■ It is recommended that the owner post, in a prominent location, instructions for the customer’s use in the event the customer smells
gas. This information should be obtained from your gas supplier.
■ Post the following warning in a prominent location.
2
WARNING: Gas leaks cannot always be detected by smell.
Gas suppliers recommend that you use a gas detector approved by UL or CSA.
For more information, contact your gas supplier.
If a gas leak is detected, follow the “What to do if you smell gas” instructions.
3
INSTALLATION REQUIREMENTS
Tools and Parts
Gather the required tools and parts before starting installation.
Read and follow the instructions provided with any tools
listed here.
Tools needed
■ 8" or 10" Pipe wrench
■ 8" or 10" adjustable
wrench
■ Flat-blade screwdriver
■ Phillips screwdriver
■ Adjustable wrench that
opens to 1" (25 mm) or 1"
(25 mm) hex-head socket
wrench
■ Security T-20 TORX
®†
driver
Parts supplied
Remove parts bag from dryer drum. Check that all parts were
included.
■ Foot boot (4)
■ Dryer foot (4)
■ Level
■ 1/4" socket and wrench
■ Vent clamps
■ Pipe-joint compound
resistant to LP gas
■ Caulk gun and caulk (for
installing new exhaust
vent)
■ Pliers
■ Stiff bladed putty knife
Location Requirements
If installing a gas dryer:
IMPORTANT: Observe all governing codes and ordinances.
■ Check code requirements: Some codes limit or do not permit
installation of clothes dryers in garages, closets, or sleeping
quarters. Contact your local building inspector.
■ Make sure that lower edges of the cabinet, plus the back and
bottom sides of the dryer, are free of obstructions to permit
adequate clearance of air openings for combustion air. See
“Recessed Area and Closet Installation Instructions” below
for minimum spacing requirements.
NOTE: The dryer must not be installed in an area where it will
be exposed to water and/or weather.
† ® TORX is a registered trademark of Saturn Fasteners, Inc.
4
ecessed Area and Closet Installation Instructions
Closet
door
R
This dryer may be installed in a recessed area or closet.
For recessed area and closet installations, minimum clearances
can be found on the warning label on the rear of the dryer.
The installation spacing is in inches and is the minimum
allowable. Additional spacing should be considered for ease
of installation, servicing, and compliance with local codes
and ordinances.
f closet door is installed, the minimum unobstructed air opening
I
in the top and bottom is required. Louvered doors with equivalent
air openings are acceptable.
The dryer must be exhausted outdoors.
No other fuel-burning appliance may be installed in the same
closet as the dryer.
Minimum Installation Clearances
4"
1
(356 mm)
ax.
m
15"
(381 mm)*
0" (0 mm)
Closet
door
2" (51 mm)
0" (0 mm)
1" (25 mm)
Product Dimensions 27" (68.6 cm) dryer
27" (686 mm)
LECTRIC
E
BACK
IEW
57⁄8"
(152 mm)
V
13"
(330 mm)
GAS
1
⁄4"
1
32 mm)
(
29" (736 mm)
271⁄4" (695 mm)
4" (102 mm)
ia.
d
EXHAUST
(159 mm)
(
1
⁄4"
6
1
⁄4"
3
83 mm)
3
8
2
⁄4"
(733 mm)
Recessed front viewCloset side view
*Additional clearances for wall, door, and floor moldings may be required
or if external exhaust elbow is used.
48 in2.
2
)*
(3.10 m
Front
View
2
24 in
(1.55 m2)*
*Opening is the minimum for a closet door.
Louvered doors with equivalent air openings are acceptable.
Closet
door
3" (76 mm)
3" (76 mm)
35"
(889 mm)
(25 mm)
31⁄2"
(89 mm)
SIDE VIEW
LEFT OR
RIGHT SIDE
EXHAUST
1"
1
10
⁄4"
(260 mm)
41⁄4"
(108 mm)
BOTTOM
EXHAUST
131⁄2"
(343 mm)
5
Electrical Requirements – Gas Dryer
GROUNDING INSTRUCTIONS
SAVE THESE INSTRUCTIONS
■
For a grounded, cord-connected dryer:
This dryer must be grounded. In the event of malfunction or
breakdown, grounding will reduce the risk of electric shock
b
y providing a path of least resistance for electric current.
This dryer is equipped with a cord having an equipmentgrounding conductor and a grounding plug. The plug must
be plugged into an appropriate outlet that is properly
installed and grounded in accordance with all local codes
and ordinances.
WARNING:Improper connection of the equipment-
grounding conductor can result in a risk of electric shock.
Check with a qualified electrician or service representative
or personnel if you are in doubt as to whether the dryer is
properly grounded. Do not modify the plug provided with the
dryer: if it will not fit the outlet, have a proper outlet installed
by a qualified electrician.
IMPORTANT: The dryer must be electrically grounded in
accordance with local codes and ordinances or, in the absence of
local codes, with the National Electrical Code, ANSI/NFPA 70,
latest edition, or Canadian Electrical Code, CSA C22.1.
If codes permit and a separate ground wire is used, it is
recommended that a qualified electrical installer determine that
the ground path is adequate.
A copy of the above code standards can be obtained from:
National Fire Protection Association
One Batterymarch Park, Quincy, MA 02269
CSA International
8501 East Pleasant Valley Road
Cleveland, Ohio 44131-5575
■A 120 volt, 60 Hz, AC only, 15- or 20-amp, fused electrical
circuit is required. A time-delay fuse or circuit breaker is also
recommended. It is recommended that a separate circuit
serving only this dryer be provided.
Recommended Ground Method
The dryer, when installed, must be electrically grounded in
accordance with local codes or, in the absence of local codes,
ith the National Electrical Code, ANSI/NFPA 70, latest edition,
w
or Canadian Electrical Code, CSA C22.1, and all local codes
and ordinances.
6
Electrical Requirements – U.S.A. Only
If using a power supply cord:
It is your responsibility
■ To contact a qualified electrical installer.
■ To be sure that the electrical connection is adequate and in
conformance with the National Electrical Code, ANSI/NFPA
70-latest edition and all local codes and ordinances.
The National Electrical Code requires a 4-wire power supply
connection for homes built after 1996 and dryer circuits
involved in remodeling after 1996.
copy of the above code standards can be obtained from:
A
National Fire Protection Association, One Batterymarch Park,
Quincy, MA 02269.
■ To supply the required 3 or 4 wire, single phase, 120/240 volt,
60 Hz., AC only electrical supply (or 3 or 4 wire, 120/208 volt
electrical supply, if specified on the serial/rating plate) on a
separate 30-amp circuit, fused on both sides of the line. A
time-delay fuse or circuit breaker is recommended. Connect
to an individual branch circuit. Do not have a fuse in the
neutral or grounding circuit.
■ Do not use an extension cord.
■ If codes permit and a separate ground wire is used, it is
recommended that a qualified electrician determine that the
ground path is adequate.
Electrical Connection
Use a UL listed power supply cord kit marked for use with
clothes dryers. The kit should contain:
■ A UL listed 30-amp power supply cord, rated 120/240 volt
minimum. The cord should be type SRD or SRDT and be at
least 4 ft (1.22 m) long. The wires that connect to the dryer
must end in ring terminals or “U” shaped spade terminals
with upturned ends.
■ A UL listed strain relief.
If your outlet looks like this:
4-wire receptacle (14-30R)
Then choose a 4-wire power supply cord with ring or spade
terminals and UL listed strain relief. The 4-wire power supply
cord, at least 4 ft (1.22 m) long, must have four 10-gauge copper
wires and match a 4-wire receptacle of NEMA Type 14-30R. The
ground wire (ground conductor) may be either green or bare. The
neutral conductor must be identified by a white cover.
If your outlet looks like this:
To properly install your dryer, you must determine the type of
electrical connection you will be using and follow the instructions
provided for it here.
■ This dryer is manufactured ready to install with a 3-wire
electrical supply connection. The neutral ground conductor is
permanently connected to the neutral conductor (white wire)
within the dryer. If the dryer is installed with a 4-wire electrical
supply connection, the neutral ground conductor must be
removed from the external ground connector (green screw),
and secured under the neutral terminal (center or white wire)
of the terminal block. When the neutral ground conductor is
secured under the neutral terminal (center or white wire) of the
terminal block, the dryer cabinet is isolated from the neutral
conductor.
■ If local codes do not permit the connection of a neutral
ground wire to the neutral wire, see “Optional 3-wire
connection” section.
■ A 4-wire power supply connection must be used when the
appliance is installed in a location where grounding through
the neutral conductor is prohibited. Grounding through the
neutral is prohibited for (1) new branch-circuit installations
and (2) areas where local codes prohibit grounding through
the neutral conductor.
3-wire receptacle (10-30R)
Then choose a 3-wire power supply cord with ring or spade
terminals and UL listed strain relief. The 3-wire power supply
cord, at least 4 ft (1.22 m) long, must have three 10-gauge copper
wires and match a 3-wire receptacle of NEMA Type 10-30R.
7
GROUNDING INSTRUCTIONS
SAVE THESE INSTRUCTIONS
■
For a grounded, cord-connected dryer:
T
his dryer must be grounded. In the event of malfunction or
breakdown, grounding will reduce the risk of electric shock
by providing a path of least resistance for electric current.
This dryer uses a cord having an equipment-grounding
conductor and a grounding plug. The plug must be plugged
into an appropriate outlet that is properly installed and
grounded in accordance with all local codes and ordinances.
■
For a permanently connected dryer:
This dryer must be connected to a grounded metal,
permanent wiring system, or an equipment-grounding
conductor must be run with the circuit conductors and
connected to the equipment-grounding terminal or lead on
the dryer.
WARNING: Improper connection of the equipment-
grounding conductor can result in a risk of electric shock.
Check with a qualified electrician or service representative
or personnel if you are in doubt as to whether the dryer is
properly grounded. Do not modify the plug on the power
supply cord: if it will not fit the outlet, have a proper outlet
installed by a qualified electrician.
If connecting by direct wire:
GROUNDING INSTRUCTIONS
SAVE THESE INSTRUCTIONS
■
For a grounded, cord-connected dryer:
This dryer must be grounded. In the event of malfunction or
breakdown, grounding will reduce the risk of electric shock
by providing a path of least resistance for electric current.
This dryer is equipped with a cord having an equipmentgrounding conductor and a grounding plug. The plug must
be plugged into an appropriate outlet that is properly
installed and grounded in accordance with all local codes
and ordinances.
WARNING:Improper connection of the equipment-
grounding conductor can result in a risk of electric shock.
Check with a qualified electrician or service representative
or personnel if you are in doubt as to whether the dryer is
properly grounded. Do not modify the plug provided with the
dryer: if it will not fit the outlet, have a proper outlet installed
by a qualified electrician.
Power supply cable must match power supply (4-wire or 3-wire)
and be:
■ Flexible armored cable or nonmetallic sheathed copper cable
(with ground wire), protected with flexible metallic conduit. All
current-carrying wires must be insulated.
10-gauge solid copper wire (do not use aluminum).
■
■ At least 5 ft (1.52 m) long.
■ To supply the required 4 wire, single phase, 120/240 volt, 60
Hz., AC only electrical supply on a separate 30-amp circuit,
fused on both sides of the line. A time-delay fuse or circuit
breaker is recommended. Connect to an individual branch
circuit.
■ This dryer is equipped with a CSA International Certified
Power Cord intended to be plugged into a standard 14-30R
wall receptacle. The cord is 5 ft (1.52 m) in length. Be sure
wall receptacle is within reach of dryer’s final location.
4-wire receptacle (14-30R)
■ Do not use an extension cord.
If you are using a replacement power supply cord, it is
recommended that you use Power Supply Cord Replacement
Part Number 8579325. For further information, please
reference the service numbers located in the “Assistance
or Service” section.
Electrical Requirements – Canada Only
It is your responsibility
■ To contact a qualified electrical installer.
■ To be sure that the electrical connection is adequate and in
conformance with the Canadian Electrical Code, C22.1-latest
edition and all local codes. A copy of the above codes
standard may be obtained from: Canadian Standards
Association, 178 Rexdale Blvd., Toronto, ON M9W 1R3
CANADA.
8
D
B
C
A
Gas Supply Requirements
Gas Supply Line
Recommended method
■ Provide a gas supply line of 1/2" (13 mm) rigid (IPS) pipe to
the dryer location. Pipe joint compounds that resist the action
f LP gas must be used. Do not use TEFLON
o
gas. Minimum tubing diameter for LP gas is 1/2" (13 mm).
Usually, LP gas suppliers determine the size and materials
sed in the system.
u
Alternate method
The gas supply may also be connected using 3/8" (10 mm)
■
approved copper or aluminum tubing. If the total length of the
supply line is more than 20 ft. (6.1 m), larger tubing will be
equired. If using natural gas, do not use copper tubing. Pipe
r
joint compounds that resist the action of LP gas must be
used.
Flexible metal appliance connector:
■ It is recommended that a new flexible stainless steel gas line,
design-certified by CSA International, be used for connecting
the dryer to the gas supply line. (The gas pipe which extends
through the lower rear of the dryer is provided with 3/8"
[10 mm] male pipe thread.)
®†
ape with LP
t
IMPORTANT: Observe all governing codes and ordinances.
This installation must conform with all local codes and
ordinances. In the absence of local codes, installation must
conform with American National Standard, National Fuel Gas
Code ANSI Z223.1/NFPA 54 or CAN/CSA B149.
A copy of the above code standards can be obtained from:
National Fire Protection Association
One Batterymarch Park, Quincy, MA 02269
CSA International
8501 East Pleasant Valley Road
Cleveland, Ohio 44131-5575
The design of this dryer has been certified by CSA International
for use at altitudes up to 10,000 feet (3048 m) above sea level at
the B.T.U. rating indicated on the model/serial plate. Burner input
adjustments are not required when the dryer is operated up to
this elevation.
When installed above 10,000 feet (3048 m), a four percent (4%)
reduction of the burner B.T.U. rating shown on the model/serial
plate is required for each 1,000 foot (305 m) increase in elevation.
For assistance when converting to other gas types and/or
installing above 10,000 feet (3048 m) elevation, contact your
local service company.
Type of Gas
This dryer is equipped for use with natural gas. It is designcertified by CSA International for LP (propane and butane) gases
with appropriate conversion. No attempt shall be made to convert
the dryer from the gas specified on the serial/rating plate for use
with a different gas without consulting the serving gas supplier.
Conversion must be done by a qualified service technician.
Gas conversion kit part numbers are listed on the gas valve
burner base.
■ Do not kink or damage the flexible stainless steel gas line
when moving the dryer.
Rigid pipe connection:
The rigid pipe connection requires a combination of pipe fittings
to obtain an in-line connection to the dryer.
■ Must include a shutoff valve:
The supply line must be equipped with a manual shutoff
valve installed within 6 ft. (1.8 m) of dryer in accordance
with National Fuel Gas Code, ANSI Z223.1. In Canada,
an individual manual shutoff valve must be installed in
accordance with the B149 installation codes CAN/CGA
B149.1 and CAN/CGA B149.2. This valve should be located
in the same room as the dryer. It should be in a location that
allows ease of opening and closing. Do not block access to
shutoff valve. The valve is for turning on or shutting off gas
to the dryer.
A. Gas supply line
B. Shut-off valve “open” position
C. To Dryer
D. NPT 1/8" fitting
†®TEFLON is a registered trademark of E.I. Du Pont De Nemours and Company.
9
■ Installed in a confined area:
If the dryer is installed in a confined area such as a
bathroom or closet, provision must be made for enough
ir for combustion and ventilation. Check governing
a
codes and ordinances or refer to the “Recessed Area
and Closet Installation Instructions” in the Location
equirements section.
R
Gas Supply Pressure Testing
Exhaust hood must be at least 12" (305 mm) from the ground
or any object that may be in the path of the exhaust (such as
flowers, rocks, or bushes).
If using an existing vent system, clean lint from the entire length
of the system and make sure exhaust hood is not plugged with
lint. Replace any plastic or metal foil vent with rigid metal or
flexible metal vent.
lan installation to use the fewest number of elbows and turns.
P
A 1/8" NPT minimum plugged tapping, accessible for test gauge
onnection, must be installed immediately upstream of the gas
c
supply connection to the dryer.
The dryer must be disconnected from the gas supply piping
system during any pressure testing of the system at test
pressures in excess of 1/2 psi (3.5 kPa).
Venting Requirements
WARNING: To reduce the risk of fire, this dryer MUST BE
EXHAUSTED OUTDOORS.
■ The dryer exhaust must not be connected into any gas vent,
chimney, wall, ceiling, attic, crawlspace, or a concealed space
of a building.
■ Only rigid or flexible metal duct shall be used for exhausting.
■ Do not use an exhaust hood with a magnetic latch.
■ Do not install flexible metal vent in enclosed walls, ceilings,
or floors.
■ 4" (102 mm) heavy metal vent and clamps must be used.
Do not use plastic or metal foil vent.
■ Use clamps to seal all joints. Do not use duct tape, screws,
or other fastening devices that extend into the interior of the
vent. Items sticking through the vent can catch lint.
■ If only flexible metal vent is used, the back pressure should
not exceed 1" (25 mm) water column at the rear of the dryer.
3
■ The total length of flexible vent must not exceed 7
IMPORTANT: Observe all governing codes and ordinances.
Rigid metal vent is recommended to avoid crushing and kinking.
Flexible metal vent must be fully extended and supported when
the dryer is in its final position. Remove excess flexible metal vent
to avoid sagging and kinking that will result in reduced airflow and
poor performance.
An exhaust hood should cap the vent to keep rodents and insects
from entering the home or business.
⁄4 ft (2.4 m).
A
Exhaust Air Flow
A. Good
B. Better
B
Allow as much room as possible when using elbows or making
turns. Bend vent gradually to avoid kinking.
Vent outlet is located at the back of the dryer, at bottom center.
The vent can be routed up, down, left, right, behind the dryer,
or straight out the back of the dryer. See “Product Dimensions.”
Vent System Length
Maximum length of vent system depends upon the type of
vent used, number of elbows, and type of exhaust hood.
The maximum length for rigid vent is shown in the chart.
Maximum Vent Length
4" (102 mm) Diameter Exhaust Hoods
BoxLouvered
Rigid Metal Vent
No. of 90° turns
0
1
2
3
4
Box Hood and Louvered StyleAngled Hood Style
130 ft. (39.6 m)
125 ft. (38.1 m)
115 ft. (35.1 m)
106 ft. (32.3 m)
98 ft. (29.9 m)
For vent systems not covered by the vent specification chart,
see your parts distributor.
If dryer is installed in a confined area, such as a bedroom,
bathroom, or closet, provision must be made for enough air
for combustion and ventilation. (Check governing codes and
ordinances.) See “Recessed Area and Closet Installation
Instructions” in the Location Requirements section.
A 4" (102 mm) outlet hood is preferred. However, a 2
outlet exhaust hood may be used. A 2
greater back pressure than other hood types. For permanent
installation, a stationary vent system is required.
21⁄2" (63.5 mm) Angled
129 ft. (39.3 m)
119 ft. (36.3 m)
109 ft. (33.2 m)
100 ft. (30.5 m)
92 ft. (28.0 m)
1
1
⁄2" (64 mm) outlet creates
⁄2" (64 mm)
10
Multiple Dryer Venting
3
0˚ max.
air ow
12"min.
(305mm)
24"min.
(610mm)
■ A main vent can be used for venting a group of dryers. The
main vent should be sized to remove 200 CFM of air per
dryer. Large-capacity lint screens of proper design may be
used in the main vent if checked and cleaned frequently. The
room where the dryers are located should have make-up air
equal to or greater than the CFM of all the dryers in the room.
■ A back-draft damper kit is needed and is available from a
commercial laundry distributor; it should be installed in the
vent of each dryer to keep exhausted air from returning into
the dryers and to keep the exhaust in balance within the main
vent. Unobstructed return air openings are required.
Each vent should enter the main vent at an angle pointing in the
direction of the airflow. Vents entering from the opposite side
should be staggered to reduce the exhausted air from interfering
with the other vents.
The maximum angle of each vent entering the main vent should
be no more than 30°.
A
B
Keep air openings free of dry cleaning fluid fumes. Fumes create
acids which, when drawn through the dryer heating units, can
damage dryers and items being dried.
A clean-out cover should be located on the main vent for periodic
cleaning of the vent system
If an exhaust hood cannot be used:
B
D
C
A. Exhaust hood or elbow
B. Wall
C. Main collector vent
D. Horizontal vent
E. 180° sweep elbow
F. Vertical vent
G. Roof
2 ft. (610 mm)
min. above
highest point
of building
A
in. 12"(305 mm) clearance
M
above any accumulation
of snow, ice, or debris such
as leaves.
E
F
C
G
A. Individual dryer vent
B. Main vent
INSTALLATION INSTRUCTIONS – COIN SLIDE AND COIN BOX
Install Coin Slide and Coin Box
The coin slide mechanism, control panel lock and key, and coin
box lock and key are not included and are available from usual
industry sources. A special coin slide extension must be used on
this model and can be purchased from the coin slide distributor.
NOTE: Slide dryer onto cardboard or hardboard before moving to
avoid damaging floor covering.
1. Using two or more people, move dryer to desired installation
location.
2. Take tape off front corners of dryer. Open dryer and remove
the literature and parts packages. Wipe the interior of the
drum thoroughly with a damp cloth.
The outside end of the main vent should have a sweep elbow
directed downward. If the main vent travels vertically through the
roof, rather than through the wall, install a 180° sweep elbow on
the end of the vent at least 2 ft. (610 mm) above the highest part
of the building. The opening in the wall or roof shall have a
diameter 1/2" (13 mm) larger than the vent diameter. The vent
should be centered in the opening.
Do not install screening or cap over the end of the vent.
3. Take two of the cardboard corners from the carton and place
them on the floor in back of the dryer. Firmly grasp the body
of the dryer and gently lay it on its back on the cardboard
corners.
4. With one of the legs in hand, check the ridges for a diamond
marking. That's how far the leg is supposed to go into the
hole.
5. Start to screw the leveling legs into the holes by hand.
(Use a small amount of liquid detergent to lubricate the
screw threads so it is easier to turn the legs.) Use a 1"
(25 mm) wrench or socket wrench to finish turning the legs
until you reach the diamond mark.
Now stand the dryer up.
6. Remove the service
door of the meter case
by lifting it up at the
back. Install the moneyaccepting device. (Refer
to manufacturer's
instructions for proper
installation.)
7. Replace the meter case
service door. Put the coin vault with lock and key in the meter
case opening.
8. Remove cardboard or hardboard from under dryer. Adjust the
legs of the dryer up or down until the dryer is level.
11
INSTALLATION INSTRUCTIONS – GAS DRYER
Make Gas Connection
1. Remove red cap from gas pipe on back of dryer.
2. Connect gas supply to dryer. Use a pipe thread compound
approved for the type of gas supplied. If flexible metal tubing
is used, be certain there are no kinks.
If necessary for service, open the front lower service panel by
using a 1/4" nutdriver to remove the 2 hex-head screws from
the bottom of the panel. Then lift up on the panel while pulling
the bottom of the panel away from the dryer.
3. Open the shutoff valve in the gas supply line and make sure
the dryer has its own gas supply opened.
4. Test all connections by brushing on an approved noncorrosive
leak-detection solution. Bubbles will show a leak. Correct any
leak found.
Connect Vent
1. Using a 4" (102 mm) clamp, connect vent to exhaust outlet
on the dryer. If connecting to existing vent, make sure the vent
is clean. The dryer vent must fit over the dryer exhaust outlet
and inside the exhaust hood. Make sure the vent is secured
to exhaust hood with a 4" (102 mm) clamp.
2. Using two or more people, move dryer to desired installation
location. Do not crush or kink vent, and remove any excess
flexible vent to improve airflow. Make sure dryer is level.
3. Check that there are no kinks in the flexible gas line.
Complete Installation
1. With dryer in final position, place level on top of the dryer, first
side to side; then front to back. If the dryer is not level, adjust
the legs of the dryer up or down until the dryer is level.
2. Plug into a grounded 3 prong outlet.
3. Check dryer operation: Close dryer door. Insert coins in slide
and press slide in slowly. Select the Whites and Colors cycle
and let the dryer run for at least five minutes.
NOTE: Dryer door must be closed for dryer to operate.
4. Open the dryer door. Check that the inside of the dryer is
warm. If the burner does not ignite and there is no heat inside
the dryer, wait for five minutes. Check that all gas supply
valves are in the “ON” position and that the electrical cord
is plugged in. Repeat five-minute test.
5. If drying time is too long, make sure that the lint screen is
clean and that there are no obstructions to airflow in the dryer
vent system.
6. Restart the dryer and allow it to complete a full cycle to make
sure it is working properly.
12
INSTALLATION INSTRUCTIONS – ELECTRIC DRYER
ower Supply Cord
P
. Disconnect power.
1
2. Remove the hold-down screw and terminal block cover.
D
C
B
A
A. Neutral ground wire
B. External ground conductor screw
C. Center terminal block screw
D. Terminal block cover and holddown screw
3. Install strain relief.
Electrical Connection Options
If your location has:And you will beGo to Section
connecting to:
4-wire receptacleA UL listed, 120/240-4-wire connection:
(NEMA Type 14-30R)volt minimum,Power supply cord
30-amp, dryer power
supply cord*
3-wire receptacleA UL listed, 120/240-3-wire connection:
(NEMA type 10-30R)volt minimum,Power supply cord
*If local codes do not permit the connection of a cabinet-ground conductor to the neutral wire, go to “Optional 3-wire connection”
section.
13
Power supply cord strain relief:
■ Remove the screws from a 3/4" (19 mm)
UL listed strain relief (UL marking on strain
relief). Put the tabs of the two clamp
ections into the hole below the terminal
s
block opening so that one tab is pointing
up and the other is pointing down, and
hold in place.
Tighten strain relief screws enough to hold the
two clamp sections together.
■ Put power supply cord through the strain
elief. Be sure that the wire insulation on
r
the power supply cord is inside the strain
relief. The strain relief should have a tight
it with the dryer cabinet and be in a
f
horizontal position. Do not further tighten
strain relief screws at this point.
A
B
C
D
A. Strain relief tab
pointing up
B. Hole below terminal
block opening
C. Clamp section
D. Strain relief tab
pointing down
5. Now complete installation following
instructions for your type of electrical
connection:
4-wire (recommended)
3-wire (if 4-wire is not available)
14
Power supply cord,
-wire connection:
4
MPORTANT: A 4-wire connection is
I
required where local codes do not permit
the use of 3-wire connections.
3. Connect ground wire (green or bare) of
power supply cord to external ground
conductor screw. Tighten screw.
A
D
B
A
C
D
A. 4-wire receptacle (NEMA type 14-30R)
B. 4-prong plug
C. Ground prong
D. Neutral prong
E. Spade terminals with upturned ends
F. 3/4"(19 mm) UL listed strain relief
G. Ring terminals
1. Remove center terminal block screw.
2. Remove neutral ground wire from
external ground conductor screw.
Connect neutral ground wire and the
neutral wire (white or center wire) of
power supply cord under center
terminal block screw. Tighten screw.
F
B
C
E
G
A. External ground conductor screw
B. Ground wire (green or bare) of power supply cord
C. 3/4
"
(19 mm) UL listed strain relief
D. Center terminal block screw
E. Neutral ground wire
F. Neutral wire (white or center wire)
E
F
4. Connect the other wires to
outer terminal block screws.
Tighten screws.
A
B
A. External ground conductor screw – Dotted line shows position of
NEUTRAL ground wire before being moved to center terminal block screw.
B. Center terminal block screw
C. Neutral ground wire
D. Neutral wire (white or center wire)
"
(19 mm) UL listed strain relief
E. 3/4
C
5. Tighten strain relief screws.
6. Insert tab of terminal block cover into
slot of dryer rear panel. Secure cover
with holddown screw.
7. You have completed your electrical
D
E
connection. Now go to “Venting
Requirements.”
15
Power supply cord,
-wire connection:
3
B
A
C
A. 3-wire receptacle (NEMA type 10-30R)
B. 3-wire plug
C. Neutral prong
D. Spade terminals with upturned ends
E. 3/4" (19 mm) UL listed strain relief
F. Ring terminals
G. Neutral (white or center wire)
Use where local codes permit connecting
cabinet-ground conductor to neutral wire.
1. Loosen or remove center terminal block
D
E
screw.
2. Connect neutral wire (white or center
ire) of power supply cord to the center
w
terminal screw of the terminal block.
Tighten screw.
3. Connect the other wires to outer terminal
G
F
block screws. Tighten screws.
C
A
4. Tighten strain relief screws.
5. Insert tab of terminal block cover into
slot of dryer rear panel. Secure cover
D
B
E
A. External ground conductor screw
B. Neutral ground wire
C. Center terminal block screw
D. Neutral wire (white or center wire)
E. 3/4" (19 mm) UL listed strain relief
with holddown screw.
6. You have completed your electrical
connection. Now go to “Venting
Requirements.”
16
Loading...
+ 36 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.