Whirlpool CGD9160GW, CED9160GW, CED9150GW, CGD9150GW Installation Instructions

INSTALLATION INSTRUCTIONS
Commercial Dryer Gas or Electric
INSTRUCTIONS D’INSTALLATION
Sécheuse commerciale (gaz et électrique)
www.whirlpoolcommerciallaundry.com
W11311969A W11311970A—SP
TABLE OF CONTENTS
Page
DRYER SAFETY ....................................................................... 2
INSTALLATION REQUIREMENTS ........................................... 5
Tools and Parts .................................................................... 5
Dimensions/Clearances ...................................................... 6
Venting Requirements ........................................................ 7
Gas Dryer Installation Requirements .................................. 9
Electric Dryer Installation Requirements ........................... 13
INSTALLING LEVELING LEGS, COIN SLIDE,
AND COIN BOX ..................................................................... 16
LEVELING .............................................................................. 17
INSTALLATION INSTRUCTIONS – GAS DRYER .................. 17
Make Gas Connection ...................................................... 17
ELECTRIC DRYER ELECTRICAL CONNECTIONS (FOR
U.S.A. ONLY) .......................................................................... 18
COMPLETE INSTALLATION ................................................. 23
REVERSING DRYER DOOR SWING .................................... 24
MAINTENANCE INSTRUCTIONS ......................................... 26
IF YOU NEED ASSISTANCE ................................................. 26
ELECTRONIC CONTROL SETUP INSTRUCTIONS ........... 27
WARRANTY .......................................................................... 33
TABLE DE MATIÈRES
Page
SÉCURITÉ DE LA SÉCHEUSE ............................................... 34
EXIGENCES D’INSTALLATION ..............................................37
Outils et pièces .................................................................... 37
Dimensions/dégagements ................................................... 38
Exigences concernant l’évacuation ..................................... 39
Exigences d’installation de la sécheuse à gaz ....................41
Exigences d’installation de la sécheuse électrique ............. 45
INSTALLATION DES PIEDS DE NIVELLEMENT, DE LA
GLISSIÈRE ÀMONNAIE ET DE LA CAISSE À MONNAIE .... 48
MISE À NIVEAU ....................................................................... 49
INSTRUCTIONS D’INSTALLATION – SÉCHEUSE À GAZ .....49
Raccordement au gaz .........................................................49
RACCORDEMENTS ÉLECTRIQUES DE LA SÉCHEUSE
ÉLECTRIQUE (É.-U. SEULEMENT) ........................................50
FIN DE L’INSTALLATION ........................................................55
INVERSION DU SENS D’OUVERTURE DE
LA PORTE DE LASÉCHEUSE (OPTIONNEL) .......................56
INSTRUCTIONS D’ENTRETIEN .............................................58
EN CAS DE BESOIN D’ASSISTANCE .................................... 58
INSTRUCTIONS DE CONFIGURATION
DES COMMANDES ÉLECTRONIQUES ................................. 59
GARANTIE ............................................................................... 65
■ It is recommended that the owner post, in a prominent location, instructions for the customer’s use in the event the customer
smells gas. This information should be obtained from your gas supplier.
■ Post the following warning in a prominent location.
2
WARNING:
FIRE OR EXPLOSION HAZARD
Failure to follow safety warnings exactly could result in serious injury, death or property damage.
Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance.
WHAT TO DO IF YOU SMELL GAS:
Do not try to light any appliance.
Do not touch any electrical switch; do not use any phone in your building.
Clear the room, building, or area of all occupants.
Immediately call your gas supplier from a neighbor's phone. Follow the gas supplier's
instructions. If you cannot reach your gas supplier, call the fire department.
Installation and service must be performed by a qualified installer, service agency, or the gas supplier.
3
In the State of Massachusetts, the following installation instructions apply:
Installations and repairs must be performed by a qualified or licensed contractor, plumber, or gas fitter qualified or licensed by
the State of Massachusetts.
Acceptable Shut-off Devices: Gas Cocks and Ball Valves installed for use shall be listed.
A flexible gas connector, when used, must not exceed 4 feet (121.9 cm).
Do not place items exposed to cooking oils in your dryer. Items contaminated with cooking oils may contribute to a chemical reaction that could cause a load to catch re. To reduce the risk of re due to contaminated loads, the nal part of a tumble dryer cycle occurs without heat (cool down period). Avoid stopping a tumble dryer before the end of the drying cycle unless all items are quickly removed and spread out so that the heat is dissipated.
IMPORTANT: The gas installation must conform with local codes, or in the absence of local codes, with the National Fuel Gas Code, ANSI Z223.1/NFPA 54, or the Natural Gas and Propane Installation Code, CSA B149.1.
The dryer must be electrically grounded in accordance with local codes, or in the absence of local codes, with the National Electrical Code, ANSI/NFPA 70, or the Canadian Electrical Code, Part 1, CSA C22.1.
4
INSTALLATION REQUIREMENTS
Tools and Parts
Tools Needed:
8" or 10" Pipe Wrench 8" or 10" Flat-Blade Screwdriver Phillips Screwdriver Adjustable Wrench that opens to 1"
TORX T-20† Security 1" Hex-Head 1⁄4" Socket Wrench Pliers (that open to 19/16") Screwdriver or Bit Socket Wrench
Level Utility Knife 1/4" Nut Driver 27" Wood Block
Caulk Gun and Caulk Vent Clamps Pipe-Joint Compound Putty Knife (for installing new exhaust vent) suitable for gas type
Flashlight (optional) 1" Open-End Wrenches Ruler or Measuring Tape
Parts Supplied:
Foot Boots (4) Leveling Legs (4)
To locate factory specied replacement parts in your area, contact the dealer from whom you purchased your dryer.
TORX and T20 are trademarks of Acument Intellectual Properties, LLC.
5
INSTALLATION REQUIREMENTS
Dimensions/Clearances
Dimensions
Front View Side View Back View
Bottom Exhaust
Clearances
Recessed Front View Closet Side View
6
0"
(0 mm)
INSTALLATION REQUIREMENTS
Venting Requirements
WARNING: To reduce the risk of re, this dryer MUST BE
EXHAUSTED OUTDOORS. IMPORTANT: Observe all governing codes and ordinances.
The dryer exhaust must not be connected into any gas vent,
chimney, wall, ceiling, attic, crawlspace, or a concealed space of a building. Only rigid or exible vent shall be used for exhausting.
Only a 4" (102 mm) heavy, metal exhaust vent and clamps
may be used.
Do not use an exhaust hood with a magnetic latch.
Use clamps to seal all joints. Do not use screws or other
fastening devices that extend into the interior of the duct and catch lint. Do not use duct tape.
Do not use plastic or metal foil vent.
Rigid metal vent:
Recommended for best drying performance and to avoid
crushing and kinking.
Flexible metal vent (acceptable only if accessible to clean):
Must be fully extended and supported in nal dryer location.
Remove excess to avoid sagging and kinking that may result
in reduced airow and poor performance.
Do not install in enclosed walls, ceilings, or oors.
The total length should not exceed 7¾ ft. (2.4 m).
An exhaust hood should cap the vent to prevent rodents and insects from entering the home or business.
Exhaust hood must be at least 12" (305 mm) from the ground or any object that may be in the path of the exhaust (such as owers, rocks, or bushes).
If using an existing vent system, clean lint from the entire length of the system and make sure exhaust hood is not plugged with lint. Replace any plastic or metal foil vent with rigid metal or exible metal vent.
Plan installation to use the fewest number of elbows and turns.
Good
Better
Allow as much room as possible when using elbows or making turns. Bend vent gradually to avoid kinking.
Vent outlet is located at the back of the dryer, at bottom center. The vent can be routed up, down, left, right, behind the dryer,
or straight out the back of the dryer. See “Product Dimensions” in the “Location Requirements” section.
Make-up air:
Although each single-load dryer should have an unobstructed outdoor air opening of 24 in2 (154 cm2) (based on 1 square inch [6.5 cm2] per 1,000 Btu [252 kcal]), common make-up air openings are also acceptable. Set up common openings so that the make-up air is distributed equally to all of the dryers. Keep in mind that the coverage area must be increased by 33% to account for use of registers or louvers over the openings. Also, make-up air openings should not be installed near the location of exhaust vents exiting the building.
Vent System Length
Maximum length of vent system depends upon the type of vent used, number of elbows, and type of exhaust hood. The maximum length for rigid vent is shown in the chart.
Maximum Vent Length
4" (102 mm) Diameter Exhaust Hoods
Box Louvered
2½" (63.5 mm) Angled
Vent System Chart (Rigid Metal Vent)
No. of 90° Box Hood and Turns Louvered Style Angled Hood Style
0 130 ft. (39.6 m) 129 ft. (39.3 m) 1 125 ft. (38.1 m) 119 ft. (36.3 m) 2 115 ft. (35.1 m) 109 ft. (33.2 m) 3 106 ft. (32.3 m) 100 ft. (30.5 m) 4 98 ft. (29.9 m) 92 ft. (28.0 m)
For vent systems not covered by the vent specication chart, see your parts distributor.
Provision must be made for enough air for combustion and ventilation. (Check governing codes and ordinances.) See “Recessed Area and Closet Installation Instructions” in the “Location Requirements” sections.
A 4" (102 mm) outlet hood is preferred. However, a 2½" (64 mm) outlet exhaust hood may be used. A 2½" (64 mm) outlet creates greater back pressure than other hood types. For permanent installation, a stationary vent system is required.
Connect Vent
1. If connecting to existing vent, make sure the vent is clean.
2. Using a 4" (102 mm) clamp, connect vent to exhaust outlet
in dryer.
Vent Collar
NOTE: Do not remove vent collar.
7
INSTALLATION REQUIREMENTS
3. Tighten hose clamp with Phillips screwdriver.
4. Make sure the vent is secured to exhaust hood with
a 4" (102 mm) clamp.
5. Move dryer into nal position. Do not crush or kink vent.
Make sure dryer is level.
NOTE: Testing for proper ventilation should be done with a Manometer. Minimum: 0.01" (0.2 mm). Maximum: 0.6" (16 mm).
For vent systems not covered by the vent specication chart, see your parts distributor.
If dryer is installed in a conned area, such as a bedroom, bathroom, or closet, provision must be made for enough air for combustion and ventilation. (Check governing codes and ordinances.) See “Recessed Area and Closet Installation Instructions” in the “Location Requirements” section.
A 4" (102 mm) outlet hood is preferred. However, a 2½" (64 mm) outlet exhaust hood may be used. A 2½" (64 mm) outlet creates greater back pressure than other hood types. For permanent installation, a stationary vent system is required.
If An Exhaust Hood Cannot Be Used
The outside end of the main vent should have a sweep elbow directed downward.
Multiple Dryer Venting
A main vent can be used for venting a group of dryers. The
main vent should be sized to remove 200 CFM of air per dryer. Large-capacity lint screens of proper design may be used in the main vent if checked and cleaned frequently. The room where the dryers are located should have make-up air equal to or greater than the CFM of all the dryers in the room.
A back-draft damper kit is needed and is available from a
commercial laundry distributor; it should be installed in the vent of each dryer to prevent exhausted air from returning into the dryers and to keep the exhaust in balance within the main vent. Unobstructed return air openings are required.
Each vent should enter the main vent at an angle pointing in the direction of the airow. Vents entering from the opposite side should be staggered to reduce the exhausted air from interfering with the other vents.
The maximum angle of each vent entering the main vent should be no more than 30°.
30˚ max.
Air ow
Air flow
Keep air openings free of dry cleaning uid fumes. Fumes create acids which, when drawn through the dryer heating units, can damage dryers and items being dried.
A clean-out cover should be located on the main vent for periodic cleaning of the vent system.
If the main vent travels vertically through the roof, rather than through the wall, install a 180° sweep elbow on the end of the vent at least 2 ft. (610 mm) above the highest part of the building. The opening in the wall or roof shall have a diameter 1/2" (13 mm) larger than the vent diameter. The vent should be centered in the opening.
Do not install screening or cap over the end of the vent.
8
12" min.
(305 mm)*
24" min.
(610 mm)
* Minimum
clearance above any accumulation of snow, ice, or debris such as leaves
WARNING
(155 cm
(310 cm
INSTALLATION REQUIREMENTS
Gas Dryer Installation Requirements
Location Requirements
Explosion Hazard
Keep flammable materials and vapors, such as gasoline, away from dryer.
Do not install in a garage.
Failure to do so can result in death, explosion, or fire.
IMPORTANT: Do not install or store the dryer where it will be exposed to water and/or the weather. Proper installation is your responsibility.
You will need:
■ A grounded electrical outlet located within 6 ft. (1.8 m) of
where the power cord is attached to the back of the dryer. See “Electrical Requirements.”
■ A level oor with a maximum slope of 1" (25 mm) under
entire dryer. Installing the dryer on soft oor surfaces, such as carpets or surfaces with foam backing, is not recommended.
Gas dryer installation clearances
■ The location must be large enough to allow the dryer door
to be fully opened.
■ Additional spacing should be considered for ease of
installation and servicing. The door opens more than 180°.
■ Additional clearances might be required for wall, door,
and oor moldings.
■ Additional spacing of 1" (25 mm) on all sides of the dryer
is recommended to reduce noise transfer.
When installing a gas dryer: IMPORTANT: Observe all governing codes and ordinances.
■ Check code requirements: Some codes limit or do not
permit installation of clothes dryers in garages, closets, or sleeping quarters. Contact your local building inspector.
■ Make sure that lower edges of the cabinet, plus the back
and bottom sides of the dryer, are free of obstructions to permit adequate clearance of air openings for combustion air. See “Recessed Area and Closet Installation Instructions” below for minimum spacing requirements.
Recessed Area and Closet Installation Instructions
This dryer may be installed in a recessed area or closet. For recessed area and closet installations, minimum clearances can be found on the warning label on the rear of the dryer or in “Dimensions/Clearances.”
The installation spacing is in inches and is the minimum allowable. Additional spacing should be considered for ease of installation, servicing, and compliance with local codes and ordinances.
If closet door is installed, the minimum unobstructed air opening in the top and bottom is required. Louvered doors with equivalent air openings are acceptable.
The dryer must be exhausted outdoors. No other fuel-burning appliance may be installed in the same
closet as the dryer.
2
48 in.
2
Front
Front
View
View
24 in.
)
Closet
Closet
Door
door
2
2
)
3"
(76 mm)
3"
(76 mm)
9
Electrical Requirements - Gas Dryer
IMPORTANT: The dryer must be electrically grounded in
accordance with local codes and ordinances or, in the absence of local codes, with the National Electrical Code, ANSI/NFPA 70, latest edition, or Canadian Electrical Code, CSA C22.1. If codes permit and a separate ground wire is used, it is recommended that a qualied electrical installer determine that the ground path is adequate.
A copy of the above code standards can be obtained from:
National Fire Protection Association
One Batterymarch Park, Quincy, MA 02269
CSA International
8501 East Pleasant Valley Road
Cleveland, Ohio 44131-5575
■ Do not ground to a gas pipe.
■ Do not have a fuse in the neutral or ground circuit.
■ A 120 V, 60 Hz, AC-only, 15 or 20 A, fused electrical circuit
is required. A time-delay fuse or circuit breaker is also recommended. It is recommended that a separate circuit serving only this dryer be provided.
■ This dryer is equipped with a power supply cord having
a 3 prong grounding plug.
■ To minimize the possibility of shock, the cord must be
plugged into a mating, 3 prong, grounding-type outlet, grounded in accordance with local codes and ordinances. If a mating outlet is not available, it is the personal responsibility and obligation of the customer to have the properly grounded outlet installed by a qualied electrician.
■ If codes permit and a separate ground wire is used, it is
recommended that a qualied electrician determine that the ground path is adequate.
■ Check with a qualied electrician if you are not sure
the dryer is properly grounded.
INSTALLATION REQUIREMENTS
Gas Dryer Grounding
GROUNDING INSTRUCTIONS
For a grounded, cord-connected dryer:
This dryer must be grounded. In the event of malfunction or breakdown, grounding will reduce the risk of electric shock by providing a path of least resistance for electric current. This dryer is equipped with a cord having an equipment­grounding conductor and a grounding plug. The plug must be plugged into an appropriate outlet that is properly installed and grounded in accordance with all local codes and ordinances.
WARNING: Improper connection of the equipment-
grounding conductor can result in a risk of electric shock. Check with a qualied electrician or service representative or personnel if you are in doubt as to whether the dryer is properly grounded. Do not modify the plug provided with the dryer: if it will not t the outlet, have a proper outlet installed by a qualied electrician.
SAVE THESE INSTRUCTIONS
10
INSTALLATION REQUIREMENTS
Gas Supply
WARNING
Explosion Hazard Use a new CSA International approved gas supply line. Install a shut-off valve. Securely tighten all gas connections. If connected to propane, have a qualified person make
sure gas pressure does not exceed 13" (33 cm) water column.
Examples of a qualified person include: licensed heating personnel,
authorized gas company personnel, and authorized service personnel.
Failure to do so can result in death, explosion, or fire.
When installed above 10,000 feet (3048 m), a four percent (4%) reduction of the burner B.T.U. rating shown on the model/ serial plate is required for each 1,000 foot (305 m) increase in elevation. For assistance when converting to other gas types and/or installing above 10,000 feet (3048 m) elevation, contact your local service company.
Gas supply pressure required to operate this dryer is a minimum of 5.2" wc (1.30 kPa) and a maximum of
10.5" wc (2.62 kPa).
IMPORTANT: Observe all governing codes and ordinances. This installation must conform with all local codes and
ordinances. In the absence of local codes, installation must conform with American National Standard, National Fuel Gas Code ANSI Z223.1/NFPA 54 or CAN/CSA B149.
A copy of the above code standards can be obtained from:
National Fire Protection Association
One Batterymarch Park, Quincy, MA 02269
CSA International
8501 East Pleasant Valley Road
Cleveland, Ohio 44131-5575
The design of this dryer has been certied by CSA International for use at altitudes up to 10,000 feet (3048 m) above sea level at the B.T.U. rating indicated on the model/serial plate. Burner input adjustments are not required when the dryer is operated up to this elevation.
11
Type of Gas
This dryer is equipped for use with natural gas. It is design­certied by CSA International for propane and butane gases with appropriate conversion. No attempt shall be made to convert dryer from gas specied on serial/rating plate for use with a different gas without consulting the serving gas supplier. Conversion must be done by a qualied service technician.
Gas conversion kit part number is W10402145. This number can also be found on a label on the gas valve burner base.
Gas Supply Line
INSTALLATION REQUIREMENTS
Recommended Method
Provide a gas supply line of 1⁄2" (13 mm) rigid (IPS) pipe to dryer location. Pipe joint compounds that resist action of propane gas must be used. Do not use TEFLON®† tape. With propane gas, piping or tubing size can be 1⁄2" (13 mm) minimum. Usually, propane gas suppliers determine size and materials used in the system.
Gas Supply Pressure Testing
A 1/8" NPT minimum plugged tapping, accessible for gauge testing, must be installed immediately downstream of the installed shut-off valve to the dryer (as shown above). The dryer must be disconnected from the gas supply piping system during any pressure testing of the system at test pressures in excess of 1/2" psig (352 kg/m2). The dryer must be isolated from the gas supply piping system by closing the equipment shut-off valve during any pressure testing of the gas supply piping system at test pressures equal to or less than 1/2" psig (352 kg/m2).
Expected Pressures For Gas Supply
Minimum
Inches of Water Natural Gas 5.2 10.5 Propane Gas 8.0 13.0
Alternate Method
The gas supply may also be connected using 3⁄8" (10 mm) approved copper or aluminum tubing. If the total length of the supply line is more than 20 ft. (6.1 m), larger tubing will be required.
If using natural gas, do not use copper tubing. Pipe joint compounds that resist action of type of gas supplied must be used.
Shut-off valve required
The supply line must be equipped with a manual shut-off valve installed within 6 ft. (1.8 m) of dryer in accordance with National Fuel Gas Code, ANSI Z223.1. This valve should be located in same room as dryer. It should be in a location that allows ease of opening and closing. Do not block access to shut-off valve. In Canada, an individual manual shut-off valve must be installed in accordance with the B149 installation
codes CAN/CGA B149.1 and CAN/CGA B149.2.
Maximum
Inches of Water
12
Flexible Metal Appliance Connector
It is recommended that a new exible stainless steel gas line, design-certied by CSA International, be used for connecting the dryer to the gas supply line. (The gas pipe which extends through the lower rear of the dryer is provided with 3⁄8" male pipe thread.)
NOTE: Do not kink or damage the exible stainless steel gas line when moving the dryer.
Rigid Pipe Connection
The rigid pipe connection requires a combination of pipe ttings to obtain an in-line connection to the dryer.
†®TEFLON is a registered trademark of Chemours.
(155 cm
(310 cm
)
INSTALLATION REQUIREMENTS
Electric Dryer Installation Requirements
Location Requirements
WARNING
Explosion Hazard
Keep flammable materials and vapors, such as gasoline, away from dryer.
Do not install in a garage.
Failure to do so can result in death, explosion, or fire.
The dryer must be exhausted outdoors.
2
48 in.
2
)
Front
Front
View
View
Closet
Closet
Door
door
3"
(76 mm)
IMPORTANT: Do not install or store the dryer where it will be exposed to water and/or the weather. Proper installation is your responsibility.
You will need:
■ A grounded electrical outlet located within 6 ft. (1.8 m) of
where the power cord is attached to the back of the dryer. See “Electrical Requirements.”
■ A level oor with a maximum slope of 1" (25 mm) under
entire dryer. Installing the dryer on soft oor surfaces, such as carpets or surfaces with foam backing, is not recommended.
Electric dryer installation clearances
■ The location must be large enough to allow the dryer door
to be fully opened.
■ Additional spacing should be considered for ease of
installation and servicing. The door opens more than 180°.
■ Additional clearances might be required for wall, door,
and oor moldings.
■ Additional spacing of 1" (25 mm) on all sides of the dryer
is recommended to reduce noise transfer.
Recessed Area and Closet Installation Instructions
This dryer may be installed in a recessed area or closet. For recessed area and closet installations, minimum clearances can be found on the warning label on the rear of the dryer or in “Dimensions/Clearances.”
The installation spacing is in inches and is the minimum allowable. Additional spacing should be considered for ease of installation, servicing, and compliance with local codes and ordinances.
If closet door is installed, the minimum unobstructed air opening in the top and bottom is required. Louvered doors with equivalent air openings are acceptable.
3"
24 in.
2
2
)
(76 mm
Electrical Requirements – U.S.A. only
It is your responsibility:
■ To contact a qualied electrical installer.
■ To be sure that the electrical connection is adequate and in
conformance with the National Electrical Code, ANSI/NFPA 70-latest edition and all local codes and ordinances.
■ The National Electrical Code requires a 4-wire power supply
connection for homes built after 1996, dryer circuits involved in remodeling after 1996, and all mobile home installations.
■ A copy of the above code standards can be obtained from:
National Fire Protection Association, One Batterymarch Park, Quincy, MA 02269.
■ To supply the required 3- or 4-wire, single-phase,
120/240 V, 60 Hz, AC-only electrical supply (or 3- or 4-wire, 120/208 V electrical supply, if specied on the serial/rating plate) on a separate 30 A circuit, fused on both sides of the line. A time delay fuse or circuit breaker is recommended. Connect to an individual branch circuit. Do not have a fuse in the neutral or grounding circuit.
■ Do not use an extension cord.
■ If codes permit and a separate ground wire is used, it is
recommended that a qualied electrician determine that the ground path is adequate.
13
Electrical Requirements – U.S.A. only (cont.)
INSTALLATION REQUIREMENTS
Electrical Connection
To properly install your dryer, you must determine the type of electrical connection you will be using and follow the instructions provided for it here.
■ This dryer is manufactured ready to install with a 3-wire
electrical supply connection. The neutral ground conductor is permanently connected to the neutral conductor (white wire) within the dryer. If the dryer is installed with a 4-wire electrical supply connection, the neutral ground conductor must be removed from the external ground connector (green screw), and secured under the neutral terminal (center or white wire) of the terminal block. When the neutral ground conductor is secured under the neutral terminal (center or white wire) of the terminal block, the dryer cabinet is isolated from the neutral conductor.
■ If local codes do not permit the connection of a neutral
ground wire to the neutral wire, see “Optional 3-wire connection” section.
■ A 4-wire power supply connection must be used when the
appliance is installed in a location where grounding through the neutral conductor is prohibited. Grounding through the neutral is prohibited for (1) new branch-circuit installations and (2) areas where local codes prohibit grounding through the neutral conductor.
Electric Dryer Grounding
Electric Dryer Power Supply Cord
If using a power supply cord:
Use a UL-listed power supply cord kit marked for use with clothes dryers. The kit should contain:
■ A UL-listed 30 A power supply cord, rated 120/240 V
minimum. The cord should be type SRD or SRDT and be at least 4 ft. (1.22 m) long. The wires that connect to the dryer must end in ring terminals or “U”-shaped spade terminals with upturned ends.
■ A UL-listed strain relief.
If your outlet looks like this:
Then choose a 4-wire power supply cord with ring or spade terminals and UL-listed strain relief. The 4-wire power supply cord, at least 4 ft. (1.22 m) long, must have four 10-gauge copper wires and match a 4-wire receptacle of NEMA Type 14-30R.
4-wire
receptacle
(14-30R)
If your outlet looks like this:
3-wire
receptacle
(10-30R)
The ground wire (ground conductor) may be either green or bare. The neutral conductor must be identied by a white cover.
Then choose a 3-wire power supply cord with ring or spade terminals and UL-listed strain relief. The 3-wire power supply cord, at least 4 ft. (1.22 m) long, must have three 10-gauge copper wires and match a 3-wire receptacle of NEMA Type 10-30R.
14
INSTALLATION REQUIREMENTS
Direct Wire
Fire Hazard Use 10 gauge copper wire. Use a UL listed strain relief. Disconnect power before making electrical connections. Connect neutral wire (white or center wire) to center
terminal. Ground wire (green or bare wire) must be connected
to green ground connector. Connect remaining 2 supply wires to remaining
2 terminals (gold). Securely tighten all electrical connections. Failure to do so can result in death, fire, or
electrical shock.
If connecting by direct wire:
Power supply cable must match power supply (4-wire or 3-wire) and be:
■ Flexible armored cable or nonmetallic sheathed copper
cable (with ground wire), covered with exible metallic conduit. All current-carrying wires must be insulated.
■ 10-gauge solid copper wire (do not use aluminum).
■ At least 5 ft. (1.52 m) long.
Electrical Requirements – Canada only
It is your responsibility:
■ To contact a qualied electrical installer.
■ To be sure that the electrical connection is adequate
and in conformance with the Canadian Electrical Code, C22.1 – latest edition and all local codes. A copy of the above codes standard may be obtained from: Canadian Standards Association, 178 Rexdale Blvd., Toronto, ON M9W 1R3 CANADA.
■ To supply the required 4 wire, single phase, 120/240 V,
60 Hz, AC-only electrical supply on a separate 30 A circuit, fused on both sides of the line. A time-delay fuse or circuit breaker is recommended. Connect to an individual branch circuit.
■ This dryer is equipped with a CSA International
Certied Power Cord intended to be plugged into a standard 14-30R wall receptacle. The cord is 5 ft (1.52 m) in length. Be sure wall receptacle is within reach of dryer’s nal location.
receptacle
(14-30R)
4-wire
■ Do not use an extension cord.
If you are using a replacement power supply cord, it is recommended that you use Power Supply Cord Replacement Part Number 8579325. For further information, please reference the service numbers located in the “Assistance or Service” section.
GROUNDING INSTRUCTIONS
For a grounded, cord-connected dryer:
This dryer must be grounded. In the event of malfunction or breakdown, grounding will reduce the risk of electric shock by providing a path of least resistance for electric current. This dryer is equipped with a cord having an equipment­grounding conductor and a grounding plug. The plug must be plugged into an appropriate outlet that is properly installed and grounded in accordance with all local codes and ordinances.
WARNING: Improper connection of the equipment-
grounding conductor can result in a risk of electric shock. Check with a qualied electrician or service representative or personnel if you are in doubt as to whether the dryer is properly grounded. Do not modify the plug provided with the dryer: if it will not t the outlet, have a proper outlet installed by a qualied electrician.
SAVE THESE INSTRUCTIONS
15
INSTALLING LEVELING LEGS, COIN SLIDE, AND COIN BOX
The coin slide mechanism, control panel lock and key, and coin box lock and key are not included and are available from usual industry sources. A special coin slide extension must be used on this model and can be purchased from the coin slide distributor.
1. Prepare dryer for leveling legs NOTE: Slide dryer onto cardboard or hardboard before moving
to avoid damaging oor covering. Using two or more people, move dryer to desired installation
location. Take tape off front corners of dryer. Open dryer and remove
the literature and parts packages. Wipe drum interior with damp cloth to remove any dust.
Take two cardboard corners from the dryer carton and place them on the oor in back of the dryer. Firmly grasp body of the dryer and gently lay it on its back on the cardboard corners.
2. Screw in leveling legs
Examine leveling legs and nd diamond marking. Screw legs into leg holes by hand. Use an adjustable wrench or 1" (25 mm) hex-head socket wrench to nish turning legs until diamond marking is no longer visible. Then t a covered foot boot over each leg foot. For oors with greater slopes, a longer leveling foot (part no. 279810) is available.
To protect the oor, use a large piece of cardboard from the dryer carton. Stand dryer up on the cardboard. Slide the dryer until it is close to its nal location. Leave enough room for electrical connection and to connect the exhaust vent.
On some models: The meter case houses the factory-installed coin slide mechanism, service lock and key, and coin box lock and key.
3. Install coin slide and coin box
Remove the service door of the meter case by lifting it up at the back. Install the money-accepting device. (Refer to manufacturer’s instructions for proper installation.)
Diamond Marking
Foot
Replace the meter case service door. Put the coin vault with lock and key in the meter case opening.
Remove cardboard or hardboard from under dryer. Adjust the legs of the dryer up or down until the dryer is level.
16
LEVELING
Leveling your dryer properly reduces excess noise and vibration. 2. Grip dryer from top and rock back and forth, making sure all
four feet are rmly on oor. Repeat, rocking dryer from side to side. If dryer rocks, adjust leveling feet.
1. Remove cardboard from beneath dryer. Place a level on top
edges of dryer, checking each side and front. If not level, tip dryer and adjust feet up or down, repeating as necessary.
3. If dryer is not level, turn the leveling feet counterclockwise
to lower the dryer or clockwise to raise the dryer. Recheck levelness of dryer and that all four feet are rmly in contact with the oor. Repeat as needed.
HELPFUL TIP: You may want to prop up front of dryer about 4" (102 mm) with a wood block or similar object that will support weight of dryer.
Not Level LEVEL Not Level
INSTALLATION INSTRUCTIONS – GAS DRYER
Make Gas Connection
1. Remove red cap from gas pipe on back of dryer.
WARNING
Explosion Hazard Use a new CSA International approved gas supply line. Install a shut-off valve. Securely tighten all gas connections. If connected to propane, have a qualified person make
sure gas pressure does not exceed 13" (33 cm) water column.
Examples of a qualified person include: licensed heating personnel,
authorized gas company personnel, and authorized service personnel.
Failure to do so can result in death, explosion, or fire.
2. Connect gas supply to dryer. Use a pipe thread compound
approved for the type of gas supplied. If exible metal tubing is used, be certain there are no kinks.
If necessary for service, open the front lower service panel by using a 1/4" nutdriver to remove the 2 hex-head screws from the bottom of the panel. Then lift up on the panel while pulling the bottom of the panel away from the dryer.
3. Open the shut-off valve in the gas supply line and make sure
the dryer has its own gas supply opened.
4. Test all connections by brushing on an approved
noncorrosive leak-detection solution. Bubbles will show a leak. Correct any leaks found.
17
Connection Options
ELECTRIC DRYER ELECTRICAL CONNECTIONS
Power Cord
4-wire receptacle (NEMA Type 14-30R) Go to "Power Supply Cord Connection" section.
3-wire receptacle (NEMA Type 10-30R) Go to "Power Supply Cord Connection" section.
NOTE: If local codes do not permit connection of a cabinet-ground conductor to neutral wire, go to “Connecting 3-Wire
Connection: Optional” section. This connection may be used with either a power supply cord or a direct wire connection.
Direct Wire
4-wire direct Go to "Direct Wire Connection" section.
5"
(127 mm)
3-wire direct Go to "Direct Wire Connection" section.
1"
(25 mm)
Power Supply Cord Connection
Power Supply Cord Strain Relief
WARNING
1. Insert strain relief.
Fire Hazard Use a new UL listed 30 amp power supply cord. Use a UL listed strain relief. Disconnect power before making electrical connections. Connect neutral wire (white or center wire) to center
terminal (silver). Ground wire (green or bare wire) must be connected to
green ground connector. Connect remaining 2 supply wires to remaining
2 terminals (gold). Securely tighten all electrical connections. Failure to do so can result in death, fire, or
electrical shock.
Remove Terminal Block Cover
A B
C
D
Remove the screws from a 3/4" (19 mm) UL listed strain relief Put the tabs of the two clamp sections (C) into the hole below the terminal block opening (B) so that one tab is pointing up (A) and the other is pointing down (D), and hold in place. Tighten strain relief screws just enough to hold the two clamp sections (C) together.
2. Insert power cord into strain relief.
Remove hold-down screw and terminal block cover.
18
Put power supply cord through the strain relief. Be sure that the wire insulation on the power supply cord is inside the strain relief. The strain relief should have a tight t with the dryer cabinet and be in a horizontal position. Do not further tighten strain relief screws at this point.
ELECTRIC DRYER ELECTRICAL CONNECTIONS
Connecting 4-Wire Connection: Power Supply Cord
IMPORTANT: A 4-wire connection is required for mobile
homes and where local codes do not permit the use of 3-wire connections.
Standard Power Supply Cord Connectors
Flanged Spade Connector Ring Connector Connecting Ground and Neutral Wires
1. Remove center terminal block screw (A) and neutral ground wire (B) by removing the external ground conductor screw (C).
B
2. Connect neutral ground wire (B) and neutral wire (white or center wire) (D) of power supply cord under center terminal block screw (A). Tighten screw.
A
C
Connecting Power Cord Ground Wire
3. Connect ground wire (green or bare) (E) of power supply cord under green external ground conductor screw (C). Tighten screw.
E
C
Connecting Remaining Wires
4. Connect remaining wires with outer terminal block screws (F). Tighten screws. Finally, reinstall terminal block cover to dryer rear panel. Secure cover with hold-down screw. Now go to “Venting Requirements.”
F
F
B
D
A
Connecting 3-Wire Connection: Power Supply Cord
Standard Power Cord Connectors
Flanged Spade Connector Ring Connector
Connecting Neutral Wire
1. Loosen or remove center terminal block screw (A).
A
19
ELECTRIC DRYER ELECTRICAL CONNECTIONS
Connecting 3-Wire Connection: Power Supply Cord (cont.)
2. Connect neutral wire (white or center wire) (D) of power supply cord under center terminal block screw (A). Tighten screw.
D
Direct Wire Connection
WARNING
Fire Hazard Use 10 gauge copper wire. Use a UL listed strain relief. Disconnect power before making electrical connections. Connect neutral wire (white or center wire) to center
terminal (silver). Ground wire (green or bare wire) must be connected to
green ground connector. Connect remaining 2 supply wires to remaining
2 terminals (gold). Securely tighten all electrical connections. Failure to do so can result in death, fire, or
electrical shock.
3. Connect remaining wires under outer terminal block screws (F). Tighten screws. Finally, reinstall terminal block cover to dryer rear panel. Secure cover with hold-down screw. Now go to “Venting Requirements.”
A
Direct Wire Strain Relief
1. Insert strain relief.
Unscrew the removable conduit connector (A) and any screws from a 3/4" (19 mm) UL listed strain relief). Put the threaded section of the strain relief (C) through the hole below the terminal block opening (B). Reaching inside the terminal block opening, screw the removable conduit connector (A) onto the strain relief threads.
2. Insert conduit into strain relief and tighten clamp.
F
F
A
B
C
Remove Terminal Block Cover
Remove hold-down screw and terminal block cover.
20
Put direct wire cable through the strain relief. The strain relief should have a tight t with the dryer cabinet and be in a horizontal position. Tighten strain relief screw against the direct wire cable.
Loading...
+ 46 hidden pages