Whirlpool LTE6234DZ2, LTE6234DZ0, LTE6234DQ1, LTE6234DZ1, LTE6234DT2 Installation Guide

...
IMPORTANT:
Large Capacity ThinTwin
Washer, Dryer - 120/240 Volt
Installation Instructions
©©©©
Read and save
these instructions.
IMPORTANT:
with the homeowner.
Homeowner: Keep Installation Instructions
for future reference,
Save Installation Instructions for local
electrical inspector's use.
www,whirlpool.com
Part No, 3397616 Rev. B
Before you start...
Your safety and the safety of others are
very important,
Wehaveprovided many important safety messages in this manualandonyour appliance•Always read and obey all safety messages.
This is the safety alert symbol•
_P_ hazardsthat can kill or hurtyou and
This symbol alerts youto potential
others•
All safety messageswill folJowthe safetyalert
symbol and either the word "DANGER"or "WARNING".Thesewords mean:
Explosion Hazard
Keep flammable materials and vapors,
such as gasoline, away from dryer.
Failure to do so can result in death,
explosion, or fire.
Location: Should be rarge enough to
fully open dryer door to 90° See Panel G for "Recessed and closet installation
instructions" and "Product dimensions." Grounded electrical connection is
required. See "Electrical requirements" Standpipe drain system: Needs
a two-inch diameter stand with minimum carry-away
capacity of 17 gallons per minute. Top of standpipe must be at least 34 inches high and no higher than 72 inches from
floor.
Floor drain system requires a siphon break
285320, available from a
Whglpool-authorized
parts distributor
Support: Floor must be sturdy enough to support washer/dryer weight, with and clothes, of 500 pounds.
You can be killed orseriously injured ifyou
don'timmediatel_follow instructions.
You can be killed orseriously injured if youdon't follow instructions.
All safety messageswill tell you what the potential
hazardis, tell you how to reducethe chanceof injury, and tellyou what can heppee ifthe
instructions are not followed•
Check location where washer/dryer will
be installed Proper installation isyour responsibility. The washer/dryer must nol
be installed or stored in an area where rt
will be exposed to water and/or weather Make sure you have everything necessary for correct
installation.
Hot and cold water faucets: Must be within
4 feet of the back of the washer/dryer and
provide water pressure of 5 100 PSh
Level floor:
1-inch maximum
slope under entire washer/dryer.
Do Not store or operate washer/dryer below 32°F (some water may remain in
washer), proper operation of dryer cycles requires temperatures above
45°F. See Use & Care Guide for
"Winterizing" information.
Check code requirements: Some codes
limit or do not permit installation of
clothes dryers _ngarages, closets,
mobile homes and sleeping quarters.
Contact your local building inspector. Chock utilities: Proper, water and
electrical supply connections must be available.
Water heater: Set to deliver 140_F water to the washer
tub drain system: Needs a
allan laundry tub. Top of tub must be at least 34 inches high and no higher than 72 inches from floor,
If a longer drain hose is needed, drain hose (Part NO. 388423) and
hose extension kit (Part No. 285442) are available from a Whirlpool- authorized parts distributor.
may be exhausted from the rear or left or right side Exhausting through the side requires Part No.
279823. See "Exhaust requirements," Panels C and D
Four-inch metal exhaust vent is required.
SEERECESSEDAREA INSTRUCTIONS ON PANELG.
Important: Observe all governing codes and
ordinances.
Tools and materials
needed for installation: Power supply cord
U L. listed, 120/240-volt minimum, 30- ampere, dryer power supply cord kit
utility -- --
knlta
Electrical Shock Hazard feet long. The wires that connect to the
_r_Sho Local codes may permit the use of a
Plug into a grounded 4-prong outlet, dryer must end with ring terminals or Failure to do so can result in death or spade terminals with upturned ends, electrical shock. A 3/4", U.L.-listed strain relief must be
____ Electz_c! _quirements and 2). upthrne*dta_r,inalssbade-- rendswith_ '
A tour-wire or three-wire, single phase,
120/240-volt, 60-Hz AC only electrical
supply (or four-wire or three-wire,
_ pllers 3/4" U.L-llstad NEUTRAL
fe:_-btode
screwdriver adjustable
wrench (two
requlred) g
120/208-volt, if specified on the model/serial rating plate) is required on
a separate, 30-ampere circuit, fused on
both sides of the line. A time-delay fuse
or circuit breaker isrecommended The
model/serial rating plate is located in the door well behind the dryer door on the front of the opening.
It is the personal responsibilily and obligation of the customer to contact a
qualified electrician to assure that the electrical Installation is adequate and in
conformance with the National Electrical Code, ANSI/NFPA 70 -- latest
edition*, and all local codes and ordinances
Coples of the standards llstad above may be obtained from:
Notional Fire Protection ASSOCiation
Batter/march Park Quincy, Massachusetts 02269
NEUTRAL Thls blade connected eng terminals
Panel A
(pigtail), Power supply cord should be Type SRD or SRDTand be at least four
installed where the power supply cord connects to the dryer (see Figures 1
ground prong (green) ring \
Four-wire power supply cord
NI:MA 14-30P
Figure I
terminals with
shaln relier (white or center)
Three-wire power supply cord
NEMA 10-30P
Figure 2
tam_lnals
For use where local codes
permit use of flexible power supply cord,
tour-wlre three-wire
receptacle(14-30R) receptacle(10-30R)
Figure 3 Figure 4
Four-wire installation is recommended (required for mobile homes): The power
supply cord must have four, No.-] 0 copper wires and match a four-wire
receptacle of NEMA Type 14-30R (see
Figure 3). The fourth wire (ground conductor) must be identified with a green cover and the neutral conductor
by a white cover
Three-wire installation (if a four-wire system isnot available): The power
supply cord must have three, No,-1O copper wires to match a three-wire receptacle of NEMA Type 10-30R (see Figure 4).
Direct wire
The washer/dryer can be connected directly to fused disconnect or circuit
breaker box with four-wire or three-wire flexible armored or non-metallic
sheathed copper cable (with ground wire), Do Not use two-wire with bare ground wire All current-carrying wires
must be insulated A conduit connector must be installed
at junction box. USEONLY 10 GAUGE SOLID COPPER WIRE DO NOT USE
ALUMINUM WIRE. Allow four feet of slack in the line so dryer can be moved if
servicing isever necessary.
Electrical connection
Thisdryer ismanufactured with the cabinet-ground conductor connected to the NEUTRAL (center) of the wiring
harness at the terminal block If local codes do NOT permit this type of
connection, use "Four wire connection" Instructions
GROUND INSTRUCTIONS: Thisappliance
must be grounded. Jnthe event of malfunction or breakdown, ground will
reduce the risk of electric shock by providing a path of least resistance for
electric current. If using a power supply cord, the plug
must be plugged into an appropriate outlet that is properly installed and grounded in accordance with all local
codes and ordinances, If using a direct wire connection, this
appliance must be connected to a grounded metal, permanent wiring
system; or an equipment-ground conductor must be run with the circuit
conductors and connected to the equipment ground terminal or lead on
the appliance WARNING - Improper connection of the
equipment ground conductor can result in a risk of electric shock Check
with a qualified electrician or serviceman if you are in doubt as to whether the appliance is properly grounded. Do not modify the power supply cord plug, If it will not fit the outlet, have a proper outlet installed by a qualified electrician.
If the house has aluminum wiring, follow
the procedure below: a) Connect a section of 8 gauge solid
copper wire to the connector block.
b) Connect the aluminum wiring to the
added section of copper wire using special connectors designed and
Underwriters Laboratories Listed for
joining copper to aluminum Follow the electrical connector
manufacturer's recommended procedure.
c) Aluminum/copper connection must
conform with local codes and industry accepted wiring practices.
Panel B
IIII
All
Fire Hazard
Use a new UL approved 30 ampere power supply cord.
Use a UL approved strain relief. Disconnect power before making
electrical connections•
Connect neutral wire (white or center
wire) to center terminal (silver). Ground wire (green or bare wire) must
be connected to green ground
connector• Connect remaining 2 supply wires to
remaining 2 terminals (gold). Securely tighten all electrical
connections•
Failure to do so can result in death,
fire, or electrical shock•
center silver- ground wire (green colored terminal with yellow stripes)
block screw and
neuITalwhite wire
power supply cord
ground wire (green)
exTernalground
connector
Figure 5
I. Disconnect the power supply.
2. Remove terminal block cover. 3, rnstall copper, four wire power
supply cord through strain relief.
4. Remove the ground wire (green with yellow stripes) from the external
ground connector and fasten under center, silver-colored
terminal block screw.
5. Connect the ground wire (green) of the copper, tour-wire power supply cord to the external ground
connector.
6. Connect the neutral wire (white) of the power supply cord to the
center, silver-colored terminal screw of the terminal block. Connect the
other wires to the outer terminals. Tighten screws firmly.
7 Tighten strain relief screws. 8 Replace the terminal block cover.
Fire Hazard
Use 10 gauge solid copper wire. Use a UL approved strain relief.
Disconnect power before making electrical connections.
Connect neutral wire (white or center wire) to center terminal (silver).
Ground wire (green or bare wire) must be connected to green ground
connector, Connect remaining 2 supply wires to
remaining 2 terminals (gold). Securely tighten all electrical
connections. Failure to do so can result in death,
fire, or electrical shock.
1. Disconnect the power supply.
2, Remove terminal block cover
3. Strip 5 inches of outer covering from end of cable. Leave bare ground wire at 5 inches. Cut 1 1/2 inches from 3 remaining insulated wires
Strip insulation back 1 inch (see
_a
314" U.L-llstad 3-I strain relief
to dlsconnecr box _IEUTRAL
I 0-gauge, 3-wire wire
wlth ground wlre
(Uomex)
Figure 6).
wlressttl pad
bare ground
Direct wire preparation
u-shaped Shape the end of each hook wire into a "U" shaped
hook (see F@ure 7). The
Figure 6
bare groundwire must
Figure 7 be 4-1/2" long after
forming the hook
4. Install copper, four-wire power
supply cable through strain relief.
5. Remove the ground wire (green with
yellow stripes) from the external ground connector and fasten under
center, silver-colored terminal block screw
6. Slide the hook end of the ground wire (bare) of the tour wire power supply cable under the external ground connector screw. Squeeze hook end of wire together. Tighten
screw,
7. Connect the neutral wire (white) of the power supply cable to the
center, silver colored terminal screw of the terminal block using the same
method. Connect the other wires to the outer terminals. Tighten screws
firmly
8. Tighten strain relief screws.
9. Replace the terminal block cover
BII
Where local codes permit connecting cabinet-ground
conductor to the neutral wire:
Fire Hazard
Use a new UL approved 30 ampere power supply cord.
Use a UL approved strain relief. Disconnect power before making
electrical connections. Connect neutral wire (white or center
wire) to center terminal (silver). Ground wire (green or bare wire) must
be connected to green ground connector.
Connect remaining 2 supply wires to remaining 2 terminals (gold).
Securely tighten all electrical
connections.
Failure to do so can result in death,
fire, or electrtcal shock.
ground wire green oenter sil_er-©olored with yellow stripes) terminal block screw and
neutral white wire
I
"_. external ground connector
Figure 8
I. Disconnect the power supply.
2 Remove terminal block cover 3 Installcopper three-wrro power supply
cord through strain relief
4 Remove the ground wire (green with
yellow stripes) from under center, silver- colored terminal block screw and
connect to external ground connector (see Figure 8).
5 Connect the neutral wire (white or
center) of the power supply cord to the center, silver-colored terminal screw of the terminal block Connect the other
wires to the outer terminals. Tighten screws firmly
6 Tighten strain relief screws 7 Replace the terminal block cover,
Where local codes DO NOT permit
connecting the cabinet-ground conductor to the neutral (white)
wire:
_!ii!i! ermna bockSCrewand withye award a
liiiill r_a a wh ewre pe)
iii_iii
iiii?iiioxtarna_
can s a vsr-co ored ground wire (green
ground sspara a coppe connector, g ound w re
Connect separate copper ground wire from external ground canna€ o to approved ground.
Figure 12
f. Disconnect the power supply.
2 Remove term nab ock cove
In f I I
3 s a IsoId copper, power supply cord or
cable through strain relief
4 Removethegroundwire(greenwith
yellow stripes) from the external ground connecfo
5 Connect the ground wire (green with
yellow stripes) and the neutral (white)
,_] wire of the power supply cord or direct
terminal screw of the terminal block
I wire cable to the center, silver-co oed
C°nnec __ eh_fehe;w_eSsr°eth_ Ufrer12
. .g g ).
Panel C
Where local codes permit connecting cabinet-ground
conductor to the neutral wire of the
)ower supply cable:
Fire Hazard
Use 10 gauge solid copper wire• Use a UL approved strain relief.
Disconnect power before making
electrical connections• Connect neutral wire (white or center
wire) to center terminal (silver), Ground wire (green or bare wire) must
be connected to green ground connector,
Connect remaining 2 supply wires to remaining 2 terminals (gold).
Securely tighten all electrical connections•
Failure to do so can result in death, fire, or electrical shock.
I. Disconnect the power supply.
2. Remove terminal block cover.
3. Strip 3 1/2 inches of outer covering from end of cable. If using three wire cable
with Iwire, cut the bare wire even with
outer covering Strip 1 inch of insulation
from the end of each insulated wire (see
Figure 9).
iiiiiiiiil
Bar_ wire out shod• Wire is not
3/4" U•L.-Ijs_ed direct "Mre cabS, strain relief
box
1O-gauge_ 3-wire or_ 10-gauge, 3-wire with ground "/:,ire(Romaxt
used. Dryer Is grounl_l thrOugh
red
Direct wire preparation
Figure 9
hook wire into a "U" shaped
hook (see Figure 10).
_ u-shaped Shape the end of each
Figure 10
ground wire {green with center sliver-colored yellow stripes) terminal block screw and
n°".":T
Figure 11
4. Install copper, three wire power supply
cable through strain relief.
5. Remove the ground wire (green with
yellow stripes) from under center, silver- colored terminal block screw and
connect to external ground connector (see Figure 11)
6, Slide the hook end of the neutral (white
or center) wire from the three-wire power supply cable under the center,
silver-colored terminal screw of the terminal block. Squeeze the hook end of
the wire together. Tighten screw.
7. Connect the other wires to the
outer terminals using the same method. Tighten screws firmly (see Figure 11)
8.Tighten strain relief screws
9. Replace the terminal block cover.
6 Connect a separate copper ground wire
(No. 10 minimum) from the external J ground screw to an adequate ground
7 Tighten strain relief screws 8 Replace the terminal block cover.
r
ofinsu_on
Exhaust requirements
Fire Hazard
Use a heavy metal vent. Do not use a plastic vent.
Do not use a metal foil vent. Failure to do so can result In death or
fire.
Important: Observe all governing codes
and ordinances.
It is recommended that you exhaust
your dryer to the outside for best
performance. Molsture and lint indoors
may cause:
Lint to gather around the dryer where it can be fue! for a fire.
Moisture damage to woodwork, furniture, paint, wallpaper, carpet,
etc.
Housecleaning problems and health problems.
Ifthe washer/dryer is installed in a confined area such as a bedroom, bathroom or closet, it must be exhausted to the outside and prevision
must be made for enough air for ventilation. Check governing codes and
ordinances Also refer to the "Recessed and closet installation instructions" on
Panel G
Dura Safe TM vent products are recommended and are available from
your qealer. See Panel G. Four-inchdlameler vent b required.
Usea heavy metal vent. Do not use p_sltc or
metal foilvent.
Do Not use non-metal fle_ble vent, or exhaust hoods with magnetic latches.
Do Not exhaust d_/er into o chimney, fu_ace, cold air vent, attic or crawl space, or any other vent used for ven_ng
Do Not installflexible vent in enclosed wall_ ceilings or floors.
I_d _ vent Isreco_n'_ndod to prevent crushing and Nnking,
Flexiblemetal vent must be fully extended and supported when the dryer isinitsfinal
IDO_IlOB.
Remove excess flexi_e vent to avoid sagging and kinldng that may result in
reduced air flow, An exhaust hood should cap the exhaust
vent to prevent rodents and insects from entering the home.
Exhoud out_t hood must be at least 12 inches from the ground or
any object that may be In the loath of the exhaust (such as flower_ rocks or bushe_ etc).
Ifusingan e_,-fing exhausl
_, oloen Nntfrom entire le_31h of systemand make sureexlxtust
haad ISnot_ wtih#nt
Replace any plastic or metal foilvent w_ _gid rr_tal or flexible metal vent.
Useclamps to seal alljoints. Do not use duct
tape, screws or other fastening devices that
extend into the interior of the vent to secure vent.
Service check: Back pressure in any exhaust
system used must not exceed 0.6 inches in
water column measured with an incline
manometer at the point that exhaust vent connects to dryer.
I
Loading...
+ 3 hidden pages