Whirlpool CED9150GW0 Installation Guide

INSTALLATION INSTRUCTIONS
Commercial Dryer Gas or Electric
INSTRUCTIONS D’INSTALLATION
Sécheuse à usage commercial
à gaz ou électrique
W10919522B W10919523B—SP
www.whirlpoolcommerciallaundry.com
TABLE OF CONTENTS
Page
DRYER SAFETY ....................................................................... 2
INSTALLATION REQUIREMENTS ........................................... 5
Tools and Parts .................................................................... 5
Dimensions/Clearances ...................................................... 6
Venting Requirements ........................................................ 7
Gas Dryer Installation Requirements ................................ 10
Electric Dryer Installation Requirements ........................... 14
INSTALLING LEVELING LEGS, COIN SLIDE,
AND COIN BOX ..................................................................... 17
INSTALLATION INSTRUCTIONS – GAS DRYER .................. 18
Make Gas Connection ...................................................... 18
INSTALLATION INSTRUCTIONS – ELECTRIC DRYER ....... 19
Electric Dryer Electrical Connections ............................... 19
LEVELING .............................................................................. 24
COMPLETE INSTALLATION ................................................. 24
REVERSING DRYER DOOR SWING .................................... 25
MAINTENANCE INSTRUCTIONS ......................................... 27
IF YOU NEED ASSISTANCE ................................................. 27
ELECTRONIC CONTROL SETUP INSTRUCTIONS ........... 28
WARRANTY .......................................................................... 34
TABLE DES MATIÈRES
Page
SÉCURITÉ DE LA SÉCHEUSE .............................................. 35
EXIGENCES D’INSTALLATION ............................................. 38
Outils et pièces .................................................................. 38
Dimensions/Distances de dégagement ............................. 39
Exigences concernant l’évacuation ................................... 40
Exigences d’installation pour la sécheuse à gaz ................ 43
Exigences d’installation pour la sécheuse électrique ........ 47
INSTALLATION DES PIEDS DE NIVELLEMENT, DE LA GLISSIÈRE À MONNAIE ET DE LA CAISSE
À MONNAIE ........................................................................... 49
INSTRUCTIONS D’INSTALLATION
POUR LA SÉCHEUSE À GAZ ................................................ 50
Raccordement à la canalisation de gaz ............................. 50
NIVELLEMENT .......................................................................51
ACHEVER L’INSTALLATION ................................................. 52
INVERSION DU SENS D’OUVERTURE
DE LA PORTE DE LA SÉCHEUSE ........................................53
INSTRUCTIONS D’ENTRETIEN ............................................55
SI VOUS AVEZ BESOIN D’ASSISTANCE ..............................55
INSTRUCTIONS DE RÉGLAGE DU TABLEAU
DE COMMANDE ÉLECTRONIQUE ...................................... 56
GARANTIE ............................................................................. 63
DRYER SAFETY
■ It is recommended that the owner post, in a prominent location, instructions for the customer’s use in the event the customer
smells gas. This information should be obtained from your gas supplier.
■ Post the following warning in a prominent location.
DRYER SAFETY
WARNING:
FIRE OR EXPLOSION HAZARD Failure to follow safety warnings exactly could result in serious injury, death, or property
damage.
Do not store or use gasoline or other ammable vapors and liquids in the vicinity of this or any other appliance.
WHAT TO DO IF YOU SMELL GAS:
Do not try to light any appliance.
Do not touch any electrical switch; do not use any phone in your building.
Clear the room, building, or area of all occupants.
Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s
instructions. If you cannot reach your gas supplier, call the re department.
Installation and service must be performed by a qualied installer, service agency, or the gas supplier.
DRYER SAFETY
IMPORTANT: The gas installation must conform with local codes, or in the absence of local codes, with the National Fuel Gas Code, ANSI Z223.1/NFPA 54, or the Natural Gas and Propane Installation Code, CSA B149.1.
The dryer must be electrically grounded in accordance with local codes, or in the absence of local codes, with the National Electrical Code, ANSI/NFPA 70, or the Canadian Electrical Code, Part 1, CSA C22.1.
INSTALLATION REQUIREMENTS
Tools and Parts
Tools Needed:
8" (200 mm) 8" (200 mm) or 10" (250 mm) Flat-Blade Screwdriver Phillips Screwdriver or 10" (250 mm) Adjustable Wrench Pipe Wrench that opens to 1" (25 mm)
TORX® T-20®† Security 1" (25 mm) Hex-Head 1⁄4" Socket Wrench Pliers (that open to Screwdriver or Bit Socket Wrench 19/16" [39 mm])
Level Utility Knife 1/4" (6 mm) Nut Driver 27" (686 mm) Wood Block
Caulk Gun and Caulk Vent Clamps Pipe-Joint Compound Putty Knife (for installing new exhaust vent) suitable for gas type
Flashlight (optional) 1" (25 mm) Ruler or Measuring Tape Open-End Wrenches
Parts Supplied:
Foot Boots (4) Leveling Legs (4)
To locate factory specied replacement parts in your area, contact the dealer from whom you purchased your dryer.
†®TORX and T20 are registered trademarks of Acument Intellectual Properties, LLC.
INSTALLATION REQUIREMENTS
Dimensions/Clearances
Dimensions
Front View Side View Back View
Bottom Exhaust
Clearances
Recessed Front View Closet Side View
0"
(0 mm)
INSTALLATION REQUIREMENTS
Venting Requirements
WARNING: To reduce the risk of re, this dryer MUST BE
EXHAUSTED OUTDOORS. IMPORTANT: Observe all governing codes and ordinances.
Dryer exhaust must not be connected into any gas vent, chimney, wall, ceiling, attic, crawlspace, or a concealed space of a building. Only rigid or exible metal vent shall be used for exhausting.
4"
(102 mm)
4" (102 mm) heavy, metal exhaust vent
Elbows:
■ 45° elbows provide better airow than 90° elbows.
Good
Better
Clamps:
■ Use clamps to seal all joints.
■ Exhaust vent must not be connected or secured with screws
or other fastening devices that extend into interior of duct and catch lint. Do not use duct tape.
Improper venting can cause moisture and lint to collect indoors, which may result in:
Moisture damage to woodwork, furniture, paint, wallpaper, carpets, etc.
Housecleaning problems and health problems.
■ Only a 4" (102 mm) heavy, metal exhaust vent and clamps
may be used.
■ Do not use plastic or metal foil vent.
Rigid metal vent:
■ Recommended for best drying performance and to avoid
crushing and kinking.
Flexible metal vent: (Acceptable only if accessible to clean)
■ Must be fully extended and supported in nal dryer location.
■ Remove excess to avoid sagging and kinking that may result
in reduced airow and poor performance.
■ Do not install in enclosed walls, ceilings, or oors.
■ The total length should not exceed 7
3
⁄4 ft. (2.4 m).
NOTE: If using an existing vent system, clean lint from entire length of the system and make sure exhaust hood is not plugged with lint. Replace plastic or metal foil vents with rigid metal or exible metal vents. Review “Vent System Chart” and if necessary, modify existing vent system to achieve best drying performance.
NOTE: Although each single-load dryer should typically have an unobstructed outdoor air opening of 24" (154 cm) (based on 1" [6.5 cm] per 1,000 Btu [252 kcal]), common make-up air openings are also acceptable.
Set up common openings so the make-up air is distributed equally to all dryers. Coverage area must be increased by 33% to account for the use of registers or louvers.
Make-up air openings should not be installed near the building exits for exhaust vents.
INSTALLATION REQUIREMENTS
Vent Hoods
4" (102 mm) Diameter Exhaust Hoods
Box Hood Louvered Hood Angled Hood
Vent System Length
Maximum Vent Length/Vent Connection
Maximum length of vent system depends upon the type of vent used, number of elbows, and type of exhaust hood.
Vent System Chart (Rigid Metal Vent)
No. of
90˚ Turns
0 64 ft. (19.5 m) 58 ft. (17.7 m) 1 54 ft. (16.5 m) 48 ft. (14.6 m) 2 44 ft. (13.4 m) 38 ft. (11.6 m) 3 35 ft. (10.7 m) 29 ft. (8.8 m) 4 27 ft. (8.2 m) 21 ft. (6.4 m)
For vent systems not covered by the vent specication chart, see your parts distributor.
Provision must be made for enough air for combustion and ventilation. (Check governing codes and ordinances.) See “Recessed Area and Closet Installation Instructions” in the “Location Requirements” sections.
A 4" (102 mm) outlet hood is preferred. However, a 21⁄2" (64 mm) outlet exhaust hood may be used. A 21⁄2" (64 mm) outlet creates greater back pressure than other hood types. For permanent installation, a stationary vent system is required.
Connect Vent
1. If connecting to existing vent, make sure the vent is clean.
2. Using a 4" (102 mm) clamp, connect vent to exhaust outlet
in dryer.
Box and
Louvered Hood
Angled Hood
Vent collar
Exhaust hood must be at least 12" (305 mm) from the ground or any object that may be in the path of the exhaust (such as owers, rocks, bushes, or snow).
12" min.
(305 mm)
3. Tighten hose clamp with Phillips screwdriver.
4. Make sure the vent is secured to exhaust hood with
a 4" (102 mm) clamp.
5. Move dryer into nal position. Do not crush or kink vent.
Make sure dryer is level.
NOTE: Do not remove vent collar.
INSTALLATION REQUIREMENTS
If an Exhaust Hood Cannot be Used Multiple Dryer Venting
The outside end of main vent should have a sweep elbow directed downward.
24" min.
12" min.
(305 mm)*
* Minimum clearance above
any accumulation of snow, ice, or debris such as leaves
(610 mm)
If main vent travels vertically through the roof, rather than through wall, install a 180° sweep elbow on end of vent at least 2 ft. (610 mm) above surface of roof.
The opening in wall or roof shall have a diameter 1/2" (13 mm) larger than vent diameter. Vent should be centered in opening.
Do not install screening over end of vent for best performance.
A main vent can be used for venting a group of dryers. The main vent should be sized to remove 5663 l/min. (200 CFM) of air per dryer. Large-capacity lint screens of proper design may be used in main vent if checked and cleaned frequently. The room where the dryers are located should have make-up air equal to or greater than CFM of all the dryers in the room.
Back-draft Damper Kit is available from your distributor and should be installed in the vent of each dryer to keep exhausted air from returning into dryers and to keep exhaust in balance within main vent. Unobstructed return air openings are required.
Each vent should enter the main vent at an angle pointing in the direction of the airow. Vents entering from the opposite side should be staggered to reduce the exhausted air from interfering with the other vents.
30˚ max.
Airflow
Air ow
The maximum angle of each vent entering the main vent should be no more than 30°.
Keep air openings free of dry cleaning uid fumes. Fumes create acids which, when drawn through the dryer heating units, can damage dryers and items being dried.
A clean-out cover should be located on the main vent for periodic cleaning of the vent system.
INSTALLATION REQUIREMENTS
(155 cm
Gas Dryer Installation Requirements
Location Requirements
Your dryer can be installed in a basement, laundry room, or recessed area.
This dryer is not intended for installation in a mobile home. Companion appliance location requirements should also be
considered. IMPORTANT: Do not install or store the dryer where it will be
exposed to water and/or the weather. Proper installation is your responsibility.
You will need:
■ A grounded electrical outlet located within 6 ft. (1.8 m) of
where the power cord is attached to the back of the dryer. See “Electrical Requirements.”
■ A level oor with a maximum slope of 1" (25 mm) under
entire dryer. Installing the dryer on soft oor surfaces, such as carpets or surfaces with foam backing, is not recommended.
Gas dryer installation clearances
■ The location must be large enough to allow the dryer door
to be fully opened.
■ Additional spacing should be considered for ease of
installation and servicing. The door opens more than 180°.
■ Additional clearances might be required for wall, door,
and oor moldings.
■ Additional spacing of 1" (25 mm) on all sides of the dryer
is recommended to reduce noise transfer.
When installing a gas dryer: IMPORTANT: Observe all governing codes and ordinances.
■ Check code requirements: Some codes limit or do not
permit installation of clothes dryers in garages, closets, or sleeping quarters. Contact your local building inspector.
■ Make sure that lower edges of the cabinet, plus the back
and bottom sides of the dryer, are free of obstructions to permit adequate clearance of air openings for combustion air. See “Recessed Area and Closet Installation Instructions” below for minimum spacing requirements.
Recessed Area and Closet Installation Instructions
This dryer may be installed in a recessed area or closet. For recessed area and closet installations, minimum clearances can be found on the warning label on the rear of the dryer or in “Dimensions/Clearances.”
The installation spacing is in inches and is the minimum allowable. Additional spacing should be considered for ease of installation, servicing, and compliance with local codes and ordinances.
If closet door is installed, the minimum unobstructed air opening in the top and bottom is required. Louvered doors with equivalent air openings are acceptable.
The dryer must be exhausted outdoors. No other fuel-burning appliance may be installed in the same
closet as the dryer.
2
48 in.
(310 cm2)
Front
Front
View
View
2
24 in.
2
Closet
Closet
Door
door
)
3"
(76 mm)
3"
(76 mm)
10
Electrical Requirements
IMPORTANT: The dryer must be electrically grounded in
accordance with local codes and ordinances or, in the absence of local codes, with the National Electrical Code, ANSI/NFPA 70, latest edition, or Canadian Electrical Code, CSA C22.1. If codes permit and a separate ground wire is used, it is recommended that a qualied electrical installer determine that the ground path is adequate.
A copy of the above code standards can be obtained from:
National Fire Protection Association
One Batterymarch Park, Quincy, MA 02269
CSA International
8501 East Pleasant Valley Road
Cleveland, Ohio 44131-5575
■ Do not ground to a gas pipe.
■ Do not have a fuse in the neutral or ground circuit.
■ A 120-volt, 60 Hz, AC-only, 15- or 20-amp, fused electrical
circuit is required. A time-delay fuse or circuit breaker is also recommended. It is recommended that a separate circuit serving only this dryer be provided.
■ This dryer is equipped with a power supply cord having
a 3 prong grounding plug.
■ To minimize the possibility of shock, the cord must be
plugged into a mating, 3 prong, grounding-type outlet, grounded in accordance with local codes and ordinances. If a mating outlet is not available, it is the personal responsibility and obligation of the customer to have the properly grounded outlet installed by a qualied electrician.
■ If codes permit and a separate ground wire is used, it is
recommended that a qualied electrician determine that the ground path is adequate.
■ Check with a qualied electrician if you are not sure
the dryer is properly grounded.
INSTALLATION REQUIREMENTS
Gas Dryer Grounding
GROUNDING INSTRUCTIONS
For a grounded, cord-connected dryer:
This dryer must be grounded. In the event of malfunction or breakdown, grounding will reduce the risk of electric shock by providing a path of least resistance for electric current. This dryer is equipped with a cord having an equipment­grounding conductor and a grounding plug. The plug must be plugged into an appropriate outlet that is properly installed and grounded in accordance with all local codes and ordinances.
WARNING: Improper connection of the equipment-
grounding conductor can result in a risk of electric shock. Check with a qualied electrician or service representative or personnel if you are in doubt as to whether the dryer is properly grounded. Do not modify the plug provided with the dryer: if it will not t the outlet, have a proper outlet installed by a qualied electrician.
SAVE THESE INSTRUCTIONS
11
Loading...
+ 24 hidden pages