273 Branchport Ave.
Long Branch, N.J. 07740 Thank you for using our products.
(800) 631-2148
www.wheelockinc.com INSTALLATION INSTRUCTIONS
SERIES RSSR STROBE APPLIANCES
Use this product according to this instruction manual. Please keep this instruction manual for future reference.
GENERAL:
Wheelock’s Series RSSR Strobes can provide a non-synchronized strobe appliance when connected directly to a fire alarm control panel (FACP), or provide a
synchronized strobe appliance when used in conjunction with a Sync Module (SM), Dual Sync Module (DSM) or Wheelock’s PS-12/24-8 Power Supply with
patented sync protocol. The RSSR Strobe appliances are UL Listed under Standard 1638 for Emergency Devices. The RSSR-2415C, RSSR-2475C and RSSR24110C strobes are intended for ceiling mount only
backboxes specified in these instructions (See Mounting Options). The RSSR models have an integrated strobe mounting plate (SMP) that can be mounted to a
single-gang, double-gang, 4” backbox, 100mm European backbox or SHBB surface backbox. The strobe uses a xenon flashtube with solid state circuitry
enclosed in a polycarbonate lens to provide maximum visibility and reliability for effective visible signaling. All inputs are polarized for compatibility with
standard reverse polarity supervision of circuit wiring by an FACP.
WARNING: PLEASE READ THESE INSTRUCTIONS CAREFULLY. FAILURE TO COMPLY WITH ANY OF THE FOLLOWING
INSTRUCTIONS, CAUTIONS AND WARNINGS COULD RESULT IN IMPROPER APPLICATION, INSTALLATION AND/OR OPERATION OF
THESE PRODUCTS IN AN EMERGENCY SITUATION, WHICH COULD RESULT IN PROPERTY DAMAGE AND SERIOUS INJURY OR
DEATH TO YOU AND/OR OTHERS.
SPECIFICATIONS:
Model
RSSR-2415C 24 16.0-33.0 15 A,B,C,D
RSSR-2415W 24 16.0-33.0 15 A,B,C,D
RSSR-2475C 24 16.0-33.0 75 A,B,C,D
RSSR-2475W 24 16.0-33.0 75 A,B,C,D
RSSR-24110C 24 16.0-33.0 110 A,B,C,D
RSSR-24110W 24 16.0-33.0 110 A,B,C,D
NOTES:
1. Strobes will produce 1 flash per second over the “Regulated Voltage” range.
2. All models are for indoor use with a temperature range of +32°F to +120°F (0°C to +49°C) and maximum humidity of 85% RH. The effect of shipping
and storage temperatures shall not adversely affect the performance of the appliance when it is stored in the original cartons and is not subjected to misuse
or abuse.
A4
A2
A7
A5
A1
A6
A3
When calculating the total currents use Table 3 to determine the highest value of RMS current for an individual strobe, then multiply these values by the total number of
strobes. Be sure to add the currents for any other appliances, including audible signaling appliances powered by the same source, and to include any required safety
factors.
NOTE: The maximum number of strobes on a single notification appliance circuit shall not exceed 50.
UL Voltage 2415C/W 2475C/W 24110C/W
DC 16-33VDC 0.090 0.315 0.420
FWR 16-33VRMS 0.145 0.480 0.645
and the RSSR-2415W, RSSR-2475W and RSSR-24110W strobes are intended for wall mount only, with the
Table 1: UL Models and Ratings
Regulated
Voltage
(VDC/VRMS)
Model Rated
RSSR-2415C 15.0cd 15 1.3 1.3 1.2 1.2 0.7
RSSR-2415W 15.0cd 15 1.3 1.3 1.2 1.2 0.7
RSSR-2475C 75.0cd 75 6.7 6.7 6.2 6.2 3.3
RSSR-2475W 75.0cd 75 6.7 6.7 6.2 6.2 3.3
RSSR-24110C 110.0cd 110 9.8 9.8 9.1 9.1 4.8
RSSR-24110W 110.0cd 110 9.8 9.8 9.1 9.1 4.8
Table 3: UL Current Ratings (AMPS)
Maximum RMS Current Draw
Voltage
Range
Strobe Candela
(cd)
Mounting
Options
(VDC/VRMS)
Table 2: Candela at Various Angles Per UL 1638
Candela
A1 A2 A3 A4 A5 A6/A7
CAUTION: These notification appliances are UL Listed as “Regulated”. They are intended to be used with FACPs whose notification circuits are UL Listed as
“Regulated.” These appliances shall not be used on UL Listed “Special Application” notification circuits unless the appliances are identified to be compatible in the
installation instructions of the FACP or unless the FACP is identified to be compatible in this instruction manual.
WARNING: THESE APPLIANCES WERE TESTED TO THE REGULATED VOLTAGE LIMITS OF 16.0-33.0 VOLTS FOR 24V MODELS USING
FILTERED DC OR UNFILTERED FULL-WAVE-RECTIFIED VOLTAGE. DO NOT APPLY VOLTAGE OUTSIDE OF THIS RANGE.
Copyright 2005 Wheelock, Inc. All rights reserved. P83884 J
Sheet 1 of 4
WARNING: CHECK THE MINIMUM AND MAXIMUM OUTPUT OF THE POWER SUPPLY AND STANDBY BATTERY AND SUBTRACT THE
VOLTAGE DROP FROM THE CIRCUIT WIRING RESISTANCE TO DETERMINE THE APPPLIED VOLTAGE TO THE STROBES. THE MAXIMUM
WIRE IMPEDANCE BETWEEN STROBES SHALL NOT EXCEED 35 OHMS.
CAUTION: Strobes are not designed to be used on coded systems in which the applied voltage is cycled on and off.
WARNING: MAKE SURE THAT THE TOTAL RMS CURRENT REQUIRED BY ALL APPLIANCES THAT ARE CONNECTED TO THE
SYSTEM’S PRIMARY AND SECONDARY POWER SOURCES, NOTIFICATION APPLICIANCE CIRCUITS, SM, DSM SYNC MODULES, OR
WHEELOCK POWER SUPPLIES DOES NOT EXCEED THE POWER SOURCES’ RATED CAPACITY OR THE CURRENT RATINGS OF ANY FUSES
ON THE CIRCUITS TO WHICH THESE APPLIANCES ARE WIRED. OVERLOADING POWER SOURCES OR EXCEEDING FUSE RATINGS
COULD RESULT IN LOSS OF POWER AND FAILURE TO ALERT OCCUPANTS DURING AN EMERGENCY, WHICH COULD RESULT IN
PROPERTY DAMAGE AND SERIOUS INJURY OR DEATH TO YOU AND/OR OTHERS.
WIRING AND MOUNTING INFORMATION:
CAUTION: The following figures (A-F) show the maximum number of field wires (conductors) that can enter the backbox used with each mounting option. If
these limits are exceeded, there may be insufficient space in the backbox to accommodate the field wires and stresses from the wires could damage the product.
CAUTION: Check that the installed product will have sufficient clearance and wiring room prior to installing backboxes and conduit, especially if sheathed
multiconductor cable or 3/4" conduit fittings are used.
Although the limits shown for each mounting option comply with the National Electrical Code (NEC), Wheelock recommends use of the largest backbox option shown
and the use of approved stranded field wires, whenever possible, to provide additional wiring room for easy installation and minimum stress on the product from wiring.
A
FLUSH MOUNTING
STD. SINGLE-GANG
BACKBOX 2" DEEP
B
#6-32 SCREWS
FLUSH OR SURFACE MOUNT
4" SQ. X 1-1/2" DEEP BACKBOX
OR 100mm X 37. 5mm
EUROPEAN BACKBOX
STROBE MOUNTING
PLATE
#8-32 SCREWS
STROBE MOUNTING
PLATE
BEAUTY PLATE
MAXIMUM NUMBER OF CONDUCTORS
AWG #18 AWG #16 AWG #14 AWG # 12
4 4 4 4
BEAUTY PLATE
MAXIMUM NUMBER OF CONDUCTORS
AWG #18 AWG #16 AWG #14 AWG # 12
4 4 4 4
C
FLUSH OR SURFACE MOUNT
DOUBLE-GANG X 2-1/4"
DEEP BACKBOX
STROBE MOUNTING
PLATE
BEAUTY PLATE
MAXIMUM NUMBER OF CONDUCTORS
AWG #18 AWG #16 AWG #14 AWG #12
4 4 4 4
D
#6-32 SCREWS
SURFACE MOUNTING
STROBE MOUNTING
E
T
A
L
SHALLOW SURFACE
BACKBOX SHBB
BEAUTY PLATE
MAXIMUM NUMBER OF CONDUCTORS
AWG #18 AWG #16 AWG #14 AWG # 12
4 4 4 4
P
#8-32 SCREWS
P83884 J
Sheet 2 of 4