WARNING: If the information in these
instructions is not followed exactly, a fire
or explosion may result causing property
damage, personal injury or death.
Do not store or use gasoline or other
flammable vapors and liquids in the
vicinity of this or any other appliance.
WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electrical switch;
do not use any phone in your
building.
• Immediately call your gas supplier
from a neighbor’s phone. Follow
the gas supplier’s instructions.
• If you cannot reach your gas
supplier, call the fire department.
Installation and service must be performed
by a qualified installer, service agency or
the gas supplier.
Installation
Instructions and
Use & Care Guide
To obtain technical, warranty, or service assistance during or after
the installation of this water heater, visit our website at:
http://www.whirlpoolwaterheatersupport.com
or call toll free
1-877-817-6750
When calling for assistance, please have the following
information ready:
1. Model number
2. 7 digit product number
3. Serial number
4. Date of installation
5. Place of purchase
Table of Contents ...................................................... 2
INSTALLER:
• AFFIX THESE INSTRUCTIONS TO OR ADJACENT
TO THE WATER HEATER.
OWNER:
• RETAIN THESE INSTRUCTIONS AND WARRANTY
FOR FUTURE REFERENCE. RETAIN THE ORIGINAL
RECEIPT AS PROOF OF PURCHASE.
6510397
W10100910
September 2006
1
WATER HEATER SAFETY
Your safety and the safety of others are very important.
We have provided many important safety messages in this manual and on your appliance. Always read and obey all
safety messages.
This is the safety alert symbol.
This symbol alerts you to potential hazards that can kill or hurt you and others.
All safety messages will follow the safety alert symbol and either the word “DANGER” or
“WARNING.” These words mean:
You can be killed or seriously injured if you don’t
immediately follow instructions.
You can be killed or seriously injured if you don’t
follow instructions.
All safety messages will tell you what the potential hazard is, tell you how to reduce the chance of injury, and tell you
what can happen if the instructions are not followed.
Important Instructions
• Do not use this appliance if any part has been under water. Immediately call a qualified service technician. Water
heaters subjected to flood conditions or any time the gas controls, main burner or pilot have been submerged in
water require replacement of the entire water heater.
• Hydrogen gas can be produced in a hot water system that has not been used for a long period of time (generally
two weeks or more). Hydrogen gas is extremely flammable and can ignite when exposed to a spark or flame. To
prevent the possibility of injury under these conditions, we recommend the hot water faucet be opened for several
minutes at the kitchen sink before using any electrical appliance which is connected to the hot water system. If
hydrogen is present, there will probably be an unusual sound such as air escaping through the faucet as water
begins to flow. Do not smoke or have any open flame near the faucet at the time it is open.
The California Safe Drinking Water and Toxic Enforcement Act requires the Governor of California to publish a list of
substances known to the State of California to cause cancer, birth defects, or other reproductive harm, and requires
businesses to warn of potential exposure to such substances.
WARNING: This product contains a chemical known to the State of California to cause cancer, birth defects, or other
reproductive harm.
This appliance can cause low-level exposure to some of the substances listed, including formaldehyde, carbon
monoxide, and soot.
Table Of Contents
Water Heater Safety ..............................................................................1-2
Installing Your Gas Water Heater ........................................................3-16
Unpacking the Water Heater ........................................................... 3
Repair Parts Illustration ..................................................................... 27-28
PAGE
2
INSTALLING YOUR GAS WATER HEATER
Important Information About
This Water Heater
This gas water heater was manufactured to voluntary
safety standards to reduce the likelihood of a flammable
vapor ignition incident. New technology used in meeting
these standards makes this product more sensitive to
installation errors or improper installation environments.
Please review the Installation Checklist found at the end of
the installation instructions section and make any required
installation upgrades or changes.
installed in accordance with Massachusetts Plumbing and
Fuel Gas Code 248 CMR Section 2.00 and 5.00.
A data plate identifying your water heater can be found next
to the gas control valve/thermostat. When referring to your
water heater, always have the information listed on the data
plate readily available.
Retain your original receipt as proof of purchase.
Unpacking the Water Heater
WARNING
Consumer Information
This water heater is design-certified by CSA International
as a Category I, non-direct vented water heater which takes
its combustion air either from the installation area or from
air ducted to the unit from the outside.
This water heater must be installed according to all local
and state codes or, in the absence of local and state codes,
the “National Fuel Gas Code”, ANSI Z223.1(NFPA 54)latest edition. This is available from the following:
CSA America, Inc.
8501 East Pleasant Valley Road
Cleveland, OH 44131
National Fire Protection Agency
1 Batterymarch Park
Quincy, MA 02269
Check your phone listings for the local authorities having
jurisdiction over your installation.
Consumer Responsibilities
This manual has been prepared to acquaint you with the
installation, operation, and maintenance of your gas water
heater and provide important safety information in these
areas.
Read all of the instructions thoroughly before attempting
the installation or operation of this water heater.
Do not discard this manual. You or future users of this
water heater will need it for future reference.
Service to the Flame Lock™ Safety System should only be
performed by a qualified person.
Examples of a qualified person include: licensed plumbers,
authorized gas company personnel, and authorized
service personnel.
IMPORTANT: The manufacturer and seller of this water
heater will not be liable for any damages, injuries, or
deaths caused by failure to comply with the installation and
operating instructions outlined in this manual.
If you lack the necessary skills required to properly install
this water heater, or you have difficulty following the
instructions, you should not proceed but have a qualified
person perform the installation of this water heater.
Massachusetts code requires this water heater to be
Excessive Weight Hazard
Use two or more people to move and install
water heater.
Failure to do can result in back or
other injury.
IMPORTANT: Do not remove any permanent instructions,
labels, or the data label from either the outside of the water
heater or on the inside of water heater panels.
• Remove exterior packaging and place installation components aside.
• Inspect all parts for damage prior to installation and
start-up.
• Completely read all instructions before attempting to
assemble and install this product.
• After installation, dispose of/recycle all packaging
materials.
3
WARNING
FLAMMABLES
FIRE AND EXPLOSION HAZARD
Can result in serious injury or death
Do not store or use gasoline or other
flammable vapors and liquids in the
vicinity of this or any other appliance.
Storage of or use of gasoline or other
flammable vapors or liquids in the vicinity
of this or any other appliance can result in
serious injury or death.
Read and follow water heater warnings and
instructions.
Flammable Vapors
Location Requirements
WARNING
Carbon Monoxide Poisoning Hazard
Do not install in a mobile home.
Doing so can result in death or
carbon monoxide poisoning.
The Flame Lock™ Safety System is designed to reduce the
risk of flammable vapor-related fires. The patented system
protects your family by trapping the burning vapors within
the water heater combustion chamber through the special
flame-trap. The burning vapors literally “burn themselves
out” without escaping back into the room. In the event of a
flammable vapor incident, the Flame Lock™ Safety System
shuts off the gas supply to the water heater’s burner and
pilot, preventing re-ignition of any remaining flammable
vapors in the area. This will disable the water heater until
the system is reset. Note: Not following these instructions
and/or an inadequate air supply can cause the Flame
Lock™ Safety System to disable the water heater. Please
make required installation and venting/air supply changes
prior to resetting the system.
IMPORTANT: This water heater has a resettable thermal
switch installed as part of the Flame Lock™ Safety System.
DO NOT attempt to disable or modify this feature in any
way.
Do not use or store flammable products such as gasoline,
solvents, or adhesives in the same room or area near the
water heater. If such flammables must be used, all gas
burning appliances in the vicinity must be shut off and their
pilot lights extinguished. Open the doors and windows for
ventilation while flammable substances are in use.
If flammable liquids or vapors have spilled or leaked in the
area of the water heater, leave the area immediately and
call the fire department from a neighbor’s home. Do not
attempt to clean the spill until all ignition sources have been
extinguished.
Keep combustibles such as boxes, magazines, clothes,
etc. away from the water heater area.
Site Location
• Select a location near the center of the water piping
system. The water heater must be installed indoors
and in a vertical position on a level surface. DO NOT
install in bathrooms, bedrooms, or any occupied room
normally kept closed.
• Locate the water heater as close to the chimney or gas
vent as practical. Consider the vent system piping and
combustion air supply requirements when selecting the
water heater location. The venting system must be able
to run from the water heater to termination with minimal
length and elbows.
• Locate the water heater near the existing gas piping.
If installing a new gas line, locate the water heater to
minimize the pipe length and elbows.
NOTE: This water heater must be installed according to all
local and state codes or, in the absence of local and state
codes, the “National Fuel Gas Code”, ANSI Z223.1(NFPA
4
54)-latest edition.
IMPORTANT: The water heater should be located in
an area where leakage of the tank or connections
will not result in damage to the area adjacent to the
water heater or to lower floors of the structure. Due
to the normal corrosive action of the water, the tank
will eventually leak after an extended period of time.
Also any external plumbing leak, including those from
improper installation, may cause early failure of the tank
due to corrosion if not repaired. If the homeowner is
uncomfortable with making the repair a qualified person
should be contacted. A suitable metal drain pan should
be installed under the water heater as shown below,
to help protect the property from damage which may
occur from condensate formation or leaks in the piping
connections or tank. The pan must limit the water level
to a maximum depth of 1-3/4” and be two inches wider
than the heater and piped to an adequate drain. NOTE:
The pan must not restrict combustion air flow. Locate the
water heater near a suitable indoor drain. Outside drains
are subject to freezing temperatures which can obstruct
the drain line. The piping should be at least 3/4” ID and
pitched for proper drainage. Under no circumstances will
the manufacturer or seller of this water heater be held
liable for any water damage which is caused by your
failure to follow these instructions.
1 3/4” maximum
Pipe to
adequate
drain
Figure 1
Air-moving
Devices
Exhaust
Fan
Reverse flow
of gases
Clearances and Accessibility
NOTE: Minimum clearances from combustible materials
are stated on the data plate adjacent to the gas control
valve/thermostat of the water heater.
The water heater is certified for installation on a
combustible floor.
• IMPORTANT: If installing over carpeting, the carpeting
must be protected by a metal or wood panel beneath
the water heater. The protective panel must extend
beyond the full width and depth of the water heater by
at least three inches (76.2mm) in any direction; or if in
an alcove or closet installation, the entire floor must be
covered by the panel.
• Figure 2 may be used as a reference guide to locate
the specific clearance locations. A minimum of 24
inches of front clearance should be provided for
inspection and service.
At least 2” greater than the
diameter of the water heater.
• The water heater should be located in an area not
subject to freezing temperatures. Water heaters located
in unconditioned spaces (i.e., attics, basements,
etc.) may require insulation of the water piping and
drain piping to protect against freezing. The drain and
controls must be easily accessible for operation and
service. Maintain proper clearances as specified on the
data plate.
• Do not locate the water heater near an air-moving
device. The operation of air-moving devices such as
exhaust fans, ventilation systems, clothes dryers,
fireplaces, etc., can affect the proper operation of
the water heater. Special attention must be given to
conditions these devices may create. Flow reversal of
flue gases may cause an increase of carbon monoxide
inside of the dwelling.
• If the water heater is located in an area that is
subjected to lint, dirt, and oil, it may be necessary
to periodically clean the flame-trap (see External
Inspection & Cleaning of the Flame-trap).
Figure 2
Minimum Clearance
Locations
Back
View
Top
Sides
Front
24” minimum
for service
Top
to
ceiling
Sides
Vent
State of California
NOTE: The water heater must be braced, anchored, or
strapped to avoid moving during an earthquake.
Contact local utilities for code requirements in your area
or call 1-877-817-6750 and request instructions.
5
Gas Supply
WARNING
Explosion Hazard
Use a new CSA approved gas supply line.
Install a shut-off valve.
Do not connect a natural gas water heater to
an L.P. gas supply.
Do not connect an L.P. gas water heater to a
natural gas supply.
Failure to follow these instructions can
result in death, explosion, or
carbon monoxide poisoning.
Gas Requirements
IMPORTANT: Read the data plate to be sure the water
heater is made for the type of gas you will be using in
your home. This information will be found on the data
plate located near the gas control valve/thermostat. If the
information does not agree with the type of gas available,
do not install or light. Call your dealer.
NOTE: An odorant is added by the gas supplier to the gas
used by this water heater. This odorant may fade over an
extended period of time. Do not depend upon this odorant
as an indication of leaking gas.
Gas Piping
The gas piping must be installed according to all local and
state codes or, in the absence of local and state codes, the
“National Fuel Gas Code”, ANSI Z223.1(NFPA 54)-latest
edition.
Tables 1 and 2 on the following page provide a sizing
reference for commonly used gas pipe materials. Consult
the “National Fuel Gas Code” for the recommended gas pipe
size of other materials.
Refer to Figure 3
NOTE: When installing gas piping, apply approved pipe joint
compound.
1. Install a readily accessible manual shut-off valve in the
gas supply line as recommended by the local utility.
Know the location of this valve and how to turn off the
gas to this unit.
2. Install a drip leg (if not already incorporated as part of
the water heater) as shown. The drip leg must be no
less than three inches long for the accumulation of dirt,
foreign material, and water droplets.
3. Install a ground joint union between the gas control
valve/thermostat and the manual shut-off valve. This
is to allow easy removal of the gas control valve/
thermostat.
4. Turn the gas supply on and check for leaks. Test all
connections by brushing on an approved noncorrosive
leak-detection solution. Bubbles will show a leak.
Correct any leak found.
6
Figure 3
Gas Piping
Manual Gas
Shut-off Valve
Ground
Joint
Union
Check with
local utility
for minimum height
3” minimum
Drip leg
Gas Pressure
IMPORTANT: The gas supply pressure must not exceed
the maximum supply pressure as stated on the water
heater’s data plate. The minimum supply pressure is for the
purpose of input adjustment.
Gas Pressure Testing
IMPORTANT: This water heater and its gas connection
must be leak tested before placing the appliance in
operation.
• If the code requires the gas lines to be tested at a
pressure exceeding 14” W.C., the water heater and its
manual shut-off valve must be disconnected from the
gas supply piping system and the line capped.
• If the gas lines are to be tested at a pressure less than
14” W.C., the water heater must be isolated from the
gas supply piping system by closing its manual shut-off
valve.
U.L. recognized fuel gas and carbon monoxide (CO)
detectors are recommended in all applications and should
be installed using the manufacturer’s instructions and local
codes, rules, or regulations.
NOTE: Air may be present in the gas lines and could
prevent the pilot from lighting on initial start-up. The gas
lines should be purged of air by a qualified person after
installation of the gas piping system.
LP Gas Only
WARNING
Explosion Hazard
Have a qualified person make sure L.P. gas
pressure does not exceed 13” water column.
Examples of a qualified person include:
licensed plumbers, authorized gas company
personnel, and authorized service
personnel.
Failure to do so can result in death,
explosion, or fire.
Combustion Air Supply and
Ventilation
WARNING
Carbon Monoxide Warning
Follow all the local and state codes or, in
the absence of local and state codes, the
“National Fuel Gas Code”, ANSI Z223.1
(NFPA 54)- latest edition to properly install
vent system.
Failure to do so can result in death,
explosion, or carbon monoxide poisoning.
IMPORTANT: Air for combustion and ventilation must not
come from a corrosive atmosphere. Any failure due to
corrosive elements in the atmosphere is excluded from
warranty coverage.
The following types of installation (not limited to the
following) will require outdoor air for combustion due to
chemical exposure and may reduce but not eliminate the
presence of corrosive chemicals in the air:
• beauty shops
• photo processing labs
• buildings with indoor pools
• water heaters installed in laundry, hobby, or craft rooms
• water heaters installed near chemical storage areas
Combustion air must be free of acid-forming chemicals
such as sulfur, fluorine, and chlorine. These elements are
found in aerosol sprays, detergents, bleaches, cleaning
solvents, air fresheners, paint, and varnish removers,
refrigerants, and many other commercial and household
products. When burned, vapors from these products form
highly corrosive acid compounds. These products should
not be stored or used near the water heater or air inlet.
Combustion and ventilation air requirements are
determined by the location of the water heater. The water
heater may be located in either an open (unconfined) area
or in a confined area or small enclosure such as a closet or
small room. Confined spaces are areas with less than 50
cubic feet for each 1,000 BTUH of the total input for all gasusing appliances.
7
Unconfined Space
A water heater in an unconfined space uses indoor air for
combustion and requires at least 50 cubic feet for each
1,000 BTUH of the total input for all gas appliances. The
table below shows a few examples of the minimum square
footage (area) required for various BTUH inputs.
Table 2
BTUH
Input
Minimum Square
Feet with
8' Ceiling
Typical Room
with 8' Ceiling
Figure 4
Opening LocationsConfined Spaces
Permanent
openings to
the outside or
additional
rooms within
the building
12” maximum
Closet
or
other
confined
space
30,000
45,000
60,000
75,000
90,000
105,000
120,000
135,000
188
281
375
469
563
657
750
844
9x21
14x20
15x25
15x31
20x28
20x33
25x30
28x30
IMPORTANT:
• The area must be open and be able to provide the
proper air requirements to the water heater. Areas that
are being used for storage or contain large objects may
not be suitable for water heater installation.
• Water heaters installed in open spaces in buildings with
unusually tight construction may still require outdoor
air to function properly. In this situation, outside air
openings should be sized the same as for a confined
space.
• Modern home construction usually requires supplying
outside air into the water heater area.
Confined Space
For the correct and proper operation of this water heater,
ample air must be supplied for the combustion, ventilation,
and dilution of flue gases. Small enclosures and confined
areas must have two permanent openings so that sufficient
fresh air can be drawn from outside of the enclosure. One
opening shall be within 12 inches of the top and one within
12 inches of the bottom of the enclosure as shown in
Figure 4.
The size of each opening (free area) is determined by the
total BTUH input of all gas utilization equipment (i.e., water
heaters, furnaces, clothes dryers, etc.) and the method by
which the air is provided. The BTUH input can be found on
the water heater data plate. Additional air can be provided
by two methods:
1. All air from inside the building.
2. All air from outdoors.
12” maximum
All Air from Inside the Building
When additional air is to be provided to the confined area
from additional room(s) within the building, the total volume
of the room(s) must be of sufficient size to properly provide
the necessary amount of fresh air to the water heater
and other gas utilization equipment in the area. If you are
unsure that the structure meets this requirement, contact
your local gas utility company or other qualified agency for
a safety inspection.
Each of the two openings shall have a minimum free area
of 1 square inch per 1,000 BTUH of the total input rating of
all gas utilization equipment in the confined area, but not
less than 100 square inches (Figure 5).
Confined
Space
Permanent
Openings
1 square
inch/1000
BTUH
(minimum
100 sq. In.)
Figure 5
All Air from Inside Building
Confined Space Installation
8
All Air from Outdoors
Outdoor fresh air can be provided to a confined area either
directly or by the use of vertical and horizontal ducts. The
fresh air can be taken from the outdoors or from crawl or
attic spaces that freely communicate with the outdoors.
Attic or crawl spaces cannot be closed and must be
properly ventilated to the outside.
Ductwork must be of the same cross-sectional area as
the free area of the opening to which they connect. The
minimum dimension of rectangular air ducts cannot be less
than three inches.
The size of each of the two openings is determined by the
method in which the air is to be provided. Refer to Table
3 to calculate the minimum free area for each opening.
Figures 6, 7, and 8 are typical examples of each method.
Louvers and Grilles
In calculating free area for ventilation and combustion
air supply openings, consideration must be given to the
blocking effect of protection louvers, grilles, and screens.
These devices can reduce airflow, which in turn may
require larger openings to achieve the required minimum
free area. Screens must not be smaller than 1/4” mesh. If
the free area through a particular design of louver or grille
is known, it should be used in calculating the specified free
area of the opening. If the design and free area are not
known, it can be assumed that most wood louvers will allow
20 - 25% of free area while metal louvers and grilles will
allow 60 - 75% of free area.
Louvers and grilles must be locked open or interconnected
with the equipment so that they are opened automatically
during equipment operation.
Keep louvers and grilles clean and free of debris or other
obstructions.
Gable vent
to outdoors
Install above
insulation
Confined
Space
Alternate
Air Inlet
1 sq. inch per
4000 BTUH
Figure 6
All Air from Outdoors; Inlet Air from Ventilated
Crawl Space/Outlet Air to Ventilated Attic
Confined
Space
Outlet
air to attic
1 Sq. inch per
4000 BTUH
Inlet air
from the
crawl
space
Open
Foundation
Vent
Gable vent
to outdoors
Install above
insulation
Outlet air
to attic
1 Sq. inch per
4000 BTUH
Inlet air duct
1 sq. inch per
4000 BTUH
Table 3
Minimum Free Area of Permanent Openings for Ventilation and
Combustion Air Supply - All Air from Outdoors Only.
Based on the total BTUH input rating for all gas utilizing equipment
within the confined space.
Opening
Source
Direct to
outdoors
Vertical ducts
Horizontal ducts
Example: A water heater with an input rate of 50,000 BTUH using
horizontal ducts would require each opening to have a minimum
free area of 25 square inches.
Minimum free area = 50,000 BTUH x 1 sq. in. / 2000 BTUH = 25
Sq. Inches.
These openings connect directly with the outdoors
*
Per Opening
(sq. in.)
1 Square inch per 4000
BTUH
1 Square inch per 4000
BTUH
1 Square inch per 2000
BTUH
Minimum Free Area
Reference
Drawing
Figure 6
Figure 7
Figure 8
through a ventilated attic, a ventilated crawl space, or
through an outside wall.
Consult the local codes of your area for specific ventilation
and combustion air requirements.
Figure 7
All Air from Outdoors
Through Ventilated Attic
Confined
Space
Figure 8
All Air from Outdoors
Using Horizontal Ducts
12” maximum
1sq.inch
per
2000 BTUH
Outlet
Outdoor
Air Ducts
Inlet
1 sq. Inch
per
2000 BTUH
9
Vent Pipe System
This water heater uses a non-direct, single-pipe vent
system to remove exhaust gases created by the burning of
fossil fuels. Air for combustion is taken from the immediate
water heater location or is ducted in from the outside (see
“Combustion Air Supply and Ventilation”).
This water heater must be properly vented for the removal
of exhaust gases to the outside atmosphere. Correct
installation of the vent pipe system is mandatory for the
proper and efficient operation of this water heater and is an
important factor in the life of the unit.
The vent pipe must be installed according to all local and
state codes or, in the absence of local and state codes, the
“National Fuel Gas Code”, ANSI Z223.1(NFPA 54)-latest
edition. The vent pipe installation must not be obstructed so
as to prevent the removal of exhaust gases to the outside
atmosphere.
IMPORTANT: The use of vent dampers is not
recommended by the manufacturer of this water heater.
Although some vent dampers are certified by CSA
International, this certification applies to the vent damper
device only and does not mean they are certified for use on
this water heater.
U.L. recognized fuel gas and carbon monoxide (CO)
detectors are recommended in all applications and should
be installed using the manufacturer’s instructions and local
codes, rules, or regulations.
IMPORTANT: If you lack the necessary skills required
to properly install this venting system, you should not
proceed, but get help from a qualified person.
Drafthood Installation
Align the legs of the drafthood with the slots provided.
Insert the legs and secure the drafthood to the water
heater’s top with the four screws provided as shown in
Figure 9. Do not alter the drafthood in any way. If you are
replacing an existing water heater, be sure to use the new
drafthood supplied with the water heater.
Figure 9
Drafthood Installation
Sheet Metal Screws (four provided)
Vent Pipe Size
It is important that you follow the guidelines in these
instructions for sizing a vent pipe system. If a transition to
a larger vent size is required, the vent transition connection
must be made at the drafthood outlet.
Vent Connectors
1. Type B, Double wall, U.L. Listed Vent Pipe.
2. Single wall Vent Pipe.
Maintain the manufacturer’s specified minimum clearance
from combustible materials when using type B double wall
vent pipe.
Vent connectors made of type B, double wall vent pipe
material may pass through walls or partitions constructed
of combustible material if the minimum listed clearance is
maintained.
Maintain a six inch minimum clearance from all combustible
materials when using single wall vent pipe.
IMPORTANT: Single wall vent pipe cannot be used for
water heaters located in attics and may not pass through
attic spaces, crawl spaces or any confined or inaccessible
location. A single wall metal vent connector cannot pass
through any interior wall.
When installing a vent connector, please note the following:
• Install the vent connector avoiding unnecessary bends,
which create resistance to the flow of vent gases.
• Install without dips or sags with an upward slope of at
least 1/4-inch per foot.
• Joints must be fastened by sheet metal screws or other
approved means. It must be supported to maintain
clearances and prevent separation of joints and
damage.
• The length of the vent connector cannot exceed 75% of
the vertical vent height.
• The vent connector must be accessible for cleaning,
inspection, and replacement.
• Vent connectors cannot pass through any ceiling, floor,
firewall, or fire partition.
IMPORTANT: Existing vent systems must be inspected for
obstructions, corrosion, and proper installation.
10
Slots
Legs
Jacket top
Install the drafthood with
the four screws provided.
Drafthood
Legs
Slots
Chimney Connection
IMPORTANT: Before connecting a vent to a chimney,
make sure the chimney passageway is clear and free of
obstructions. The chimney must be cleaned if previously
used for venting solid fuel appliances or fireplaces. Also
consult local and state codes for proper chimney sizing and
application or, in the absence of local and state codes, the
“National Fuel Gas Code”, ANSI Z223.1(NFPA 54)-latest
edition.
• The connector must be installed above the extreme
bottom of the chimney to prevent potentially blocking
the flue gases.
• The connector must be firmly attached and sealed to
prevent it from falling out.
• To aid in removing the connector, a thimble or slip joint
may be used.
• The connector must not extend beyond the inner edge
of the chimney as it may restrict the space between it
and the opposite wall of the chimney (Figure 10).
Do not terminate the vent connector in a chimney that has
not been certified for this purpose. Some local codes may
prohibit the termination of vent connectors in a masonry
chimney.
3 ft. minimum
*
*
Slope up
1/4 in.
per ft.
minimum
3 ft. minimum
Listed Lined
Chimney
2 ft. minimum above any
object within10 ft.
horizontally
2 ft. minimum above any
object within10 ft.
horizontally
Vertical Exhaust Gas Vent
Vertical exhaust gas vents must be installed with U.L. listed
type B vent pipe according to the vent manufacturer’s
instructions and the terms of its listing.
It must be connected to the water heater’s drafthood by
a listed vent connector or by directly originating at the
drafthood opening.
Vertical gas vents must terminate with a listed cap or
other roof assembly and be installed according to their
manufacturer’s instructions.
Gas vents must be supported to prevent damage, joint
separation, and maintain clearances to combustible
materials (Figures 11 and 12).
IMPORTANT: This gas vent must be terminated in a vertical
position to facilitate the removal of the burnt gases.
An unused chimney flue or masonry enclosure may be
used as a passageway for the installation of a gas vent
(Figure 12).
Common (combined) venting is allowable with vertical type
B vent systems and lined masonry chimneys.
Figures 10-12 are examples of vent pipe system
installations and may or may not be typical for your specific
application. Consult the “National Fuel Gas Code”, NFPA
54, ANSI Z223.1-latest edition and the guidelines set forth
by prevailing local codes.
**
Vent
connector
slope up
1/4 in. per ft.
minimum
5 in. minimum
*
Slope up
1/4 in.
per ft.
minimum
Maintain vent pipe clearance requirements to local, state
*
and/or the “National Fuel Gas Code”, ANSI Z223.1(NFPA
**
54)-latest edition.
NFPA 211, Standard for Chimneys, Fireplaces, Vents,
**
and Solid Fuel-Burning Appliances states that these
chimneys are intended to be installed in accordance with
the installation instructions provided with each chimney
support assembly. Minimum air space clearance to
combustible materials should be maintained as marked on
the chimney sections.
11
Water System Piping
Piping Installation
Piping, fittings, and valves should be installed according to
the installation drawing (Figure 13). If the indoor installation
area is subject to freezing temperatures, the water piping
must be protected by insulation.
Water supply pressure should not exceed 80% of the
working pressure of the water heater. The working pressure
is stated on the water heater’s data plate. If this occurs,
a pressure limiting valve with a bypass may need to be
installed in the cold water inlet line. This should be placed
on the supply to the entire house in order to maintain equal
hot and cold water pressures.
IMPORTANT: Heat cannot be applied to the water fittings
on the heater as they may contain nonmetallic parts. If
solder connections are used, solder the pipe to the adapter
before attaching the adapter to the hot and cold water
fittings.
IMPORTANT: Always use a good grade of joint compound
and be certain that all fittings are drawn up tight.
1. Install the water piping and fittings as shown in Figure
13. Connect the cold water supply (3/4” NPT) to the
fitting marked “C”. Connect the hot water supply (3/4”
NPT) to the fitting marked “H”.
IMPORTANT: Some models may contain energy saving
heat traps to prevent the circulation of hot water within the
pipes. Do not remove the inserts within the heat traps.
2. The installation of unions in both the hot and cold water
supply lines is recommended for ease of removing the
water heater for service or replacement.
3. The manufacturer of this water heater recommends
installing a tempering valve or an anti-scald device
in the domestic hot water line as shown in Figure 14.
These valves reduce the point-of-use temperature of
the water by mixing cold and hot water and are readily
available for use.
4. If installing the water heater in a closed water system,
install an expansion tank in the cold water line as
specified under Closed System/Thermal Expansion.
5. Install a shut-off valve in the cold water inlet line. It
should be located close to the water heater and be
easily accessible. Know the location of this valve and
how to shut off the water to the heater.
6. A temperature and pressure relief valve must be
installed in the opening marked “Temperature and
Pressure (T & P) Relief Valve” on the water heater.
A discharge line must be added to the opening of
the T&P Relief Valve. Follow the instructions under
Temperature and Pressure Relief Valve.
7. After piping has been properly connected to the water
heater, remove the aerator at the nearest hot water
faucet. Open the hot water faucet and allow the tank to
completely fill with water. To purge the lines of any excess air, keep the hot water faucet open for 3 minutes
after a constant flow of water is obtained. Close the
faucet and check all connections for leaks.
Figure 13
Water Piping Installation
Hot Water
Outlet
Union
1”minimum
Metal
Drain Pan
1 3/4” depth maximum
Figure 14
Typical Tempering
Valve Installation
Follow the tempering
valve manufacturer’s
instructions.
Tempered water
to fixtures
In a closed system use a
thermal expansion tank
Cold Water
Inlet Valve
Temperature and
Pressure Relief Valve
Discharge line
6” maximum
above drain
Drain line
3/4” ID
minimum
Drain
Hot
Water
Outlet
Cold Water
Supply to Fixtures
Main
Water
Supply
Pressure reducing
valve with bypass
Massachusetts:
Install a vacuum relief
in cold water line per
section 19 MGL 142.
Cold
Water
Inlet
Tempering valve
(Set to 120°F)
12
Please note the following:
• The system should be installed only with piping that is
suitable for potable (drinkable) water such as copper,
CPVC, or polybutylene. This water heater must not be
installed using iron piping or PVC water piping.
• Use only pumps, valves, or fittings that are compatible
with potable water.
• Use only full flow ball or gate valves. The use of valves
that may cause excessive restriction to water flow is
not recommended.
• Use only 95/5 tin-antimony or other equivalent solder.
Any lead based solder must not be used.
• Piping that has been treated with chromates, boiler
seal, or other chemicals must not be used.
• Chemicals that may contaminate the potable water
supply must not be added to the piping system.
Closed System/Thermal Expansion
WARNING
Explosion Hazard
If the temperature and pressure relief valve
is dripping or leaking, have a qualified
person replace it.
Examples of a qualified person include:
licensed plumbers, authorized gas company
personnel, and authorized service
personnel.
Do not plug valve.
Do not remove valve.
Failure to follow these instructions can
result in death, or explosion.
Periodic discharge of the temperature and pressure relief
valve may be due to thermal expansion in a closed water
supply system. The water utility supply meter may contain a
check valve, backflow preventer or water pressure reducing
valve. This will create a closed water system. During
the heating cycle of the water heater, the water expands
causing pressure inside the water heater to increase. This
may cause the temperature and pressure relief valve to
discharge small quantities of hot water. To prevent this, it
is recommended that a diaphragm-type expansion tank
(suitable for potable water) be installed on the cold water
supply line. The expansion tank must have a minimum
capacity of 1.5 U.S. gallons for every 50 gallons of stored
water. Contact the local water supplier or plumbing
inspector for information on other methods to control this
situation.
IMPORTANT: Do not plug or remove the temperature and
pressure relief valve.
13
Temperature and Pressure
Relief Valve
WARNING
Explosion Hazard
If the temperature and pressure relief valve
is dripping or leaking, have a qualified
person replace it.
Examples of a qualified person include:
licensed plumbers, authorized gas company
personnel, and authorized service
personnel.
Do not plug valve.
Do not remove valve.
Failure to follow these instructions can
result in death, or explosion.
Figure 15A
Temperature and Pressure
Relief Valve Installation
Discharge line 3/4" minimum
Do not cap or plug.
6" maximum
IMPORTANT: Only a new temperature and pressure relief
valve should be used with your water heater. Do not use an
old or existing valve as it may be damaged or not adequate
for the working pressure of the new water heater. Do not
place any valve between the relief valve and the tank.
The Temperature & Pressure Relief Valve:
• Must not be in contact with any electrical part.
• Must be connected to an adequate discharge line.
• Must not be rated higher than the working pressure
shown on the data plate of the water heater.
The Discharge Line:
• Must not be smaller than the pipe size of the relief
valve or have any reducing coupling installed in the
discharge line.
• Must not be capped, blocked, plugged or contain any
valve between the relief valve and the end of the discharge line.
• Must terminate a maximum of six inches above a floor
drain or external to the building.
• Must be capable of withstanding 250°F (121°C) without
distortion.
• Must be installed to allow complete drainage of both
the valve and discharge line.
T&P Relief Valve and Pipe Insulation (Some Models)
1. Locate the T&P Relief Valve on the water heater.
2. Locate the slit running the length of the insulation.
3 Spread this slit open and slip it over the T&P Relief Valve.
See Figure 15B. Apply gentle pressure to the insulation
to ensure it is fully seated on the T&P Relief Valve. Once
sealed secure the insulation with a section of tape.
IMPORTANT: The insulation or tape should not block or
cover the T&P Relief Valve drain opening. Also the
insulation or tape should not block or hinder access to the
T&P Relief Valve manual relief lever.
4. Next locate the hot water (outlet) & cold water (inlet) pipes
to the water heater.
5. Select one of the sections of pipe insulation and locate the
slit that runs the length of the insulation.
6. Spread the slit open at the base of the insulation and slip
it over the cold water (inlet) pipe. Apply gentle
pressure along the length of the insulation to ensure it is
fully seated around the cold water pipe. Also ensure that
the base of insulation is flush with the water heater. Once
seated, secure the insulation with a section of tape.
7. Repeat steps 5 through 6 for the hot water (outlet) pipe.
For protection against excessive pressures and
temperatures, a temperature and pressure relief valve must
be installed in the opening marked “T & P RELIEF VALVE”
(see Figure 15A). This valve must be design certified by
a nationally recognized testing laboratory that maintains
periodic inspection of the production of listed equipment or
materials as meeting the requirements for Relief Valves and
Automatic Shut-off Devices for Hot Water Supply Systems,
ANSI Z21.22. The function of the temperature and pressure
relief valve is to discharge water in large quantities in the
event of excessive temperature or pressure developing
in the water heater. The valve’s relief pressure must not
exceed the working pressure of the water heater as stated
on the data plate.
14
Figure 15B
T&P Relief Valve Insulation
T&P Relief Valve Insulation
Manual Relief Lever
T&P Relief Valve
T&P Relief Valve
Drain Line
Special Applications
Combination Space Heating/Potable
Water System
Some water heater models are equipped with inlet/outlet
tappings for use with space heating applications. If this
water heater is to be used to supply both space heating
and domestic potable (drinking) water, the instructions
listed below must be followed.
• Be sure to follow the manual(s) shipped with the air
handler system.
• This water heater is not to be used as a replacement
for an existing boiler installation.
• Do not use with piping that has been treated with
chromates, boiler seal or other chemicals and do not
add any chemicals to the water heater piping.
• If the space heating system requires water temperatures in excess of 120°F, a tempering valve or an antiscald device should be installed per its manufacturer’s
instructions in the domestic (potable) hot water supply
to limit the risk of scald injury.
• Pumps, valves, piping and fittings must be compatible
with potable water.
• A properly installed flow control valve is required to prevent thermosiphoning. Thermosiphoning is the result
of a continuous flow of water through the air handler
circuit during the off cycle. Weeping (blow off) of the
temperature and pressure relief valve (T & P) or higher
than normal water temperatures are the first signs of
thermosiphoning.
• The domestic hot water line from the water heater
should be vertical past any tempering valve or supply
line to the air handler to remove air bubbles from the
system. Otherwise, these bubbles will be trapped in the
air handler heat exchanger coil, reducing the efficiency.
• Do not connect the water heater to any system or
components previously used with non-potable water
heating appliances when used to supply potable water.
Some jurisdictions may require a backflow preventer
in the incoming cold water line. This may cause the
temperature and pressure relief valve on the water heater
to discharge or weep due to expansion of the heated water.
A diaphragm-type expansion tank suitable for potable
water will normally eliminate this weeping condition. Please
read and follow the manufacturer’s instructions for the
installation of such tanks.
Also see Water System Piping for additional instructions on
the safe and correct installation and operation of this water
heater.
Figure 16
Typical Tempering Valve Installation
Combination Space Heating/Potable
Water Heating System
Domestic
Hot Water
Out
Tempering
Valve
Hot
Water
Out
Unions
Must be vertical to
remove air bubbles
Cold
Water
Inlet
To
Air
Handler
Shut-off
Valve
Flow Control
Pump
Massachusetts code
does not allow this
type of installation.
Valve
Out
Handler
In
Coil
Air
Solar Installation
If this water heater is used as a solar storage heater or as a
backup for the solar system, the water supply temperatures
to the water heater tank may be in excess of 120°F. A
tempering valve or other temperature limiting valve must
be installed in the water supply line to limit the supply
temperature to 120°F.
NOTE: Solar water heating systems can often supply water
with temperatures exceeding 180°F and may result in water
heater malfunction.
15
Important Information About This Water Heater
This gas water heater was manufactured to voluntary safety standards to reduce the likelihood of a flammable vapor ignition
incident. The new technology used in meeting these standards makes this product more sensitive to installation errors.
Please review the following checklist and make any required installation upgrades or changes.
Questions? Call 1-877-817-6750.
Installation Checklist
Water Heater Location
Water heater location is important and can affect system
performance. Please check the following:
□ Installation area free of corrosive elements and
flammable materials.
□ Centrally located with the water piping system.
Located as close to the gas piping and vent pipe
system as possible.
□ Located indoors and in a vertical position. Protected
from freezing temperatures.
□ Proper clearances from combustible surfaces
maintained and not installed directly on a carpeted
floor.
□ Provisions made to protect the area from water
damage. Drain pan installed and piped to an
adequate drain.
□ Sufficient room to service the water heater. See
Clearances and Accessibility section of this manual.
□ Water heater not located near an air moving device.
□ Is the installed environment dirty (excessive
amounts of lint, dirt, dust, etc.)? If so, the flame
arrestor located on the bottom of the water heater
will need to be cleaned periodically. Refer to the
Maintenance of your Water Heater section of this
manual for information on cleaning the flame-trap.
Combustion Air Supply and Ventilation
Check for sufficient combustion air supply. Insufficient air
for the combustion of gas will result in the flame becoming
“lazy”, thereby allowing heat to build up in the combustion
chamber. This excessive heat will cause a thermal switch
on the door assembly to trip. Is the water heater installed in
a closet or other small, enclosed space? If so:
□ Are there openings for make-up air to enter and
exit the room/area?
□ Are the openings of sufficient size? Remember,
if there are other gas-fired or air-consuming
appliances in the same room, you need more
make-up air. Refer to the Location Requirements
section of this water heater manual for specific
requirements.
Fresh air not taken from areas that contain negative
pressure producing devices such as exhaust fans,
fireplaces, etc.
□ Is there a furnace/air handler in the same room
space as the water heater? If so, has a return air
duct system been attached that exits the room?
If so, check for leaks on the air duct system. If no
air duct system is present, correct immediately
by contacting a local Heating, Ventilation, AirConditioning & Refrigeration (HVAC-R) authorized
service provider.
□ Fresh air supply free of corrosive elements and
flammable vapors.
□ Fresh air openings sized correctly with consideration
given to the blocking effect of louvers and grilles.
□ Ductwork is the same cross-sectional area as the
openings.
Vent Pipe System
Check for proper drafting at the water heater draft hood.
Refer to the “Checking the Draft” section of this manual for
the test procedure. If the procedure shows insufficient draft
is present, please check the following.
□ Drafthood properly installed.
□ Vent connectors securely fastened with screws and
supported properly to maintain six inch clearance.
□ Vent connector made of approved material and
sized correctly.
□ Vent pipe system installed according to all local
and state codes or, in the absence of local and
state codes, the “National Fuel Gas Code”, ANSI
Z223.1(NFPA 54)-latest edition.
□ Flue baffle engaged in slots provided in the flue tube.
□ Check the vent system for restrictions/obstructions
and check the vent termination height. Refer to
the Air Supply and Ventilation section of this water
heater manual for specific requirements.
□ Recheck for sufficient combustion air supply.
Water System Piping
□ Temperature and pressure relief valve properly
installed with a discharge line run to an open drain
and protected from freezing.
□ All piping properly installed and free of leaks.
□ Heater completely filled with water.
□ Closed system pressure build-up devices installed.
□ Tempering valve (when applicable) installed per
manufacturer’s instructions (See Water Temperature
Regulation section).
Gas Supply and Piping
□ Gas type is the same as that listed on the water
heater data plate.
□ Gas line equipped with shut-off valve, union, and
used to check all connections and fittings for possible
gas leaks. Correct any leak found.
16
OPERATING YOUR WATER HEATER
Lighting Instructions
Read and understand these directions thoroughly before
attempting to light or re-light the pilot. Make sure the
viewport is not missing or damaged. (See Figure 23)
Make sure the tank is completely filled with water before
lighting the pilot. Check the data plate near the gas control
valve/thermostat for the correct gas. Do not use this water
heater with any gas other than the one listed on the data
plate. If you have any questions or doubts, consult your gas
supplier or gas utility company.
FOR YOUR SAFETY READ BEFORE LIGHTING
WARNING:
may result causing property damage, personal injury or loss of life.
A. This appliance has a pilot which is lighted by a
piezoelectric igniter. When lighting the pilot, follow these
instructions exactly.
B. BEFORE LIGHTING smell all around the appliance area
for gas. Be sure to smell next to the floor because some
gas is heavier than air and will settle on the floor.
WHAT TO DO IF YOU SMELL GAS:
vDo not try to light any appliance.
vDo not touch any electrical switch; do not use any
phone in your building.
vImmediately call your gas supplier from a
neighbor’s phone. Follow the gas supplier’s
instructions.
vIf you cannot reach your gas supplier, call the fire
department.
If you do not follow these instructions exactly, a fire or explosion
WARNING
Explosion Hazard
Replace viewport if glass is
missing or damaged.
Failure to do so can result in
death, explosion or fire.
C. Use only your hand to push in or turn the gas control
knob. Never use tools. If the knob will not push in or
move by hand, don’t try to repair it, call a qualified service
technician. Force or attempted repair may result in a fire
or explosion.
D. Do not use this appliance if any part has been under
water. Immediately call a qualified service technician to
inspect the appliance. Water heaters subjected to flood
conditions or anytime the gas controls, main burner or
pilot have been submerged in water require replacement
of the entire water heater.
E. DO NOT USE THIS APPLIANCE IF THERE HAS BEEN AN
IGNITION OF VAPORS. Immediately call a qualified service
technician to inspect the appliance. Water heaters
subjected to a flammable vapors ignition will show a
discoloration on the air intake grid and require
replacement of the entire water heater.
LIGHTING INSTRUCTIONS
1. STOP! It is imperative that you read all the safety warnings
before lighting the pilot.
2. Remove the outer door.
3. Turn the temperature dial counterclockwise to its
lowest setting.
RESET
BUTTON
UNITROL
R
E
W
A
B
D
AR
E
A
F
OR
L
N
L
IN
INS
E
G
T
R
U
LIGH
T
O
H
W
A
R
M
C
A
U
T
I
O
N
INDEX
C
T
I
O
N
TIN
S
G
BARS
V
A
C
A
T
I
O
N
4. Depress the dial stop and turn
gas control knob clockwise
to the “OFF” position.
5. To clear any gas that may have
accumulated wait ten (10) minutes.
If you then smell gas, STOP! Follow “B” in the safety
warning above. If you do not smell gas go to the next
step.
6. Turn the gas control knob
counterclockwise
to “PILOT”.
GAS
CONTROL
KNOB
DIAL
STOP
130° F
BAR
130° F
BAR
T
O
H
120° F
BAR
W
A
R
M
T
I
O
U
N
A
C
V
W
T
H
S
A
A
R
O
Y
H
E
T
T
T
E
E
R
S
E
C
R
A
U
E
I
N
R
R
C
J
A
I
N
S
I
K
T
D
O
L
F
A
S
C
I
O
N
N
O
CAUTION
DO NOT PRY
P
ON DIAL
I
L
DAMAGE
O
T
WILL
RESULT
O
F
F
CAUTION
DO NOT PRY
O
ON DIAL
F
DAMAGE
F
N
WILL
O
RESULT
P
T
I
L
O
7. Depress the reset button all the way
PUSHBUTTON
in and IMMEDIATELY depress the
igniter button until you hear a loud
click. Observe the pilot through the
view port. Do not release the reset
button. Repeat immediately if pilot
does not light on the first try. If the
pilot does not light by the fourth
attempt with the igniter, repeat steps
4 - 7. Continue to hold the button for
about (1) minute after the pilot is lit.
Release the reset button and it will pop
back up. Pilot should remain lit. If the
pilot light goes out, repeat steps 3 - 7.
IGNITER
IMPORTANT: If the pilot will not stay lit after several tries,
depress the dial stop and turn gas control knob to “OFF”,
then call your service technician or gas supplier.
IMPORTANT: If the reset button (see graphic at step 3) does
not pop up when released, stop and immediately shut off
the gas at the line valve or tank. Call your service technician
or gas supplier.
8. Turn the gas control knob
counterclockwise
to “ON”.
9. Set the temperature dial to
F
F
O
CAUTION
DO NOT PRY
T
ON DIAL
O
DAMAGE
L
I
WILL
P
RESULT
O
N
the desired setting.
10. Replace the outer door.
TO TURN OFF GAS TO APPLIANCE
1. Turn the temperature dial counterclockwise to its
lowest setting.
2. Turn the gas control knob clockwise to the “OFF”
position.
17
L.P.G. (Bottled Propane) Models
Liquefi ed petroleum gas is over 50% heavier than air
and in the occurrence of a leak in the system, the gas
will settle at fl oor level. Basements, crawl spaces, skirted
areas under mobile homes (even when ventilated), closets
and areas below ground level will serve as pockets for
the accumulation of gas. Before lighting an L.P. gas water
heater, smell all around the appliance at fl oor level. If you
smell gas, follow the instructions as given in the warning on
the front page.
When your L.P. tank runs out of fuel, turn off the gas at
all gas appliances including pilot lights. After the tank is
refi lled, all appliances must be re-lit according to their
manufacturer’s instructions.
Water Temperature Regulation
WARNING
Checking the Draft
WARNING
Burn Hazard
Do not touch vent.
Doing so can result in burns.
After successfully lighting the water heater, allow the unit
to operate for 15 minutes and check the drafthood relief
opening for proper draft. Make sure all other appliances
in the area are operating and
all doors are closed when
performing the draft test. Pass
a match flame around the relief
opening of the drafthood. A
steady flame drawn into the
opening indicates proper draft.
If the flame flutters or is blown
out, combustion products
are escaping from the relief opening. If this occurs, do
not operate the water heater until proper adjustments or
repairs are made to the vent pipe system and/or air supply
requirements.
Burner Flames
Inspect the burner
flames through the
viewport and compare
them to the drawings
in Figure 18. A properly
operating burner should
produce a soft blue
flame. Blue tips with
yellow inner cones are
satisfactory. The tips of the flame may have a slight yellow
tint. The flame should not be all yellow or have a sharp
blue-orange color. Contaminated air may cause an orange
colored flame. Contact a qualified person if the flame is not
satisfactory.
Stacking
Stacking occurs when a series of short draws of hot water
(3 gallons or less) are taken from the water heater tank.
This causes increased cycling of the burner and can result
in increased water temperatures at the hot water outlet. An
anti-scald device is recommended in the hot water supply
line to reduce the risk of scald injury.
Emergency Shut Down
IMPORTANT: Should overheating occur or the gas supply
fails to shut off, turn off the water heater’s manual gas
control valve and call a qualified person.
18
Figure 17
Match
Figure 18
Flame Characteristics
Correct flame
soft blue
Drafthood
Opening
Tips may have
a yellow tint
Yellow inner
cones are
satisfactory
Relief
Water temperature over 125°F can cause
severe burns instantly or death from scalds.
Children, disabled and elderly are at highest
risk of being scalded.
Feel water before bathing or showering.
Temperature limiting valves are available.
The thermostat is adjusted to its lowest temperature
when it is shipped from the factory. Water temperature
can be regulated by moving the temperature dial to the
preferred setting. The preferred starting point is 120°F.
Align the index bar on the thermostat with the desired water
temperature as shown in Figure 19. There is a hot water
scald potential if the thermostat is set too high.
IMPORTANT: Adjusting the thermostat past the 120°F bar
on the temperature dial will increase the risk of scald injury.
Hot water can produce first degree burns within:
120°F (49°C) more than 5 minutes
130°F (54°C) at 20 seconds
140°F (60°C) at 3 seconds
150°F (66°C) at 1-1/2 seconds
160°F (71°C) at less than 1 second
Figure 19
Robertshaw Gas Valve/Thermostat
Settings
UNITROL
R
E
A
BEFO
D
A
R
T
O
H
C
A
U
T
Reset
Button
Control
Knob
Dial
W
ARNIN
L
L
IN
E
G
S
T
R
U
C
LIG
T
IO
HTING
N
S
W
A
R
M
I
O
N
V
A
C
A
T
I
O
N
Stop
Index
Bars
Gas
130°F
Bar
130°F
Bar
O
H
A
C
T
W
T
H
A
H
T
E
E
R
R
I
S
K
O
NOTE: During low demand periods when hot water is not
being used, a lower thermostat setting will reduce energy
losses and may satisfy your normal hot water needs. If hot
water use is expected to be more than normal, a higher
thermostat setting may be required to meet the increased
demand. When leaving your home for extended periods
(vacations, etc.) turn the temperature dial to its lowest
setting. This will maintain the water at low temperatures
with minimum energy losses and prevent the tank from
freezing during cold weather.
120°F
Bar
W
A
R
M
T
I
O
U
N
V
S
A
R
O
Y
E
T
T
E
S
R
C
A
U
E
I
N
R
C
J
A
N
I
T
D
L
F
A
S
C
I
O
N
Operational Conditions
Condensation
Moisture from the products of combustion condenses on
the tank surface and the outside jacket of the water heater
and forms drops of water which may fall onto the burner or
other hot surfaces. This will produce a “sizzling” or “frying”
noise. NOTE: This condensation is normal and should not be
confused with a leaking tank. Condensation may increase or
decrease at different times of the year.
High efficient energy saver water heaters will produce
larger amounts of condensation on initial start-up or when
a large amount of hot water is being used. NOTE: Do not
confuse this with a “tank leak”. Once the water reaches a
temperature of 120°F and the tank warms up (usually 1-2
hours), the condensation will stop.
IMPORTANT: It is always recommended that a suitable drain
pan be installed under the water heater to protect the area
from water damage resulting from normal condensation
production, a leaking tank or piping connections. Refer to
Location Requirements. Under no circumstances is the
manufacturer to be held responsible for any water damage in
connection with this water heater.
Water Heater Sounds
During the normal operation of the water heater, sounds or
noises may be heard. These noises are common and may
result from the following:
1. Normal expansion and contraction of metal parts during
periods of heat-up and cool-down.
2. Condensation causes sizzling and popping within the
burner area and should be considered normal.
3. Sediment buildup in the tank bottom will create varying
amounts of noise and may cause premature tank failure.
Drain and flush the tank as directed under “Draining and
Flushing”.
Smoke/Odor
The water heater may give off a small amount of smoke
and odor during the initial start-up of the unit. This is due to
the burning off of oil from metal parts of a new unit and will
disappear after a few minutes of operation.
Safety Shut-off
This water heater is designed to automatically shut-off in the
event of the following:
1. The pilot flame is extinguished for any reason.
2. The water temperature exceeds 180°F (83°C).
3. Excessive combustion chamber temperatures.
4. The ignition of flammable vapors.
A thermocouple is used to determine if a pilot flame is
present, and will shut off the gas supply to the main burner
and the pilot if the flame is absent. This unit is also equipped
with a thermal switch, designed to shut off the gas supply in
the event the water heater has been exposed to flammable
vapors (e.g., spilled gasoline), poor combustion caused by
a blocked vent or insufficient combustion air. If the thermal
switch opens:
1. Check the flame-trap for signs of high temperature (blue
or black discoloration). See Figure 28A.
2. If there are signs of high temperature, inspect your
installation for any problems with venting, combustion
air supply and for a flammable vapor event (see Pilot
Light Troubleshooting Flow Chart). Correct any issues
prior to resetting the thermal switch. Contact the Product
Service and Support Department for service information
at 1-877-817-6750.
3. Reset the thermal switch by depressing the small button
in the center of the thermal switch. Follow the Lighting
Instructions found on the front of your water heater.
A high temperature limit switch or ECO (Energy Cut Off) in
the tank is used to shut off the unit if the water temperature
exceeds 180°F (83°C). The ECO is a single-use switch,
which, if activated, requires complete replacement of the
entire gas control valve/thermostat. If the ECO should
activate, the water heater cannot be used until the gas
control valve/thermostat is replaced by a qualified person.
Contact your local dealer for service information.
Anode Rod/Water Odor
Each water heater contains at least one anode rod, which
will slowly deplete while protecting the glass-lined tank
from corrosion and prolonging the life of the water heater.
Once the anode is depleted, the tank will start to corrode,
eventually developing a leak. Certain water conditions will
cause a reaction between this rod and the water. The most
common complaint associated with the anode rod is a “rotten
egg smell” produced from the presence of hydrogen sulfide
gas dissolved in the water. IMPORTANT: Do not remove
this rod permanently as it will void any warranties. The parts
list includes a special anode that can be ordered if water
odor or discoloration occurs. NOTE: This rod may reduce
but not eliminate water odor problems. The water supply
system may require special filtration equipment from a water
conditioning company to successfully eliminate all water odor
problems.
Artificially softened water is exceedingly corrosive because
the process substitutes sodium ions for magnesium and
calcium ions. The use of a water softener may decrease the
life of the water heater tank.
The anode rod should be removed from the water heater
tank every 3 years for inspection. The following are typical
(but not all) signs of a depleted anode rod:
• The majority of the rods diameter is less than 3/8”.
• Signifi cant sections of the support wire (approx. 1/3 or
more of the anode rod’s length) are visible.
If the anode rod show signs of either or both it should be
replaced. NOTE: Whether re-installing
or replacing the anode rod, check for
any leaks and immediately correct if
found.
In replacing the anode:
1. Turn off gas supply to the water
heater.
2. Shut off the water supply and
open a nearby hot water faucet to
depressurize the water tank.
3. Drain approximately 5 gallons
of water from tank (Refer to
“Draining and Flushing” for proper
procedures). Close drain valve.
4. Remove old anode rod.
5. Use Teflon® tape or approved pipe
sealant on threads and install new
anode rod.
6. Turn on water supply and open
nearby hot water faucet to
purge air from water system. Check for any leaks and
immediately correct any if found.
7. Restart the water heater as directed under “Operating
Your Water Heater.” See the Repair Parts Illustration for
anode rod location.
TEFLON is a registered trademark of E.I. Du Pont De Nemours and Company.
19
MAINTENANCE OF YOUR WATER HEATER
Draining and Flushing
It is recommended that the tank be drained and flushed
every 6 months to remove sediment which may build up
during operation. The water heater should be drained if
being shut down during freezing temperatures. To drain the
tank, perform the following steps:
1. Turn off the gas to the water heater at the manual gas
shut-off valve.
2. Close the cold water inlet valve.
3. Open a nearby hot water faucet.
4. Connect a hose to the drain valve and terminate it to an
adequate drain.
NOTE: The drain hose should be rated for at least 200°F.
If the drain hose does not have this rating, open the cold
water inlet valve and a nearby hot faucet until the water is
no longer hot.
5. Open the water heater drain valve and allow all the
water to drain from the tank. Flush the tank with water
as needed to remove sediment.
6. Close the drain valve, refill the tank, and restart the
heater as directed under “Operating Your Water
Heater”.
If the water heater is going to be shut down for an extended
period, the drain valve should be left open.
IMPORTANT: Condensation may occur when refilling the
tank and should not be confused with a tank leak.
Routine Preventive
Maintenance
At least annually, a visual inspection should be made of
the venting and air supply system, piping systems, main
burner, pilot burner, and flame-trap. Check the water heater
for the following:
• Obstructions, damage, or deterioration in the venting
system. Make sure the ventilation and combustion air
supplies are not obstructed.
• Build up of soot and carbon on the main burner and
pilot burner. Check for a soft blue flame.
• Leaking or damaged water and gas piping.
• Presence of flammable or corrosive materials in the
installation area.
• Presence of combustible materials near the water
heater.
• After servicing this water heater, check to make sure it
is working properly. (See Operating Your Water Heater
section of this manual.)
IMPORTANT: If you lack the necessary skills required to
properly perform this visual inspection, you should not
proceed, but get help from a qualified person.
Temperature and Pressure
Relief Valve
WARNING
Explosion Hazard
If the temperature and pressure relief valve
is dripping or leaking, have a qualified
person replace it.
Examples of a qualified person include:
licensed plumbers, authorized gas company
personnel, and authorized service
personnel.
Do not plug valve.
Do not remove valve.
Failure to follow these instructions can
result in death, or explosion.
Manually operate
the temperature
and pressure relief
valve at least once
a year to make
sure it is working
properly. To prevent
water damage,
the valve must be
properly connected
to a discharge line
which terminates
at an adequate
drain. Standing clear of the outlet (discharged water may
be hot), slowly lift and release the lever handle on the
temperature and pressure relief valve to allow the valve to
operate freely and return to its closed position. If the valve
fails to completely reset and continues to release water,
immediately shut off the manual gas control valve and the
cold water inlet valve and call a qualified person.
Figure 21
Temperature and Pressure
Relief Valve
Manual Relief
Val ve
Discharge line to drain
20
Replacement Parts
IMPORTANT: The following maintenance procedures
are for the Flame Lock™ Safety System components and
should be performed by a qualified person.
Replacement parts may be ordered through your plumber
or the local distributor. Parts will be shipped at prevailing
prices and billed accordingly. When ordering replacement
parts, always have the following information ready:
1. model, serial, and product number
2. type of gas
3. item number
4. parts description
See Repair Parts Section for a list of available repair parts.
Removing the Burner from the
Manifold Assembly
Natural Gas Burner (Low Nox)
1. Take off the burner by removing the two (2) screws located
underneath the burner.
2. Check the burner to see if it is dirty or clogged. The burner
may be cleaned with soap and hot water (Figure 24A).
Connector
Manifold Door
Assembly
Thermal Switch
Igniter Wire
Pilot
Tube
Figure 24A
Natural Gas (Low Nox)
Burner Assembly
Burner
Two Piece Wire
Removing the Manifold Assembly
1. Turn off the gas to the water heater at the manual
shut-off valve (Figure 3).
2. Depress the dial stop and turn the gas control knob on
the combination gas control
valve/thermostat clockwise to
the “OFF” position (Figure 19).
3. Remove the outer door.
4. Remove the two screws
securing the manifold door
assembly to the combustion
chamber (Figure 23).
5. Disconnect the thermocouple
(right-hand thread), pilot
tube, the igniter wire from
the igniter button, the two
connectors attached to
the thermal switch, and
manifold tube at the gas
control valve/thermostat.
(Figures 22 & 23.) NOTE:
L.P. Gas systems use reverse (left-hand) threads on
the manifold tube.
6. Grasp the manifold tube and push down slightly to free
the manifold, pilot tube, and thermocouple.
7. Carefully remove the manifold assembly from the
burner compartment. NOTE: Be sure not to damage
internal parts.
Figure 23
Burner Assembly
Removal
Thermocouple
Manifold
Screw (2)
Manifold
Tube
Viewport
Gas Valve /
Thermostat
U N IT R O L
WARNING
READALL INSTRUCTIONS
BEFORE LIGHTING
T
T
I
U
O
A
H
R
C
O
T
W
B
H
H
R
A
O
E
E
E
T
T
T
R
E
R
R
E
I
T
R
I
C
S
N
S
K
O
H
L
F
A
S
C
A
W
Two Piece Wire
W
A
R
M
O
N
Y
S
R
E
V
S
U
A
A
J
C
N
I
A
D
T
I
O
N
Connector
Figure 22
Right-Hand
Thread
Thermocouple
Manifold Tube
Piezo
Igniter
Button
Dial Stop
U N I T R O L
WARNING
READ ALL INSTRUCTIONS
BEFORE LIGHTING
T
T
I
U
O
A
H
R
C
O
T
W
B
H
H
R
O
A
E
E
E
T
T
T
R
E
A
R
R
E
I
T
R
I
C
N
S
S
K
O
D
H
L
F
A
C
S
A
W
Pilot Tube
Thermal Switch
Manifold
Door
Igniter
Button
W
A
R
M
O
N
Y
S
R
E
V
S
U
A
J
N
C
I
A
T
I
O
N
Igniter
Wire
Pilot
Tube
Thermal
Switch Wires
Manifold
Tube
Pilot
Tube
Thermocouple
Retainer Clip
Pilot Assembly
Manifold
Door
Gasket
Pilot Bracket
Thermocouple
Viewport
Thermocouple
Manifold Door
Assembly
Burner
Pilot Assembly
Manifold
Tube
Screws
L.P. Gas Burner
1. Separate the pilot bracket from the L.P. burner by
removing screw.
2. Loosen set screw located on top of the L.P. burner near
the manifold door. Carefully, pull the burner away from the
manifold door assembly.
3. Check the burner to see if it is dirty or clogged. The burner
may be cleaned with soap and hot water (Figure 24B).
Figure 24B
L.P. Gas Burner
Assembly
Burner
Pilot Assembly
Manifold Door
Gasket
Two Piece Wire
Connector
Screws
Thermocouple
Retainer Clip
Pilot Bracket
Manifold Door
Assembly
Thermal Switch
Viewport
Igniter Wire
Pilot
Tube
Manifold
Tube
Thermocouple
21
Replacing the Thermocouple
1. Remove the manifold assembly as directed previously.
2. Remove the retainer clip from the back of the two piece
wire connector and remove the two piece wire connector from the manifold door (Figure 25).
3. Pull the thermocouple from the pilot assembly (Figure
29).
IMPORTANT: Be careful not to bend or alter the position of
the pilot assembly components.
4. Push the new thermocouple through the holes in the pilot bracket. Insert the thermocouple tube into the holes
provided in the pilot assembly until it clicks into place.
5. Position the new thermocouple through the larger
opening of the two piece wire connector (Figure 25). Be
sure igniter wire is positioned through the small opening of the two piece wire connector.
6. See Replacing the Manifold Assembly.
Figure 25
Two Piece Wire
Connector
Assembly
Thermocouple
Igniter Wire
Other fittings
not shown
for clarity
External Inspection & Cleaning of the
Flame-trap
Although not likely to occur, if debris collects on the flametrap, use a vacuum, compressed air, or a soft bristle brush
to remove it. NOTE: If unable to inspect or clean the flame
trap from underneath, follow the “Cleaning the Combustion
Chamber and Flame-trap” instructions.
Figure 27
Flame-trap visual inspection
Flashlight
Two Piece
Wire Connector
Figure 26
Thermocouple
Assembly
Pilot T ube
Retainer Clip
Manifold
Door
Mirror
Mirror
Cleaning the Combustion Chamber and
Flame-trap
1. Follow procedure outlined in “Removing the Manifold
Assembly”.
2. Use a vacuum cleaner/shop vac to remove all loose
debris in the combustion chamber (Figure 28A). Use
compressed air to clear any dust or debris that may
have accumulated in the flame-trap.
3. Reassemble following the procedure under “Replacing
the Manifold Assembly”.
22
Replacing the Manifold Assembly
WARNING
Explosion Hazard
Tighten both manifold door screws
securely.
Remove any fiberglass between gasket
and combustion chamber.
Replace viewport if glass is missing or
damaged.
Replace two piece wire connector if missing
or removed.
Replace door gasket if damaged.
Failure to follow these instructions can
result in death, explosion, or fire.
1. Check the door gasket for damage or imbedded debris
prior to installation.
9. Check for leaks by brushing on an approved
noncorrosive leak detection solution. Bubbles forming
indicate a leak. Correct any leak found. IMPORTANT:
All leaks must be fixed immediately.
10. Replace the outer door.
Figure 28A
Combustion Chamber
Door Gasket
Figure 28B
Manifold Assembly
Close-up
Flame-trap
Tab
Close-up inside view of
the combustion chamber.
Bracket
Slot
WARNING
Explosion Hazard
Replace viewport if glass is
missing or damaged.
Failure to do so can result in
death, explosion or fire.
2. Inspect the viewport for damage and replace as
required.
3. Insert the manifold assembly into the burner
compartment making sure that the tab of the manifold
tube engages in the slot of the bracket inside the
combustion chamber (Figure 28B).
4. Inspect the door gasket and make sure there is no
fiberglass insulation between the gasket and the
combustion chamber.
5. Replace the two screws, which secure the manifold
assembly door to the combustion chamber and
tighten securely. Once the manifold assembly door is
tightened, visually inspect the door gasket between
the manifold assembly door and the combustion
chamber for spaces or gaps that would prevent a
seal. IMPORTANT: Do not operate the water heater
if the door gasket does not create a seal between the
manifold door and the combustion chamber.
6. Reconnect the two wire leads to the thermal switch, the
manifold tubing, pilot tubing, and thermocouple to the
gas control valve/thermostat. Do not cross-thread or
apply any thread sealant to these fittings.
The thermocouple nut should be started and turned
all the way in by hand. An additional quarter turn
with a 7/16” open-end wrench will then be sufficient
to seat the lockwasher.
7. Reconnect the igniter wire.
8. Turn gas supply on and refer to the Lighting
Instructions.
Bracket
Manifold tube
Tab
Piezoelectric Igniter System
The piezoelectric igniter system consists of the igniter
button, electrode, and wire. The pilot is ignited by an
electric spark generated when the igniter button is pressed.
The spark gap of 0.125 inch is set when the electrode is
installed at the factory. (See Figure 29). Use only factory
authorized piezoelectric igniter parts for replacement.
Electrode
Thermocouple
Pilot
Tip
Electrode
Bracket
.125 *
Pilot
L.P. Gas
Figure 29
Natural Gas & L.P. Gas
Igniter Assemblies
Igniter
Button
Wire
to
electrode
Snap-on Connector
* Note: Spark gap distance measured from electrode tip to pilot.
Pilot
Bracket
Thermocouple
.125 *
Natural Gas
Pilot
Tip
Testing the Igniter System
Turn off the gas to the water heater at the manual gas shutoff valve. Watch the electrode tip while activating the igniter.
A visible spark should jump from the electrode. To avoid
shock, do not touch the burner or any metal part on the
pilot or pilot assembly. If no spark is visible, check the wire
connections and make sure the electrode is not broken.
Replace the igniter if defective. Dirt and rust on the pilot or
electrode tip can prevent the igniter spark. Wipe clean with
a damp cloth and dry completely. Rust can be removed
from the electrode tip and metal surfaces by lightly sanding
with an emery cloth or fine grit sandpaper.
23
Removing and Replacing the Gas
Control Valve/Thermostat
IMPORTANT: The gas control valve/thermostat is a standard
valve with wire leads that connect to a thermal switch.
Removing the Gas Valve:
1. On the gas control valve/thermostat turn the temperature
dial counterclockwise to its lowest setting. Depress the
dial stop and turn the gas control knob clockwise to the
“OFF” position (Figure 19).
2. Turn off the gas at the manual shut-off valve on the gas
supply pipe (Figure 3).
3. Drain the water heater. Refer to the section of Draining
and Flushing and follow the procedure.
4. Disconnect the igniter wire from the igniter button.
Remove the igniter button by depressing front and rear
holding tabs and lift. Remove igniter bracket. Disconnect
the thermocouple (right-hand threads), pilot tube, two
wire leads at the thermal switch, and manifold tube at
the gas control valve/thermostat (Figure 22). NOTE:
L.P. gas systems use reverse (left-hand) threads on the
manifold tube.
5. Refer to “Gas Piping” (Figure 3) and disconnect the
ground joint union in the gas piping. Disconnect the
remaining pipe from the gas control valve/thermostat.
6. To remove the gas valve, thread a correctly sized
pipe into the inlet and use it to turn the gas valve
(counterclockwise.) Do not use pipe wrench or
equivalent to grip body. Damage may result, causing
leaks. Do not insert any sharp objects into the inlet or
outlet connections. Damage to the gas valve may result.
Replacing the Gas Valve:
To replace the gas control valve/thermostat, reassemble in
reverse order. This water heater has a resettable thermal
switch installed. DO NOT attempt to disable or modify this
feature in any way. When replacing the gas valve, thread a
correctly sized pipe into the inlet and use it to turn the gas
valve (clockwise.) DO NOT OVER TIGHTEN, damage may
result.
• Be sure to use approved Teflon
compound on the gas piping connections and fitting on
the back of the gas control valve that screws into tank.
• Be sure to remove the pilot ferrule nut from the new gas
control valve/thermostat.
• Turn the gas supply on and check for leaks. Test all
connections by brushing on an approved noncorrosive
leak-detection solution. Bubbles will show a leak.
Correct any leak found.
• Be sure tank is completely filled with water before
lighting and activating the water heater. Follow the
Lighting Instructions.
• If additional information is required, contact the Service
Department at: 1-877-817-6750.
TEFLON is a registered trademark of E.I. Du Pont De Nemours and Company.
Flame Lock™ Safety System Operational Checklist
1. Manifold gasket properly sealed.
2. Viewport not damaged or cracked.
3. Flame-trap free of debris and undamaged.
4. Two piece wire connector properly installed.
5. No leaks at pilot and manifold connection.
6. Manifold door screws securely tightened.
7. Depress the button on the thermal switch.
®
tape or pipe joint
TROUBLESHOOTING CHART
PROBLEMPOSSIBLE CAUSE(S)CORRECTIVE ACTION
BURNER WILL NOT IGNITE1. Pilot not lit
SMELLY WATER1. Sulfides in the water1. Replace the anode with a special anode
BURNER FLAME YELLOWLAZY
PILOT WILL NOT LIGHT OR
REMAIN LIT
2. Thermostat set too low
3. No gas
4. Dirt in the gas lines
5. Pilot line clogged
6. Main burner line clogged
7. Non-functioning thermocouple
8. Non-functioning thermostat
9. Heater installed in a confined area
1. Insufficient secondary air
2. Low gas pressure
3. Flue clogged
4. Main burner line clogged
5. Heater installed in a confined area
6. Obstruction in main burner orifice
1. Non-functioning igniter
2. The thermal switch tripped
3. Thermocouple connection loose
4. Air in gas line
5. Low gas pressure
6. No gas
7. Dirt in gas lines
8. Cold drafts
9. Thermostat ECO switch open
10. Pilot line or orifice clogged
11. Non-functioning thermocouple
12. Air for combustion obstructed
13. Flammable vapors incident, Flame Lock
function utilized
24
1. Light pilot
2. Turn temp. dial to desired temperature
3. Check with gas utility company
4. Notify utility-install trap in gas line
5. Clean, locate source and correct
6. Clean, locate source and correct
7. Replace thermocouple
8. Replace thermostat
9. Provide fresh air ventilation
1. Provide ventilation to water heater
2. Check with gas utility company
3. Clean, locate source and correct
4. Clean, locate source and correct
5. Proper fresh air ventilation
6. Clean or replace orifice
1. Replace igniter pilot assembly
2. See Pilot Light Troubleshooting Flowchart
section
3. Finger tighten; then 1/4 turn with wrench
4. Bleed the air from the gas line
5. Check with gas utility company
6. Check with gas utility company
7. Notify utility-install dirt trap in gas line
8. Locate source and correct
9. Replace thermostat
10. Clean, locate source and correct
11. Replace thermocouple
12. See maintenance section for inspection and
™
cleaning of flame trap
13. Replace water heater, eliminate flammable
vapors source. Call 1-877-817-6750
PROBLEMPOSSIBLE CAUSE(S)CORRECTIVE ACTION
HIGH OPERATION COSTS1. Thermostat set too high
INSUFFICIENT HOT WATER 1. Thermostat set too low
SLOW HOT WATER
RECOVERY
DRIP FROM RELIEF VALVE1. Excessive water pressure
THERMOSTAT FAILS TO
SHUT-OFF
COMBUSTION ODORS1. Insufficient secondary air
SMOKING AND CARBON
FORMATION (SOOTING)
CONDENSATION1. Temperature setting too low1. Increase the temperature setting
BURNER FLAME FLOATS
AND LIFTS OFF PORTS
BURNER FLAME TOO HIGH 1. Orifice too large1. Replace with correct orifice
FLAME BURNS AT ORIFICE1. Thermostat not functioning properly
PILOT FLAME
TOO SMALL
2. Sediment or lime in tank
3. Water heater too small for job
4. Wrong piping connections
5. Leaking faucets
6. Gas leaks
7. Wasted hot water
8. Long runs of exposed piping
9. Hot water piping in exposed wall
2. Sediment or lime in tank
3. Water heater too small
4. Wrong piping connections
5. Leaking faucets
6. Wasted hot water
7. Long runs of exposed piping
8. Hot water piping in outside wall
9. Low gas pressure
1. Insufficient secondary air
2. Flue clogged
3. Low gas pressure
4. Improper calibration
5. Thermostat set too low
6. Water heater too small
7. Wrong piping connections
8. Wasted hot water
2. Heater stacking
3. Closed water system
1. Thermostat not functioning properly
2. Improper calibration
2. Flue clogged
3. Heater installed in a confined area
1. Insufficient secondary air
2. Low gas pressure
3. Flue clogged
4. Thermostat not functioning properly
5. Heater installed in a confined area
6. Burner flame yellow-lazy
1. Orifice too large
2. High gas pressure
3. Flue clogged
4. Cold drafts
2. Low gas pressure
1. Pilot line or orifice clogged
2. Low gas pressure
1. Set temperature dial to lower setting
2. Drain/flush-provide water treatment if needed
3. Install adequate heater
4. Correct piping-dip tube must be in cold inlet
5. Repair faucets
6. Check with utility-repair at once
7. Advise customer
8. Insulate piping
9. Insulate piping
1. Turn temperature dial to desired setting
2. Drain/flush-provide water treatment if needed
3. Install adequate heater
4. Correct piping-dip tube must be in cold inlet
5 Repair faucets
6. Advise customer
7. Insulate piping
8. Insulate piping
9. Check with gas utility company
1. Provide ventilation to water heater. Check flue
way, flue baffle, and burner
2. Clean flue, locate source and correct
3. Check with gas utility company
4. Replace thermostat
5. Turn temperature dial to desired setting
6. Install adequate heater
7. Correct piping-dip tube must be in cold inlet
8. Advise customer
1. Use a pressure reducing valve and relief valve
2. Lower the thermostat setting
3. See “Closed System/Thermal Expansion”
1. Replace thermostat
2. Replace thermostat
1. Provide ventilation to water heater. Check flue
way, flue baffle, and burner
2. Clean, locate source and correct
3. Provide fresh air ventilation
1. Provide ventilation to water heater. Check flue
way, flue baffle, burner
2. Check with gas utility company
3. Clean, locate source and correct
4. Replace thermostat
5. Provide fresh air ventilation
6. See “Burner Flame Yellow-Lazy”
1. Replace with correct orifice
2. Check with gas utility company
3. Clean flue and burner-locate source and correct
4. Locate source and correct
1. Replace thermostat
2. Check with gas utility company
1. Clean, locate source and correct
2. Check with gas utility company
25
PILOT LIGHT TROUBLESHOOTING FLOWCHART
Does pilot light go out
when button is released?
Check Draft. (See Checking the
NO
Draft section of this manual.)
YES
Has the thermal switch
tripped?
YES
Are the wires from the gas
NO
control valve/thermostat firmly
connected to the switch?
Are the wires damaged
and/or frayed?
Check for insufficient
combustion air.
Are there openings
for make-up air to
enter the room?
Install correct size make-up air openings
NO
per the Combustion Air Supply and
Ventilation section in this manual.
Replace the gas control
valve/thermostat.
YES
Are the openings of sufficient size?
See Combustion Air Supply and Ventilation
section in this manual for requirements.
YES
YES
YES
Correct size of openings
NO
to allow sufficient air.
Secure connections
NO
and attempt a relight.
Is the thermocouple
NO
connection loose?
Tighten the connection
Does the thermocouple pass the test?
YES
YES
Test the thermocouple using the following
procedure: Disconnect the thermocouple
from the gas control valve/thermostat. Using
a multimeter with alligator clip leads, attach
the red lead to the body (copper part) of
the thermocouple. Attach the black lead to
the end (silver part) of the thermocouple
that connects to the gas control valve/
NO
thermostat. Follow the instruction to light
the pilot and watch the voltage readings on
the multimeter. After 45 seconds the meter
should read 12 millivolts DC or more.
Replace the thermocouple.
NO
Is there a furnace/air
handler in the same room
NO
as the water heater?
YES
Does the return air duct for the furnace/air handler
draw its air from a separate location than the water
heater? See the Location Requirements section
NO
and the Combustion Air Supply section.
YES
Is there proper drafting at the
drafthood? See Checking the
Draft section in this manual.
Check the vent system for restrictions/obstructions and check
the vent termination height. Refer to the Installation Instructions
NO
section of this manual for specific requirements.
YES
Is the flame-trap free from
debris due to excessive lint,
dirt, dust or oil?
Refer to the Use & Care Guide section of this manual for
NO
information on cleaning the flame-trap.
YES
Check the water heater for a Flammable Vapor (FV) event. Note: it may
be necessary to remove the manifold door assembly to visually inspect
the water heater. Reference the Maintenance of your Water Heater
section of this manual for removal instructions.
Is the igniter wire insulation burnt or
show signs of discoloration?
YES
NO
Is the pilot tube
damaged?
YES
Contact a local Heating, Ventilation, AirConditioning & Refrigeration authorized
service provider.
Does the flametrap show signs
NO
of discoloration
and/or debris?
YES
U N IT R O L
WARNING
READALL INSTRUCTIONS
BEFORE LIGHTING
W
A
R
M
T
T
I
U
O
O
A
H
N
R
C
O
T
Y
W
B
H
S
H
R
R
A
O
E
E
E
E
T
T
V
T
S
R
U
E
A
R
A
J
R
E
I
T
R
I
C
N
C
S
N
S
I
K
A
O
D
T
H
L
F
A
S
C
A
I
O
W
N
N
Thermal
Switch
26
Shut-off the gas supply to the water
heater at the manual gas shut-off
valve, then contact Customer Service
at: 1-877-817-6750.
REPAIR PARTS ILLUSTRATION
5
Alternate anode
location for top
T&P
Anode location
for side T&P
8
When ordering repair parts always give the following
information:
1. Model, serial, and product number
2. Type of gas
3. Item number
4. Parts description
Repair Parts List
Item
No.
1DRAFTHOOD
2REDUCER RING - SOME MODELS
3FLUE BAFFLE
4HEAT TRAP (COLD) - SOME MODELS
5HEAT TRAP (HOT) - SOME MODELS
6COLD WATER DIP TUBE
7ANODE ROD
8TEMPERATURE & PRESSURE RELIEF VALVE
(LOCATED TOP OR SIDE)
9DRAIN VALVE
10GAS CONTROL VALVE/THERMOSTAT
11OUTER DOOR
12*PILOT ASSEMBLY KIT (Natural Gas)
13*PILOT ASSEMBLY KIT (L.P. Gas)
14*BURNER (Natural Gas/Low Nox)
15*BURNER (L.P. Gas/Low Nox)
16*MANIFOLD DOOR ASSEMBLY (Natural Gas/Low Nox)
17*MANIFOLD DOOR ASSEMBLY (L.P. Gas)
18*TWO PIECE WIRE CONNECTOR
WITH RETAINER CLIP
19*MANIFOLD DOOR GASKET
20*VIEWPORT ASSEMBLY
21*PIEZOELECTRIC IGNITER BUTTON
22*THERMOCOUPLE
*Pictured on next page.
Parts Description
(with wire leads)
LEGEND
Special anode rod (see Anode Rod/Water Odor
section)
Temperature and Pressure Relief Valve is required,
but may not be factory installed
Unique: Flame Lock™ Safety System parts
10
4
11
1
6
7
9
2
3
27
Listed Parts Kits and Illustrations
Item 12: Pilot assembly kit, which contains the pilot assembly, igniter electrode and retainer clip (Natural Gas)
Item 13: Pilot assembly kit, which contains the pilot assembly, igniter electrode and retainer clip (L.P. Gas)
Item 14: Burner (Natural Gas/Low Nox)
Item 15: Burner (L.P. Gas)
Item 16: Manifold door assembly which contains the manifold tube, gasket, door, pilot tube, thermocouple, two piece wire
connector with retainer clip, thermal switch, and pilot assembly. (Natural Gas/Low Nox)
Item 17: Manifold door assembly which contains the manifold tube, gasket, door, pilot tube, thermocouple, two piece wire
connector with retainer clip, thermal switch, and pilot assembly. (L.P. Gas)
Item 18: Contains two piece wire connector and retainer clip