
insects from entering the home or business.
Maximum length of vent system depends upon the type of vent used, number of elbows, and type of exhaust hood. The
maximum length for rigid vent is shown in the chart.
Maximum Vent Length
4" (10.2 cm) Diameter Exhaust Hoods
Rigid Metal Vent
; ;i ; r ; r r ; ; r ri r; r r ; r; r r
No.of90°turns BoxHoodandLouveredStyle AngledHoodStyle
0 130 ft, (39,8 m) 129 ft, (39,3 m)
1 125 ft, (38,1 m) 119 ft, (36,3 m) 2 115 ft, (35,1 m) 109 ft, (33,2 m) 3 106 ft, (32,3 m) 100 ft, (30,5 m) 4 98 ft. (29.9 m) 92 ft. (28.0 m)
For vent systems not covered by the vent specification chart, see your parts distributor.
If dryer is installed in a confined area, such as a bedroom, bathroom, or closet, provision must be made for enough air
for combustion and ventilation. (Check governing codes and ordinances.) See "Recessed Area and Closet Installation
Instructions" in the Location Requirements section. A 4" (10.2 cm) outlet hood is preferred. However, a 21/," (6.4 cm)
outlet exhaust hood may be used. A 21/2`' (6.4 cm) outlet creates greater back pressure than other hood types. For permanent
installation, a stationary vent system is required.
10
[] A main vent can be used for venting a group of dryers. The
main vent should be sized to remove 200 CFM of air per
dryer. Large-capacity lint screens of proper design may be
used in the main vent if checked and cleaned frequently. The room where the dryers are located should have make-up air
equal to or greater than the CFM of all the dryers in the room.
[] Back-draft Damper Kit, Whirlpool Part No. 3391910, is
available from your dealer and should be installed in the vent of each dryer to prevent exhausted air from returning into the
dryers and to keep the exhaust in balance within the main vent. Unobstructed air openings are required.
Each vent should enter the main vent at an angle pointing in the direction of the airflow. Vents entering from the opposite side
should be staggered to reduce the exhausted air from interfering with the other vents.
The maximum angle of each vent entering the main vent should be no more than 30°.
A
Keep air openings free of dry cleaning fluid fumes. Fumes create acids which, when drawn through the dryer heating units, can
damage dryers and loads being dried. A clean-out cover should be located on the main vent for periodic
cleaning of the vent system If an exhaust hood cannot be used:
B
A U °
O_ _ ................E
2 ft. (61 cm) min. above highest point of building
air flow _ B _---
A.Individualdryervent B. Mainvent
INSTALLATIONINSTRUCTIONS- COINSLIDEANDCOINBOX
The console houses the factory-installed accumulator timer with actuating arm and button.
The factory-installed timer is set to provide 45 minutes (4 pins) of drying time when activated by the coin slide. Timer cams for
30-minute (6 pins) and 60-minute (3 pins) drying times are included in the parts bag.
The coin slide mechanism, control panel lock and key, and coin box lock and key are not included and are available from usual
industry sources.
Excessive Weight Hazard Use two or more people to move and install dryer. Failure to do so can result in back or other injury.
NOTE: Slide dryer onto cardboard or hardboard before moving to avoid damaging floor covering.
1. Using two or more people, move dryer to desired installation location.
2. Take tape off front corners of dryer. Open dryer and remove
the literature and parts packages. Wipe the interior of the drum thoroughly with a damp cloth.
G.Roof
The outside end of the main vent should have a sweep elbow directed downward. If the main vent travels vertically through the
roof, rather than through the walt, install a 180° sweep elbow on the end of the vent at least 2 ft. (61 cm) above the highest part of
the building. The opening in the wall or roof shall have a diameter 1Z2"(1.3 cm) larger than the vent diameter. The vent should be
centered in the opening. Do not install screening or cap over the end of the vent.
3=
Take two of the cardboard corners from the carton and place them on the floor in back of the dryer. Firmly grasp the body
of the dryer and gently lay it on its back on the cardboard corners.
4=
With one of the legs in hand, check the ridges for a diamond
marking. That's how far the leg is supposed to go into the hole.
5=
Start to screw the leveling legs into the holes by hand. (Use a small amount of liquid detergent to lubricate the screw
threads so it is easier to turn the legs.) Use a 1" wrench or socket wrench to finish turning the legs until you reach the diamond mark.
Now stand the dryer up.
6=
Remove the service
door of the meter case
by lifting it up at the back. Install the money-
accepting device. (Refer to manufacturer's
instructions for proper installation.)
For dryers using coin
slides, use the adapter kit supplied with the dryer.
7=
Replace the meter case service door. Put the coin vault with lock and key in the meter case opening.
8.
Remove cardboard or hardboard from under dryer.the legs of
the dryer up or down until the dryer is level.
11
INSTALLATIONINSTRUCTIONS- GASDRYER
Excessive Weight Hazard
Use two or more people to move and install dryer. Failure to do so can result in back or other injury.
1. Remove red cap from gas pipe on back of dryer.
2. Connect gas supply to dryer. Use a pipe thread compound
approved for the type of gas supplied. If flexible metal tubing
is used, be certain there are no kinks. If necessary for service, open the front lower service panel by
using a V4" nutdriver to remove the 2 hex-head screws from
the bottom of the panel. Then lift up on the panel while pulling the bottom of the panel away from the dryer.
3. Open the shutoff valve in the gas supply line and make sure
the unit has its own gas supply opened.
4. Test all connections by brushing on an approved noncorrosive leak-detection solution. Bubbles will show a leak. Correct any
leak found.
1=
With dryer in final position, place level on top of the dryer, first side to side; then front to back. }fthe dryer is not level, adjust
the legs of the dryer up or down until the dryer is level.
Electrical Shock Hazard
Plug into a grounded 3 prong outlet.
Do not remove ground prong. Do not use an adapter.
Do not use an extension cord. Fai{ure to follow these instructions can result in
death, fire, or electrical shock.
1. Using a 4" (10.2 cm) clamp, connect vent to exhaust outlet in dryer. If connecting to existing vent, make sure the vent is
clean. The dryer vent must fit over the dryer exhaust outlet and inside the exhaust hood. Make sure the vent is secured
to exhaust hood with a 4" (10.2 cm) clamp.
2. Using two or more people, move dryer to desired installation location. Do not crush or kink vent. Make sure dryer is level.
3. Check to be sure there are no kinks in the flexible gas line.
2. Plug into a grounded 3 prong outlet.
3. Check dryer operation (some accumulated time may be on the timer due to factory testing):
Close dryer door. Insert coins in slide and press slide in slowly. (Operating time will accumulate per number of coins
and type of timing cam used.) Select the Whites and Colors cycle and let the dryer run for at least five minutes.
NOTE:
Dryer door must be closed for dryer to operate.
4. Open the dryer door. Check that the inside of the dryer is warm. If the burner does not ignite and you can feel no heat
inside the dryer, wait for five minutes. Check that all supply
valve controls are in "ON" position and that the electrical cord
is plugged in. Repeat five-minute test.
5. Check lint screen for debris and other obstructions.
6. Restart the dryer and allow it to complete the Whites and Colors cycle to make sure it is working properly.
12
Loading...
+ 28 hidden pages