wheelock PSC-2420 INSTALLATION INSTRUCTIONS

273 Branchport Avenue Long Branch, NJ 07740 Thank you for using our products. (732) 222-6880
INSTALLATION INSTRUCTIONS
MODEL PSC-2420-B AND PSC-2420-R
Use this product according to this instruction manual. Please keep this instruction manual for future reference.
DESCRIPTION:
The PSC-2420 is a special application 20 Amp, 24VDC Power Supply Battery Charger Unit. It is UL Listed under Standard 1481, Power Supplies for Fire Protective Equipment, and is used to power the Dual Circuit SAFEPATH. Refer to the Dual Circuit SAFEPATH Operation and Installation Manual for further information.
NOTE: All CAUTIONS and WARNINGS are identified by the symbol
. All warnings are printed in bold capital letters.
WARNING: QUALIFIED PERSONNEL MUST TEST THE SAFEPATH PANEL AFTER THE POWER SUPPLY MODULE HAS BEEN INSTALLED AND BEFORE THE SAFEPATH PANEL IS PLACED IN SERVICE IN ACCORDANCE WITH THE INSTRUCTIONS IN THE SAFEPATH OPERATION AND INSTALLATION MANUAL. FAILURE TO TEST THE SAFEPATH PANEL OR CORRECT ANY TROUBLE CONDITION BEFORE THE SAFEPATH PANEL IS PLACED IN SERVICE COULD RESULT IN A MESSAGE NOT BEING PLAYED WHEN AND WHERE REQUIRED IN AN EMERGENCY SITUATION. THIS COULD RESULT IN PROPERTY DAMAGE AND SERIOUS INJURY OR DEATH TO YOU AND/OR OTHERS.
SPECIFICATIONS:
Mechanical
Dimensions (H x W x D) 21 x 16 x 6 in.
Weight 40 lb.
Finish Black or red
Enclosure Construction Type 0.050” steel
Mounting Indoor surface mount
Wiring Entry Top and bottom knockouts (3/4”, 1”)
Door Lock Standard Wheelock key-lock
PC Boards Power Supply
Environmental
Operating Temperature 0 to 49 °C (32 to 120 °F)
Storage Temperature -20 to 70 °C (-4 to 158 °F)
Humidity, Non-condensing
Copyright 1997, 1998 Wheelock, Inc. All rights reserved.
Electrical (Power Supply)
Battery Charger Fuse Block
85±5% @ 30±2 °C (86 ± 4 °F)
P83572 C
Sheet 1 of 8
Input Parameters
Supply Voltage (Nominal) 120VAC Supply Voltage Absolute Minimum 102VAC Supply Voltage Absolute Maximum 132VAC Input Frequency
60 ± 1Hz Input Current at 120VAC, 20A 10AAC Max Input Power at 120VAC, 20A 900W Efficiency at 120VAC, 20A Power Factor at 120VAC, 20A
87.6 ± 1.75% .75 ± .015
Output Parameters
Output Power at 50o C Natural Convection Cooling 500W Output Voltage at 120VAC, No Load
24.2 ± VDC Total Regulation, Over Temperature Range 1.5% Min Load Regulation .25% Min Line Regulation .10% Min Ripple and Noise 2% Max Peak to Peak Temperature Coefficient -.01%/Degree C Transient Response at 25 Ohm to 1.15 Ohm Load 2% for 10mS Max
Electrical (Battery Charger)
Line Input Voltage, Nominal 120VAC Line Input Voltage, Minimum 102VAC Line Input Voltage, Maximum 132VAC Line Input Frequency Line Input Current at 120VAC 10AAC Max Power Supply Input Voltage, Nominal 24VDC Power Supply Input Voltage, Minimum 20.4VDC Power Supply Input Voltage, Maximum 26.4VDC Power Supply Input Current at 24VDC, Standby Power Supply Input Current at 24VDC, Float Charge State 1A Max DC Power Supply Input Current at 24VDC, Bulk Charge State
Battery Charge Enable Voltage Battery Float State Voltage Battery Float State Voltage, 0o C to 65o C Battery Overcharge Voltage Battery Overcharge Termination Current Battery Bulk Charge Rate at Vbat=26VDC Battery Open Circuit Voltage Battery Short Circuit Current Battery Low Detect Voltage Battery Open Detect Voltage Battery Capacity 24 to 60 AH’s Battery Type Sealed Lead Acid Battery Charge Time, 24 AH’s 19 Hrs Max Battery Charge Time, 38 AH’s 30 Hrs Max Battery Charge Time, 48 AH’s 38 Hrs Max Battery Charge Time, 60 AH’s 48 Hrs Max
Trouble Output Sink Current at .2V
Relay Delay, Turn On 25 to 100mS Relay Delay, Turn Off 250 to 400mS Relay Switching Time, Turn On 5 to 40mS Relay Switching Time, Turn Off 5 to 40mS
INSTALLATION
Location
:
CAUTION: The maximum current of all output circuits must not exceed 20A.
Input Parameters
60Hz ± 1Hz
40 ± 4mADC
3.7 ± .56ADC
Output Parameters
20 ± .5VDC
27.34 ± .27VDC
V(Float)=(28.83-.047T) ± 2.5%
28.92 ± .29VDC
469 ± 188mADC
2.57 ± .39ADC
37.57 ± 1.88VDC 20 ± 2mADC
20.03 ± .50VDC
30.80 ± .77VDC
120 ± 12mADC
P83572 C
Sheet 2 of 8
This panel shall be mounted in a location within the environmental limits specified in the latest UL Standard 864 for indoor
control panels. The panel shall not be located in a hazardous area.
CAUTION
: In order to comply with the latest NFPA and UL requirements for interconnection of fire alarm control equipment, this panel must be located in the same room as, and within 20 feet of, listed compatible units with the wiring enclosed in conduit and properly connected to such control panel.
Procedure
1. See Figure 1 for mounting hole layout.
2. Drill mounting holes for appropriate screws and anchors to ensure secure mounting to the type of surface at the selected location.
3. Prevent dust and dirt contamination of the panel during installation. This contamination can interfere with the operation and reduce the life of the equipment.
4. Open the door. Mount the panel.
14.00"
GROUND TERMINALS
17.00"
CONDUIT ENTRANCES (TYP. TOP & BOTTOM)
14.00"
Figure 1.
Panel Mounting
WIRING GUIDELINES:
CAUTION:
The National Electric Code limits the maximum number of conductors that can be installed in conduit and wiring boxes depending on the size of the conduit, the volume of the boxes, and the gauge of the wire used. Make sure that wiring used for installation complies with the latest NEC, NFPA, Local, State, County or Province requirements.
The National Electrical Code defines the types of circuits for protective signaling systems as either power limited circuits or non-
power limited circuits. The SAFEPATH circuits have been designed as non-power limited circuits.
Field Wiring:
Before installation, the system specifier shall determine the proper wire gauge for all field wiring and ensure that all wiring
complies with the latest NEC, NFPA, Local, State, County of Province Requirements.
The wiring terminals are designed to accept #12 to #22 American Wire Gauge (AWG) (one wire per terminal). When connecting
field wiring to terminals, refer to Figure 2.
Check the integrity of all field wiring following directions in the "Field Wiring Checkout" section. Confirm that the specified
cable is installed and there is continuity between required points (no "open circuits"), with no unwanted shorts to other conductors, chassis, or earth ground. Perform the field wiring checkout before making any connections to the wiring terminals.
P83572 C
Sheet 3 of 8
Loading...
+ 5 hidden pages