273 Branchport Ave.
Long Branch, N.J. 07740
(800) 631-2148 Thank you for using our products.
www.wheelockinc.com
INSTALLATION INSTRUCTIONS
SERIES RSS AND RSSP STROBE APPLIANCES
(WALL MOUNT VERSIONS)
Use this product according to this instruction manual. Please keep this instruction manual for future reference.
GENERAL:
Wheelock’s Series RSS and RSSP Strobes can provide a non-synchronized strobe appliance when connected directly to a Fire Alarm
Control Panel (FACP), or provide a synchronized strobe appliance when used in conjunction with a Sync Module (SM), Dual Sync
Module (DSM) or Power Supply (PS-12/24-8). The Series RSS and RSSP Strobe Appliances are UL Listed under Standard 1971
(Signaling Devices for the Hearing Impaired) for indoor fire protection service. These Strobes are listed for wall mount only,
with the
backboxes specified in these instructions (See Mounting Options). RSS models have an integrated Strobe Mounting Plate (SMP) that
can be mounted to a single-gang, double-gang, 4” backbox, 100mm European backbox or SHBB surface backbox. The strobes use a
Xenon flashtube with solid state circuitry enclosed in a rugged Lexan lens to provide maximum visibility and reliability for effective
visible signaling. All inputs are polarized for compatibility with standard reverse polarity supervision of circuit wiring by the FACP.
NOTE: All CAUTIONS and WARNINGS are identified by the symbol
WARNING: THE RSS STROBE APPLIANCE IS A "FIRE ALARM DEVICE - DO NOT PAINT."
. All warnings are printed in bold capital letters.
WARNING: READ THESE INSTRUCTIONS CAREFULLY. FAILURE TO COMPLY WITH ANY OF THE
FOLLOWING INSTRUCTIONS, CAUTIONS AND WARNINGS COULD RESULT IN IMPROPER APPLICATION,
INSTALLATION AND/OR OPERATION OF THESE PRODUCTS IN AN EMERGENCY SITUATION, WHICH COULD
RESULT IN PROPERTY DAMAGE AND SERIOUS INJURY OR DEATH TO YOU AND/OR OTHERS.
SPECIFICATIONS:
Table 1: Ratings Per UL 1971
Model
RSS-2415W 24 16.0-33.0 15 A,B,C,D
RSSP-2415W 24 16.0-33.0 15 E,F
RSS-2430W 24 16.0-33.0 30 A,B,C,D
RSSP-2430W 24 16.0-33.0 30 E,F
RSS-2475W 24 16.0-33.0 75 A,B,C,D
RSSP-2475W 24 16.0-33.0 75 E,F
RSS-24110W 24 16.0-33.0 110 A,B,C,D
RSSP-24110W 24 16.0-33.0 110 E,F
RSS-1215W 12 8.0-17.5 15 A,B,C,D
RSSP-1215W 12 8.0-17.5 15 E,F
Regulated
Voltage
VDC/VRMS
Voltage
Range Limit
VDC/VRMS
Strobe
Candela
(CD)
Mounting
Options
Product Series
Multitone Appliances AMT, MT, MT4
Motor Bells MB-G6/G10
Speakers
Chimes CH70
NOTES:
1. Strobes will produce 1 flash per second over the “Regulated
Voltage” range.
2. All models are UL Listed for indoor use with a temperature
range of +32
humidity of 85% RH.
Audibles/Speakers for RSSP Strobe/Plate
o
F to +120oF (0oC to +49oC) and maximum
Table 1A.
ET-1010/1070/1080, ET70,
E7025/7070, E70
NOTE: THE MAXIMUM WIRE IMPEDANCE BETWEEN STROBES SHALL NOT EXCEED 35 OHMS. THE
MAXIMUM NUMBER OF STROBES ON A SINGLE NOTIFICATION APPLIANCE CIRCUIT SHALL NOT EXCEED 47.
WARNING: THESE APPLIANCES WERE TESTED TO THE OPERATING VOLTAGE LIMITS OF 16-33 VOLTS
FOR 24V MODELS AND 8-17.5 VOLTS FOR 12V MODELS USING FILTERED (DC) OR UNFILTERED FULL-WAVE
RECTIFIED (FWR). DO NOT APPLY 80% AND 110% OF THESE VOLTAGE VALUES FOR SYSTEM OPERATION.
WARNING: CHECK THE MINIMUM AND MAXIMUM OUTPUT OF THE POWER SUPPLY AND STANDBY
BATTERY AND SUBTRACT THE VOLTAGE DROP FROM THE CIRCUIT WIRING RESISTANCE TO DETERMINE
THE APPLIED VOLTAGE TO THE STROBES.
Copyright 2001 Wheelock, Inc. All rights reserved.
P84022 F
Sheet 1 of 6
Table 2A: Current Ratings (AMPS) for 24VDC Models
Rated Average Current
Voltage 2415W 2430W 2475W 24110W
MEAN RMS MEAN RMS MEAN RMS MEAN RMS
16.0VDC 0.072 0.090 0.125 0.143 0.215 0.257 0.276 0.327
24.0VDC 0.053 0.079 0.085 0.113 0.140 0.200 0.169 0.256
33.0VDC 0.045 0.072 0.069 0.103 0.114 0.174 0.138 0.228
16.0VRMS ----- 0.105 ----- 0.141 ----- 0.262 ----- 0.330
24.0VRMS ----- 0.076 ----- 0.121 ----- 0.211 ----- 0.262
33.0VRMS ----- 0.070 ----- 0.105 ----- 0.185 ----- 0.229
Rated Peak Current *
Voltage 2415W 2430W 2475W 24110W
16.0VDC 0.185 0.264 0.456 0.584
24.0VDC 0.190 0.269 0.470 0.586
33.0VDC 0.195 0.274 0.474 0.596
16.0VRMS 0.182 0.259 0.458 0.586
24.0VRMS 0.185 0.268 0.472 0.590
33.0VRMS 0.197 0.286 0.492 0.596
Rated Inrush Current **
Voltage 2415W 2430W 2475W 24110W
16.0VDC 0.110 0.110 0.110 0.110
24.0VDC 0.165 0.165 0.165 0.165
33.0VDC 0.230 0.230 0.230 0.230
16.0VRMS 0.155 0.155 0.155 0.155
24.0VRMS 0.235 0.235 0.235 0.235
33.0VRMS 0.325 0.325 0.325 0.325
Table 2B: Current Ratings (AMPS) for 12VDC Models
Rated Average Current
Voltage 1215W
MEAN RMS
8.0VDC 0.220 0.246
12.0VDC 0.129 0.187
17.5VDC 0.099 0.163
8.0VRMS ----- 0.246
12.0VRMS ----- 0.198
17.5VRMS ----- 0.170
Rated Peak Current *
Voltage 1215W
8.0VDC 0.410
12.0VDC 0.426
17.5VDC 0.438
8.0VRMS 0.414
12.0VRMS 0.426
17.5VRMS 0.444
Rated Inrush Current **
Voltage 1215W
8.0VDC 0.081
12.0VDC 0.100
17.5VDC 0.145
8.0VRMS 0.098
12.0VRMS 0.140
17.5VRMS 0.190
* Rated average current is measured using mean value. ** The time duration for the peak current is 100 microseconds.
*** The time duration for the inrush current is 4 milliseconds.
WARNING: MAKE SURE THAT THE TOTAL AVERAGE CURRENT, TOTAL PEAK CURRENT AND TOTAL INRUSH CURRENT
REQUIRED BY ALL APPLIANCES THAT ARE CONNECTED TO THE SYSTEM’S PRIMARY AND SECONDARY POWER SOURCES, NAC
CIRCUITS, SM, DSM SYNC MODULES OR PS-12/24-8 POWER SUPPLY DO NOT EXCEED THE POWER SOURCES’ RATED CAPACITY
OR THE CURRENT RATINGS OF ANY FUSES ON THE CIRCUITS TO WHICH THESE APPLIANCES ARE WIRED. OVERLOADING
POWER SOURCES OR EXCEEDING FUSE RATINGS COULD RESULT IN LOSS OF POWER AND FAILURE TO ALERT OCCUPANTS
DURING AN EMERGENCY, WHICH COULD RESULT IN PROPERTY DAMAGE AND SERIOUS INJURY OR DEATH TO YOU AND/OR
OTHERS.
P84022 F
Sheet 2 of 6