wheelock PS-12-24-8 MP INSTALLATION INSTRUCTIONS

Page 1
POWERPATH
PS-12/24-8MP
(103046)
POWER BOOSTER
POWER SUPPLY
Installation Instructions
273 Branchport Avenue, Long Branch, NJ 07740-6899 Ph: (800) 631-2148 Fax: (732) 222-8707 Web Site: www.wheelockinc.com e-mail: info@wheelockinc.com
A84531 B
Copyright 2005 Wheelock, Inc. All rights reserved.
Page 2
Use this product according to this instruction manual.
Thank you for using our products.
Please keep this instruction manual for future reference.
TABLE OF CONTENTS
1.0 - INTRODUCTION AND SPECIFICATIONS 2
1.1 - INTRODUCTION 2
1.2 - SPECIFICATIONS 3
1.3 - TERMINOLOGY 3
1.4 - TERMINAL IDENTIFICATION 4
1.5 - LED STATUS 6
1.6 - BATTERY MAINTENANCE 6
2.0 - INSTALLATION INSTRUCTIONS 6
2.1 - UNPACKING 6
2.2 - MOUNTING 6
2.3 - WIRING 8
2.4 - RELAY STATUS CONNECTIONS 8
3.0 - OPERATION 10
3.1 - MODES OF OPERATION 10
3.2 - DIP SWITCH SETTINGS 10
3.3 - CLASS “B” OPERATION 11
3.4 - CLASS “A” OPERATION 14
3.5 - MASTER REMOTE OPERATION 18
4.0 - TROUBLESHOOTING 20
5.0 - BATTERY CALCULATION SHEET 21
6.0 - WARRANTY STATEMENT 22
WHEELOCK INC. COMPATIBLE APPLIANCES Appendix A
LIST OF FIGURES
FIGURE 1: TERMINAL LOCATIONS 5
FIGURE 2: MOUNTING DIMENSIONS 7
FIGURE 3: POWERPATH PS-12/24-8MP 9
FIGURE 4: OUTPUT DIP SWITCH(S) 10
LIST OF TABLES
TABLE 1: TERMINAL IDENTIFICATION 4
TABLE 2: LED STATUS DESCRIPTION 6
TABLE 3: DIP SWITCH SELECTION 8
P84333 K Sheet 2 of 23
TABLE 4: TROUBLESHOOTING 20
Page 3
NOTE: All CAUTIONS and WARNINGS are identified by the symbol letters.
WARNING: READ THIS INSTRUCTION MANUAL CAREFULLY. FAILURE TO COMPLY WITH ANY OF THE FOLLOWING INSTRUCTIONS, CAUTIONS, AND WARNINGS COULD RESULT IN IMPROPER APPLICATION AND/OR OPERATION OF THESE PRODUCTS IN AN EMERGENCY SITUATION, WHICH COULD RESULT IN PROPERTY DAMAGE AND SERIOUS INJURY OR DEATH TO YOU AND/OR OTHERS.
. All WARNINGS are printed in bold capital
1.0 INTRODUCTION AND SPECIFICATIONS:
1.1 INTRODUCTION
The PS-12/24-8MP POWERPATH is an 8 Amp, 12/24VDC, filtered and regulated, supervised remote power supply/charger used for supervision and expanded power driving capability for Fire Alarm Notification Appliance Circuits. The PS-12/24-8MP may be connected to any 12VDC or 24VDC Fire Alarm Control Panel (FACP) by using a Notification Appliance Circuit (NAC) or a “Dry Contact”. Primary applications include NAC expansion (supports ADA requirements) and auxiliary power to support system accessories. This unit provides filtered and regulated 12VDC or 24VDC, 8 Amp up to four (4) Class "B", two (2) Class “A”, or two (2) Class “B” and one (1) Class “A” Notification Appliance Circuits. Additionally, an auxiliary power output of 3.5 Amps is provided, which can be reset. The PS-12/24-8MP also contains a battery charger capable of charging either 7 or 12 Amp/Hour (AH) of battery backup.
Two FACP NAC circuits or two “Dry” contact closures can be connected to the POWERPATH inputs. These inputs can then be directed to control supervision and power delivery to any combination of the four (4) outputs.
Each output is rated at 3.0 Amps (Class "B") or 3.0 Amps (Class "A") and can be programmed to generate a steady or Code 3 Temporal Horn sound and a strobe output under alarm condition. Total load for the PS-12/24-8MP NAC circuits shall not exceed 8.0 Amps.
The PS-12/24-8MP under non-alarmed condition provides independent loop supervision for Class “A” and Class “B” FACP NAC circuits. In the event of a loop trouble, the FACP will be notified via the POWERPATH steered input (IN1 or IN2). In addition there are common trouble output terminals (used to indicate a loop trouble) and common trouble input terminals (used generically by any initiating circuit).
Wheelock horns/strobes, strobes and horns with synchronizing capability can be utilized with the PS-12/24­8MP. Audibles can be silenced with only two wires. Additionally, the POWERPATH can provide a temporal coded signal for appliances that can utilize it.
P84333 K Sheet 3 of 23
Page 4
1.2 SPECIFICATIONS
Approvals:
UL Listed 864 Standard for Control Units for Fire Protective Signaling Systems
FM
MEA approved – NYC Dept. of Buildings
California State Fire Marshall (CSFM) approved
Pending: Bureau of Fire Protection (BFP) Chicago
NFPA 72 compliant
Inputs:
120VAC, 50/60Hz, 5.0 Amps or 240VAC, 50/60Hz 3.0 Amps Operating Power in Alarm
12/24VDC Battery Backup Connection
Two (2), 12VDC or 24VDC NAC Initiating Circuits (8-33VDC at 5mA)
Two (2) “Dry” Contact initiating Circuits
Accepts two Class “A” or two Class “B” circuit inputs
Built in battery charger for sealed lead acid or gel type batteries
Outputs:
Switch selectable 12VDC or 24VDC power limited outputs
8 Amp in alarm supply current at 12VDC or 24VDC
Capable of four (4), Class "B" circuits (2.0 Amps each)
Capable of two (2) Class “A” circuits (3.0 Amps each)
Capable of one (1) Class “A” circuit (3.0 Amps) and two (2) Class “B” circuits (2.0 Amps each)
Capable of two (2) Class “B” circuits (3.0 Amps each) and (2) Class “B” circuits (2.0 Amps total)
Temporal (Code 3) or constant voltage output generation
Built-in Wheelock synchronization mode that can be fed to any or all of the output circuits
Input and output can be synchronized with “IN>OUT SYNC” mode (SM, DSM or 2
required)
Audible silence capability
Filtered and electronically regulated output
3.5 Amp auxiliary power limited output with reset capability. (Removed upon AC loss or alarm. Automatic
reset 30 seconds after AC power returns or the alarm condition is over)
Supervision:
Compatible with 12VDC or 24VDC FACP
Signaling appliance loops are supervised and steered to either IN1 or IN2
2.2K Ohm, 1 Watt (Wheelock Model #MPEOL) End of Line Resistor (EOLR) for supervision of all outputs
Common input and output trouble circuits
Automatic switchover to standby battery when AC fails
Thermal and short circuit protection with auto reset
Input and output status LED indicators
AC fail supervision (Form C contact, 1 Amp 28VDC)
Battery presence and low battery supervision (Form C contact, 1 Amp 28VDC)
Ground Fault Detection
1.3 TERMINOLOGY
CLASS “A” = STYLE Z CLASS “B” = STYLE Y FACP = Fire Alarm Control Panel EOLR = End of Line Resistor NAC = Notification Appliance Circuit SM = Wheelock Sync Module with single output. DSM = Wheelock Dual Sync Module with two outputs. C = Common NC = Normally Closed NO = Normally Open AH = Ampere/Hour
nd
PS-12/24-8MP is
P84333 K Sheet 4 of 23
Page 5
1.4 TERMINAL IDENTIFICATION
Table 1: Terminal Identification
Terminal Block
Identification
Numbers (Figure 1) Identification
TB4-1, 2
TB4-3, 4,
TB5-1, 2 TB5-5, 4 TB4-5, 6
TB5-5, 6
TB6-1, 2 TB6-3, 4 TB6-5, 6 TB6-7, 8
TB7-1-3
TB7-4, 5
Terminal Function/Description
IN1+,IN1- These terminals connect to the input voltage source (i.e. 12VDC or
24VDC FACP). The FACP will supply a voltage from 8-33VDC at 5mA. During the alarm condition these inputs will cause the designated outputs to drive the notification appliances (designated outputs are set by output DIP switch banks). During Stand-by on a FACP, a trouble condition on the designated loop will cause these inputs to trip the FACP by opening the FACP loop. Alarm condition always overrides trouble to drive output indicating appliances.
RET1+, RET1- EOLR is connected on these terminals corresponding to IN1+ and IN1-,
or the loop may be continued to other power supplies or appliances
before terminating. IN2+, IN2- Same as IN1+, IN1- for corresponding terminals. RET2+, RET2- Same as RET1+, RET1- for corresponding terminals. C “DRY1” NC Dry contacts are used to actuate the designated outputs. Contacts are
normally closed
and actuate the power supply on contact Open. Designated outputs correspond to IN1+,IN1-. NOTE: FACP NAC circuit cannot energize the power supply by these contacts. NOTE: When these terminals are not in use, a jumper must be connected across them.
C “DRY2” NC Operates the same as IN2+,IN2- for corresponding terminals. When
these terminals are not in use, a jumper must be connected across them.
+OUT1­+OUT2­+OUT3­+OUT4-
Indicating appliances are connected to these outputs (See Examples in Operation Section). Each output can supply a maximum load of 3.0 Amps, Class "B" or 3.0 Amps Class "A" and can be individually programmed for Normal Mode, Temporal Mode, IN>OUT SYNC Mode, or WHEELOCK SYNC Mode. The outputs can be configured as four Class "B" circuits, two Class "A" circuits, or two Class "B" and one Class "A" circuits. Outputs are controlled by a designated input (INPUT 1 or 2) as selected by the DIP switch for that output. NOTE: When the panel has been set to synchronization mode, IN1 is used for strobe activation and IN2 is used for audible silence. Individual output control is disabled.
“NO” “C” “NC” (COMMON
Typically used to trigger remote alerts or other reporting appliances. Form C contacts rated 28VDC at 1 Amp.
TROUBLE OUTPUT) + AUX - This output is capable of 3.5 Amps which can be used for door holders
and can be reset by a momentary switch on the board. The 3.5 Amps of power is disconnected when AC power is lost or the unit is in alarm. The
3.5 Amps of power is reconnected 30 seconds after AC power returns or the alarm condition is over.
P84333 K Sheet 5 of 23
Page 6
(NONPOWER-LIMITED, SUPERVISED)
(LINE OR BLACK LEAD) L1
(NEUTRAL OR WHITE LEAD) L2
(GROUND OR GREEN LEAD) EARTH
(NONPOWER-LIMITED, SUPERVISED)
AC POWER
120VAC, 50/60Hz
240VAC, 50/60Hz
TB1
F1
10 AMP
250V
AC POWER
FUSE
OR
G L2
G L1
MADE IN USA
WITH PRIDE
SEE INSTALLATION INSTRUCTION (P84333) FOR DETAILS
AC POWER SELECTION 120/240VAC
SW1
115V
CONTROL 1
NAC ACTIVATION FROM FACP
TO NEXT
BOOSTER
SHORTED (NO ALARM)
OPEN (ALARM)
CONTROL 2
NAC ACTIVATION FROM FACP
TO NEXT
BOOSTER
SHORTED (NO ALARM)
OPEN (ALARM)
OUTPUT1
IN>OUT SYNC
WHEELOCK SYNC
TEMPORAL
INPUT SELECT
OUTPUT2
IN>OUT SYNC
WHEELOCK SYNC
TEMPORAL
INPUT SELECT
P84230 REV.
TB4
+
-
IN1
+
RET1
-
DRY1
+
-
IN2
+
RET2
-
DRY2
OUT TRB
D8
D13
D14
D18
ON
D70
SW8
SYS
RESET
IN1+
IN1-
OUT1
OUT2
OUT3
OUT4
SW2
2 3 41
41 2 3
SW5
OFF
RET1+
MICRO FAULT
D9
D15
D16
D19
SW3
SW6
D10
INP1
INP2
GND
FAULT
BATT
ON OFF
DRY1RET1-
C NC
AC
D71
OUTPUT3 IN>OUT SYNC WHEELOCK SYNC
2 3 41
TEMPORAL INPUT SELECT
OUTPUT4
41 2 3
IN>OUT SYNC WHEELOCK SYNC TEMPORAL INPUT SELECT
CLASS A/B
SELECTION
SWITCHES
IN2-
IN2+
TB5
POWER SUPPLY DC
SW4
O N
1 2
3
4
DRY2
RET2-
C
RET2+
NC
DC POWER OUT
12V
SELECTION
24V
12Vdc OR 24Vdc
SW9
OUT1
+
TB6
AUXILIARY POWER
RESET
SW7
(MP VERSION)
OUT2
-
OUT3
+
- + - + -
OUT4
NO C NC
AUX
+ -
TB3
BATTERY CONNECTION
-
BATT
7AH-12AH
+
(NONPOWER-LIMITED, SUPERVISED)
W1
TB7
AUXILIARY POWER OUTPUT
(MP VERSION)
3.5A
0.2A 24HR or 0.06A 60HR (CP VERSION) (POWER-LIMITED, FAIL-SAFE)
NC TROUBLE RELAY C FORM-C NO (NONSUPERVISED)
-
NAC4
+
­+
­+
­+
28VDC 1 AMPPOWER-LIMITED
NAC OUTPUTS
NAC3
EOLR 2.2K CLASS A OR B
NAC2
(POWER-LIMITED, SUPERVISED)
NAC1
TWO DIFFERENT SOURCES OF POWER MAY BE CONNECTED TO THIS UNIT.
WAR NIN G
DISCONNECT BOTH SOURCES OF POWER BEFORE SERVICING. FAILURE TO DISCONNECT BOTH SOURCES OF POWER BEFORE SERVICING COULD RESULT IN PROPERTY DAMAGE, SERIOUS INJURY OR DEATH TO YOU AND/OR OTHERS
FCC COMPLIANCE:
1) THIS DEVICE MAY NOT CAUSE HARMFUL INTERFERENCE; AND 2) THIS DEVICE MUST ACCEPT ANY INTERFERENCE
RECEIVED, INCLUDING INTERFERENCE THAT MAY CAUSE UNDESIRED OPERATION.
THIS DEVICE COMPLIES WITH PART 15 OF THE FCC RULES. OPERATION IS SUBJECT TO THE FOLLOWING TWO CONDITIONS:
PAT. PEND. PAT. 5400009, 5608375, 5751210, 5982275 FGN PAT. 185360, 2282717
Figure 1:
Terminal Locations
P84333 K Sheet 6 of 23
Page 7
1.5 LED STATUS
Table 2 lists status of the LED indicators. The ALARM condition occurs when the input causes the output circuits to energize. TROUBLE condition occurs when the circuit is no longer supervised correctly. The TROUBLE LED’s for OUT1, OUT2, OUT3, OUT4 and, GND FAULT latch ON when the trouble occurs. They are turned OFF when an alarm condition occurs or the PS12/24-8MP system rest (SW8) is pressed. The trouble relay follows any trouble condition and is not latching. NOTE: An alarm condition overrides a trouble condition.
Table 2: LED Status Description
LED
OUT1 STANDBY -------- TROUBLE OUT2 STANDBY -------- TROUBLE OUT3 STANDBY -------- TROUBLE OUT4 STANDBY -------- TROUBLE INP1 STANDBY ALARM TROUBLE* INP2 STANDBY ALARM TROUBLE* GND FAULT -------- TROUBLE -------­AC No AC AC Present -------­BATT -------- TROUBLE -------­MICRO FAULT -------- TROUBLE -------­POWER SUPPLY DC TROUBLE DC PRESENT --------
* NOTE: If INP1 or INP2 LED and OUT1-OUT4 TROUBLE LED are on, TROUBLE exists currently.
1.6 BATTERY MAINTENANCE
Battery Replacement: Power-Sonic (or equal) 12VDC, replace with new batteries every four (4) years or as needed if battery will no longer accept full charge. Two 12V batteries are required for 24VDC setting. Use either a 7AH battery or a 12AH battery in accordance with the proper battery calculation for the application using BATTERY CALCULATION SHEET provided on Sheet 23.
NOTE: Battery compartment measures 4-1/2" High X 11-1/2" Wide X 4-1/2" Deep.
2.0 INSTALLATION INSTRUCTIONS:
NOTE: The PS-12/24-8MP POWERPATH shall be installed in accordance with the National Fire Protection
Association (NFPA), National Electrical Code (NEC) and all applicable state and local regulations.
2.1 UNPACKING
The POWERPATH was carefully checked before leaving the factory. Inspect shipping container and unit carefully for indications of improper handling. If damage is detected, make an immediate claim to the carrier.
Remove the POWERPATH from the shipping container and check that the door lock keys, door lock, and battery connection wires are inside. Make sure the printed circuit board is securely mounted to the rear of the enclosure.
2.2 MOUNTING
WARNING: TO REDUCE THE RISK OF FIRE OR ELECTRIC SHOCK, DO NOT EXPOSE THIS UNIT
TO RAIN OR MOISTURE.
CAUTION: This product is not intended for use in hazardous locations as defined by the National
Electrical Code (NEC) and by the National Fire Protection Association (NFPA).
Mount the POWERPATH in the desired location using the mounting dimensions in Figure 2.
Mount the panel in a location that does not exceed a temperature range of 0° C to 49° C (32° F to 120° F) and a humidity equal to 10% to 85% at 30° C (86° F) non-condensing.
When mounting on interior walls, use proper screw anchors in plaster. When mounting to concrete, especially when moisture is expected, first attach a piece of ¾ inch plywood to the concrete surface. Attach the POWERPATH to the plywood.
P84333 K Sheet 7 of 23
OFF
ON
ON
Page 8
13.950"
.544"
1.060"
10.000"
Figure 2:
Mounting Dimensions
DIMENSIONS (H x W x D) - 16” x 12.25” x 5”
NOTE: All dimensions shown are measured in inches.
P84333 K Sheet 8 of 23
Page 9
2.3 WIRING
Review the Operation Section (3.0) in order to select the proper hook-up and use of the POWERPATH. Set switches and wire the POWERPATH as follows: Terminal locations are shown in Figure 1. Set Power Supply switch (SW1) for 120VAC or 240VAC operation. See Figure 1.
A. Set Power Supply switch (SW4) for desired output voltage (Down for 24VDC, Up for 12VDC). See
Figure 1.
B. Set output DIP Switch(s) to follow corresponding input (IN1, IN2) and desired output mode. See Table
3 DIP Switch Selection and DIP Switch Settings Section (3.2).
C. Set DIP Switch SW9 position 1 & 2 to select Class “A” or Class “B” operation (Off for Class "B", On for
Class "A"). See Figure 1.
D. Dress battery wire down to the back of the enclosure, observing ¼” separation of power limited wire
V.S. non-power limited wiring. See Figure 3.
E. Connect notification appliances to desired outputs OUT1 – OUT4. See Operation Section (3.0).
The POWERPATH has in-out wiring terminals that accept two #18 to #12 American Wire Gauge (AWG) wires at each screw terminal. Strip leads 3/8 inches and connect to screw terminals.
Separate all in-out wire runs on supervised circuits to insure integrity of circuit supervision. The polarity shown in the wiring diagrams and on the circuit boards is for operation of the appliances. The polarity is reversed by the FACP during supervision.
Total load for the PS-12/24-8MP NAC circuits shall not exceed 8.0 Amps.
Total load of any Class “B”output circuit shall not exceed 3.0 Amps.
Total load of any Class “A”output circuit shall not exceed 3.0 Amps.
Terminate unused outputs with a 2.2K Ohm EOLR.
F. Connect the indicating circuit(s) from the FACP to the desired input(s), IN1 and IN2. Connect EOLR to
RET1 and RET2. The value is determined by FACP.
G. Connect desired auxiliary equipment (Door Holder) to the auxiliary output terminals +AUX-. This output
is disconnected upon AC loss or alarm condition. The power is reconnected 30 seconds after AC
power returns or the alarm condition is over. H. Connect trouble relays as desired. I. Connect backup batteries. Observe correct polarity and voltage. For 12VDC, use a single 12V battery.
For 24VDC, use two of the same connected in series. Use either a 7AH or a 12AH battery depending
on circuit loading, BATTERY CALCULATION SHEET is provided on Sheet 23. J. Install battery cover between both battery wires and Power Limited Wiring. See Figure 3. K. Connect AC source. The AC source shall be connected to a dedicated, non-switch power source. The
AC must first be wired into the buildings main electrical power. The conduit entry can be either from the
top or left hand side using the knock-outs. See Figure 3. Connect Earth Ground First. L. Press Auxiliary Power Reset, SW7 to ensure that Auxiliary Power is present. M. Close door and secure with 2 screws on side.
Table 3: DIP Switch Selection
Function Switch Position Description Note
INPUT SELECT
ON
OFF
Selected output to be controlled by Input 1 (IN1+, IN1-) (DRY1)
Selected output to be controlled by Input 2 (IN2+, IN2-) (DRY2)
------
------
TEMPORAL ON Generates Code 3 temporal signal on this output. 1
IN>OUT SYNC ON Allows a sync signal on the input to be used by the output. -----­WHEELOCK SYNC MODE
WHEELOCK SYNC “ON”
IN>OUT SYNC “ON”
Generates Wheelock sync signal for synchronizing Wheelock horns and strobes.
NOTE 1: Use only with appliances that can operate using a coded horn appliance. (Example: Wheelock Series
CH, and Series MT)
NOTE 2: Use only with Wheelock Series AS/AH, Series NS/NS4/NH, Series RSS and products with SL/SLM
strobes.
2.4 RELAY STATUS CONNECTIONS
COMMON TROUBLE TERMINALS – The common trouble terminals are located on the right bottom side of the PC Board. The three terminals are labeled “NO”, “C” and “NC”. When the PS-12/24-8MP is operating normally the “NC” “C” terminals are shorted, and the “C” “NO” terminals are open. There are five trouble conditions that will cause these terminals to change state. The relay follows the trouble condition and is not latching.
Supervision trouble on any output
Battery Fail
(+OUT1-, +OUT2-, +OUT3-, +OUT4-)
AC Loss • GND Fault
Micro Processor Fault
P84333 K Sheet 9 of 23
2
Page 10
INPUT CIRCUITS
POWER-LIMITED
BATTERY
COVER
RESTS ON
TOP OF
BATTERIES
AC POWER
NON-POWER LIMITED
120VAC, 5 AMPS, 50/60Hz 240VAC, 3 AMPS, 50/60Hz
F1
AC POWER
FUSE
OUTPUT1
IN>OUT SYNC
WHEELOCK SYNC
TEMPORAL
INPUT SELECT
OUTPUT2
IN>OUT SYNC
WHEELOCK SYNC
TEMPORAL
INPUT SELECT
P84230 REV.
TB4
TB1
10 AMP
250V
OUT TRB
D8
D13
D14
D18
ON OFF
RESET
IN1+
SW8
SYS
D70
G L2
OUT1
OUT2
OUT3
OUT4
IN1-
3 4
SW2
2 1
4 3
SW5
1 2
MICRO FAULT
RET1+
G L1
SELECTION
D9
D15
D16
D19
SW3
SW6
ON OFF
AC POWER
120/240VAC
D10
INP1
INP2
GND
FAULT
BATT
OUTPUT3 IN>OUT SYNC
3 4
WHEELOCK SYNC
2
TEMPORAL
1
INPUT SELECT
OUTPUT4
4
IN>OUT SYNC
3
WHEELOCK SYNC TEMPORAL
1 2
INPUT SELECT
DRY1RET1-
C NC
TB5
AC
D71
IN2+
SW1
115V
CLASS A/B
SELECTION
SWITCHES
POWER SUPPLY DC
SW4
O N
1 2
3
4
DRY2
RET2-IN2-
C
RET2+
+ YELLOW -
12V 24V
SW9
NC
TB6
DC POWER OUT SELECTION 12Vdc OR 24Vdc
AUXILIARY POWER
RESET
SW7
OUT2
OUT1
+
- +
(MP VERSION)
OUT3
- + - + -
OUT4
BLACK -
NO C
RED +
RELAY CONTACTS
AUX OUTPUT POWER-LIMITED
TB3
-
BATT
+
AUX
+ -
W1
TB7
OUTPUT CIRCUITS POWER-LIMITED
BATTERY WIRES TO BE DRESSED TO BACK OF ENCLOSURE TO ENSURE POWER LIMITED V.S. NON POWER LIMITED 1/4" SEPARATION.
NC
RED +
+
-
+
BLACK -
+ YELLOW -
-
BATTERY TERMINALS
TOP VIEW
Figure 3:
POWERPATH PS-12/24-8MP
P84333 K Sheet 10 of 23
Page 11
3.0 OPERATION:
3.1 MODES OF OPERATION
The PS-12/24-8MP POWERPATH can provide a 12VDC or 24VDC output when initiated by a 8VDC to 33VDC appliance (IN1 or IN2) or an open contact (DRY1 or DRY2). The output will remain on until the deactivation of the input returns it to standby mode.
The outputs can be configured as four Class “B” circuits, two Class “A” circuits, or two Class “B” and one Class “A” circuits.
Each Class "A" circuit is 3.0 Amps and each Class "B" circuit is 3.0 Amps. Total load for the PS-12/24-8MP NAC circuits shall not exceed 8.0 Amps.
There are four output modes which can be used with either Class “A” or Class “B” circuits.
NORMAL MODE Used for a constant 12VDC or 24VDC output.
TEMPORAL MODE Provides a temporal output for appliances that can utilize a coded
signal. (i.e. single stroke bells and chimes and some horns) (NOTE: Do not use with Wheelock AS, NS, RSS appliances.)
IN>OUT SYNC MODE Allows a coded signal or synchronization signal input to be utilized by
the POWERPATH. This signal may come from a FACP, another PS­12/24-8MP or a Wheelock Synchronization Module (SM-12/24 or DSM­12/24). Audibles can also be silenced.
WHEELOCK SYNC MODE Activates the built-in Wheelock Synchronization Mode for use with
patented synchronized horns and strobes. Audibles can also be
3.2 DIP SWITCH SETTINGS
The following is the DIP Switch settings for Output 1. Each of the remaining outputs is controlled similarly.
When switches are changed, press SYS RESET and wait 30 seconds before activating.
silenced.
Figure 4:
MODE DIP SWITCH SETTING
NORMAL MODE INPUT SELECT (1) “ON” for “IN1” or “DRY1” “OFF” for “IN2” or “DRY2” TEMPORAL (2) “OFF” WHEELOCK SYNC (3) “OFF” IN>OUT SYNC (4) “OFF”
TEMPORAL INPUT SELECT (1) “ON” for “IN1” or “DRY1” “OFF” for “IN2” or “DRY2” TEMPORAL (2) “ON” WHEELOCK SYNC (3) “OFF” IN>OUT SYNC (4) “OFF”
IN>OUT SYNC INPUT SELECT (1) “ON” for “IN1” or “DRY1” “OFF” for “IN2” or “DRY2” TEMPORAL (2) “OFF” WHEELOCK SYNC (3) “OFF” IN>OUT SYNC (4) “ON”
WHEELOCK SYNC INPUT SELECT (1) “ON” for “IN1” or “DRY1” “OFF” for “IN2” or “DRY2” TEMPORAL (2) “OFF” WHEELOCK SYNC (3) “ON” IN>OUT SYNC (4) “ON”
P84333 K Sheet 11 of 23
Output DIP Switch(s)
OUT1-4
4
IN>OUT SYNC
3
WHEELOCK SYNC
2
TEMPORAL
1
ON
INPUT SELECT
Page 12
3.3 CLASS “B” OPERATION
Class “B” outputs can be controlled from either IN1 or IN2. Switch SW9 position 1 & 2 on the board are in the “OFF” position.
The following are examples of Class “B” connections. A FACP is used as a representative input.
IN1 and/or IN2 can be used for connection to the FACP. The INPUT SELECT Switch (1) selects which
input is to be used to activate the output.
Board switch SW9 position 1 & 2 control Class “A” or Class “B” configuration. SW9 position 1 controls
Outputs 1 and 3. SW9 position 2 controls Outputs 2 and 4.
The PS-12/24-8MP requires a 2.2K Ohm End of Line Resistor (EOLR) on each output for proper
supervision.
Example 1: NORMAL MODE (CLASS B)
OUT1-4
4
IN>OUT SYNC
3
WHEELOCK SYNC
2
ON
TEMPORAL
1
INPUT SELECT
+
IN1
-
F A C
TO NEXT APPLIANCE OR EOLR
+
RET1
-
POWERPATH
P
SW9
ON
4
2
3
1
LEGEND
OUT1
OUT2
OUT3
OUT4
+
TO NEXT APPLIANCE
OR EOLR
-
+
(2.2K OHMS)
TO NEXT APPLIANCE
OR EOLR
-
+
(2.2K OHMS)
TO NEXT APPLIANCE
OR EOLR
-
+
(2.2K OHMS)
TO NEXT APPLIANCE
OR EOLR
-
(2.2K OHMS)
STROBE
Example 2: TEMPORAL MODE (CLASS B)
OUT1
4
F A C
TO NEXT APPLIANCE OR EOLR
+
IN1
-
+
RET1
-
POWERPATH
ON
ON
IN>OUT SYNC WHEELOCK SYNC
23
TEMPORAL
1
INPUT SELECT
OUT2-4
4
IN>OUT SYNC WHEELOCK SYNC
23
TEMPORAL
1
INPUT SELECT
P
SW9
ON
4
2
3
1
OUT1
OUT2
OUT3
OUT4
+
-
+
-
+
-
+
-
EOLR
2.2K OHMS
EOLR
2.2K OHMS
AUDIBLE
TO NEXT APPLIANCE OR EOLR
(2.2K OHMS)
TO NEXT APPLIANCE OR EOLR
(2.2K OHMS)
CAUTION: Strobes require constant voltage and will not operate properly in the TEMPORAL MODE. A second
output set in the NORMAL MODE will provide the constant voltage.
CAUTION: Only use audible appliances that can use a coded signal. Do not use with Wheelock Series AS/AH,
NS/NH or HS4/HS appliances.
P84333 K Sheet 12 of 23
Page 13
Example 3: IN>OUT SYNC MODE from CODED INPUT SOURCE (CLASS B)
F A C
P
CODED
TO NEXT APPLIANCE OR EOLR
CONSTANT
TO NEXT APPLIANCE OR EOLR
+
IN1
-
+
-
+
-
+
-
ON
RET2
ON
IN2
POWERPATH
RET2
SW9
ON
2
3
1
4
IN>OUT SYNC
WHEELOCK SYNC
23
TEMPORAL
1
INPUT SELECT
4
IN>OUT SYNC WHEELOCK SYNC
23
TEMPORAL
1
INPUT SELECT
4
OUT1
OUT2-4
OUT1
OUT2
OUT3
OUT4
+
TO NEXT APPLIANCE OR EOLR
-
+
SW9
(2.2K OHMS)
TO NEXT APPLIANCE OR EOLR
-
+
EOLR
-
2.2K OHMS
+
EOLR
-
2.2K OHMS
(2.2K OHMS)
Minimum pulse duration for coded signals must be greater than 0.4 seconds.
CAUTION: Strobes require constant voltage and will not operate properly in the IN>OUT SYNC MODE with a coded input source. A second constant input with a second output set in the NORMAL MODE will provide the constant voltage.
CAUTION: Only use audible appliances that can use a coded signal. Do not use with Wheelock Series AS/AH, NS/NH or HS4/HS appliances.
Example 4: IN>OUT SYNC MODE with External Sync Module without Audible Silence
(CLASS B)
SM/DSM
OUT1
OUT2
OUT3
OUT4
+
-
+
-
+
-
+
-
EOLR
2.2K OHMS
EOLR
2.2K OHMS
EOLR
2.2K OHMS
+
F
+ OUT1
+ IN1
MINUS 1
TO NEXT APPLIANCE OR EOLR
IN1
-
+
RET1
-
4
23
1
ON
OUT1-4
IN>OUT SYNC WHEELOCK SYNC TEMPORAL INPUT SELECT
A
+ AUDIBLE
C
- AUDIBLE
POWERPATH
P
SW9
ON
4
2
3
1
NOTE: When using the Wheelock external Sync Module (SM or DSM), synchronization will only occur with Wheelock sync appliances.
P84333 K Sheet 13 of 23
TO NEXT APPLIANCE
OR EOLR (2.2K OHMS)
Page 14
Example 5: IN>OUT SYNC MODE with External Sync Module with Audible Silence
(CLASS B)
F A C
P
SM/DSM
+ OUT1
+ IN1
MINUS 1
EOLR
+ AUDIBLE
- AUDIBLE
TO NEXT APPLIANCE OR EOLR
OUT1-4
4
4
4
+
IN1
-
+
RET1
-
IN>OUT SYNC
23
23
23
WHEELOCK SYNC
1
1
1
TEMPORAL
ON
ON
ON
INPUT SELECT
POWERPATH
SW9
ON
4
2
3
1
OUT1
OUT2
OUT3
OUT4
+
-
+
-
+
-
+
-
TO NEXT APPLIANCE OR EOLR
(2.2K OHMS)
EOLR
2.2K OHMS
EOLR
2.2K OHMS
EOLR
2.2K OHMS
NOTE: When using the Wheelock external Sync Module (SM or DSM), synchronization will only occur Wheelock sync appliances.
Example 6: WHEELOCK SYNC MODE without Audible Silence (CLASS B)
with
F
+
-
-
+
IN1
RET1
ON
ON
ON
4
4
4
OUT1-4
IN>OUT SYNC
23
23
23
WHEELOCK SYNC
1
1
1
TEMPORAL
INPUT SELECT
OUT1
OUT2
+
-
+
-
EOLR
2.2K OHMS
TO NEXT APPLIANCE OR EOLR
(2.2K OHMS)
A
POWERPATH
C P
+
-
+
-
SW9
IN2
RET2
ON
TO NEXT APPLIANCE OR EOLR
4
2
3
1
This mode will only synchronize Wheelock horns, horn strobes, and strobes with the synchronization capability.
If only strobes are connected to the POWERPATH outputs, the initiating input to IN2 is not required.
When synchronized horns are used on the two wire output of the POWERPATH, IN2 must be connected as
shown or the horns will not operate.
OUT3
OUT4
+
-
+
-
EOLR
2.2K OHMS
EOLR
2.2K OHMS
P84333 K Sheet 14 of 23
Page 15
Example 7: WHEELOCK SYNC MODE with Audible Silence (CLASS B)
F A C
P
TO NEXT APPLIANCE OR EOLR
AUDIBLE SILENCE
TO NEXT APPLIANCE OR EOLR
+
-
+
-
IN1
RET1
ON
ON
ON
4
4
4
OUT1-4
IN>OUT SYNC
23
23
23
WHEELOCK SYNC
1
1
1
TEMPORAL
INPUT SELECT
POWERPATH
+
IN2
-
+
RET2
-
SW9
ON
4
2
3
1
OUT1
OUT2
OUT3
OUT4
+
-
+
-
+
-
+
-
TO NEXT APPLIANCE OR EOLR
(2.2K OHMS)
EOLR
2.2K OHMS
EOLR
2.2K OHMS
EOLR
2.2K OHMS
This mode will only synchronize Wheelock horns, horn strobes, and strobes with the synchronization capability.
3.4 CLASS “A” OPERATION
Class “A” circuit 1 uses “OUT1” and “OUT3”. Class “A” circuit 2 uses “OUT2” and “OUT4”. When operating in Class “A” the two circuits must have the same switch settings for the operational mode selected. Switch SW9 position 1 & 2 on the PC board are in the “ON” position.
IN1 and/or IN2 can be used for connection to the FACP. The INPUT SELECT Switch (1) selects which input is to be used to activate the output.
Board switch SW9 position 1 & 2 control Class “A” or Class “B” configuration. SW9 position 1 controls Outputs 1 and 3. Switch SW9 position 2 controls Outputs 2 and 4.
DIP Switch settings for each circuit in the Class “A” output must be set identically.
Example 8: NORMAL MODE (CLASS A)
F A
TO NEXT APPLIANCE
OR EOLR OR RETURN TO FACP (CLASS "A")
+
IN1
-
+
RET1
-
ON
OUT1-4
4
IN>OUT SYNC
3
WHEELOCK SYNC
2
TEMPORAL
1
INPUT SELECT
OUT1
OUT2
+
-
+
-
POWERPATH
C
OUT3
-
+
P
SW9
ON
-
OUT4
4
2
3
1
P84333 K Sheet 15 of 23
+
Page 16
Example 9: TEMPORAL MODE (CLASS A)
OUT3
OUT4
4
+
OUT1
3
2
1
ON
4
ON
3
2
1
OUT2
OUT3
-
+
-
-
+
F A C
TO NEXT APPLIANCE OR EOLR OR RETURN TO FACP (CLASS "A")
OUT1
4
+
IN1
-
+
RET1
-
3
2
1
ON
4
3
2
ON
IN>OUT SYNC WHEELOCK SYNC TEMPORAL INPUT SELECT
OUT2
IN>OUT SYNC WHEELOCK SYNC TEMPORAL
1
INPUT SELECT
POWERPATH
P
SW9
ON
4
2
3
1
CAUTION: Strobes require constant voltage and will not operate properly in the TEMPORAL MODE. A second Class “A” output set in the NORMAL MODE will provide the constant voltage for the strobe circuit. Only use sounding appliances that can use a coded signal. Do not use Wheelock AS/AH or NS/NS4/NH appliances with TEMPORAL MODE.
Example 10: IN>OUT SYNC MODE from CODED INPUT SOURCE (CLASS A)
OUT4
-
+
OUT3
OUT4
+
4
OUT1
-
3
2
1
ON
+
4
OUT2
-
3
2
1
ON
-
OUT3
+
-
OUT4
+
F A C
P
CODED
TO NEXT APPLIANCE OR EOLR OR RETURN TO FACP (CLASS "A")
CONSTANT
TO NEXT APPLIANCE OR EOLR OR RETURN TO FACP (CLASS "A")
OUT1
+
IN1
-
+
RET1
-
+
IN2
-
+
RET2
-
SW9
4
IN>OUT SYNC
3
WHEELOCK SYNC
2
TEMPORAL
1
INPUT SELECT
ON
OUT2
4
IN>OUT SYNC
3
WHEELOCK SYNC
2
TEMPORAL
1
INPUT SELECT
ON
POWERPATH
ON
4
2
3
1
CAUTION: Strobes require constant voltage and will not operate properly in the IN>OUT SYNC MODE with a coded input. A second Class “A” output set in the NORMAL MODE will provide the constant voltage for the strobe circuit. Only use audible appliances that can use a coded signal. Do not use Wheelock AS/AH or NS/NS4/NH appliances with a coded input.
P84333 K Sheet 16 of 23
Page 17
Example 11: IN>OUT SYNC MODE with External Sync Module without Audible Silence
(CLASS A)
SM/DSM
+
IN1
-
+
RET1
-
F
+ OUT1
+ IN1
MINUS 1
TO NEXT APPLIANCE OR EOLR
A
+ AUDIBLE
C
- AUDIBLE
POWERPATH
P
SW9
ON
NOTE: When using the Wheelock external Sync Module (SM or DSM), synchronization will only occur Wheelock sync appliances.
Example 12: IN>OUT SYNC MODE with External Sync Module with Audible Silence
(CLASS A)
OUT1-4
4
IN>OUT SYNC
3
WHEELOCK SYNC
2
TEMPORAL
1
INPUT SELECT
ON
4
2
3
1
OUT1
OUT2
OUT3
OUT4
+
-
+
-
-
+
-
+
with
SM/DSM
F A C
AUDIBLE
SILENCE
EOLR
+ OUT1
+ IN1
MINUS 1
+ AUDIBLE
- AUDIBLE
TO NEXT APPLIANCE OR EOLR
+
IN1
-
+
RET1
-
POWERPATH
ON
OUT1-4
4
IN>OUT SYNC
3
WHEELOCK SYNC
2
TEMPORAL
1
INPUT SELECT
P
SW9
ON
4
2
3
1
NOTE: When using the Wheelock external Sync Module (SM or DSM), synchronization will only occur Wheelock sync appliances.
P84333 K Sheet 17 of 23
OUT1
OUT2
OUT3
OUT4
+
-
+
-
-
+
-
+
with
Page 18
Example 13: WHEELOCK SYNC MODE without Audible Silence (CLASS A)
OUT1-4
F A
+
-
-
+
IN1
RET1
ON
4
IN>OUT SYNC
3
WHEELOCK SYNC
2
TEMPORAL
1
INPUT SELECT
OUT1
OUT2
+
-
+
-
C P
TO NEXT APPLIANCE OR EOLR OR RETURN TO FACP (CLASS "A")
POWERPATH
+
IN2
-
-
RET2
+
SW9
ON
4
2
3
1
OUT3
OUT4
-
+
-
+
This mode will only synchronize Wheelock horns, horn strobes, and strobes with the synchronization capability.
If only strobes are connected to the POWERPATH outputs, the initiating input to IN2 is not required.
When synchronized horns are used on the two wire output of the POWERPATH, IN2 must be connected as
shown or the horns will not operate.
Example 14: WHEELOCK SYNC MODE with Audible Silence (CLASS A)
ON
OUT1-4
4
IN>OUT SYNC
3
WHEELOCK SYNC
2
TEMPORAL
1
INPUT SELECT
OUT1
OUT2
+
-
+
-
F A
TO NEXT APPLIANCE OR EOLR OR RETURN TO FACP (CLASS "A")
+
IN1
-
+
RET1
-
C
AUDIBLE SILENCE
P
TO NEXT APPLIANCE OR EOLR OR RETURN TO FACP (CLASS "A")
This mode will only synchronize Wheelock horns, horn strobes, and strobes with the synchronization capability.
COMBINATION CLASS “A” AND CLASS “B” HOOKUP
POWERPATH
+
IN2
-
+
RET2
-
SW9
ON
4
2
3
1
OUT3
OUT4
-
+
-
+
The PS-12/24-8MP POWERPATH can be configured to have one Class “A” (3.0 Amps) and two Class “B” (2.0 Amps each circuit) Outputs at the same time. This is done by Switch SW9 position 1 & 2. NOTE: When SW9 position 1 is on, OUTPUTS 1 and 3 are the Class “A” circuit. When SW9 position 2 is on, OUTPUTS 2 and 4 are the Class “A” circuit.
COMBINATION OF MODES
In Class “B” configuration, each output can be set to an independent mode as desired.
In Class “B”, IN1 or IN2 can be selected to activate any of the outputs desired.
In Class “A”, OUTPUT DIP Switches must be set identically for each Class “A” output.
P84333 K Sheet 18 of 23
Page 19
3.5 MASTER REMOTE OPERATION:
4
5
5
Example 15: Synchronized Multiple PS-12/24-8MP or PS-12/24-8CP Using a Master PS-12/24-8MP or PS-12/24-8CP (in the WHEELOCK SYNC MODE) Without Audible Silence, and Using Input #1.
NOTE 2
FACP
NAC INPUT IN
ALARM CONDITION
-
+
P84230 REV.
P84230 REV.
TB1
F1
IN>OUT SYNC
WHEELOCK SYNC
TEMPORAL
INPUT SELECT
IN>OUT SYNC
WHEELOCK SYNC
TEMPORAL
INPUT SELECT
TB4
MH8
NOTE 5
TB1
F1
IN>OUT SYNC
WHEELOCK SYNC
TEMPORAL
INPUT SELECT
IN>OUT SYNC
WHEELOCK SYNC
TEMPORAL
INPUT SELECT
TB4
OUTPUT1
OUTPUT2
IN1+
OUTPUT1
OUTPUT2
IN1+ MH8
L1
ON OFF
D70
SW8
IN1-
L1
ON OFF
D70
SW8
IN1-
GND L2
RET1+
SW2
SW5
GND L2
D8
D13
D14
SW2
SW5
RET1+
GND
115V
SW1
D10
OUT TRB
AC
D9
D8
INP1
OUT1
D15
D13
OUT2
INP2
D14
D16
OUT3
FAULT
D18
D19
OUT4
BATT
SW3
OUTPUT3
IN>OUT SYNC
WHEELOCK SYNC
TEMPORAL
INPUT SELECT
OUTPUT4 IN>OUT SYNC
WHEELOCK SYNC
TEMPORAL
INPUT SELECT
SW6
ON OFF
NCC
RET2-
RET2+
IN2+
RET1-
IN2-
DRY1
TB5
GND
115V
SW1
D10
OUT TRB
AC
D9
INP1
OUT1
D15
OUT2
INP2
D16
OUT3
FAULT
D18
D19
OUT4
BATT
SW3
OUTPUT3
IN>OUT SYNC
WHEELOCK SYNC
TEMPORAL
INPUT SELECT
OUTPUT4
IN>OUT SYNC
WHEELOCK SYNC
TEMPORAL
INPUT SELECT
SW6
ON OFF
NC
C
RET2-
RET2+
IN2+
RET1-
IN2-
DRY1
TB5
MASTER
R40
SW4
12V 24V
AUX
RESET
SW7
SW9
NC
C
+ -
+ -
TB6
OUT1
OUT2
DRY2
NOCNC
+ -
+ -
OUT4
OUT3
TB2
DC
­+
TB3
W1
-
+
MH9
AUX
NOTE
REMOTE
NOTE 6
R40
SW4
12V 24V
AUX
RESET
SW7
SW9
NC
C
+ -
TB6
OUT1
DRY2
+ -
+ -
+ -
OUT4
OUT3
OUT2
NOCNC
TB2
DC
­+
TB3
W1
-
+
MH9
AUX
NOTE
GND L2
GND
L1
TB1
F1
115V
SW1
D10
OUT TRB
AC
D9
D8
INP1
OUT1
D15
D13
OUT2
INP2
D14
D16
OUT3
FAULT
D18
D19
OUT4
BATT
SW3
SW2
OUTPUT1
IN>OUT SYNC
WHEELOCK SYNC
TEMPORAL
INPUT SELECT
OUTPUT2
IN>OUT SYNC
WHEELOCK SYNC
TEMPORAL
INPUT SELECT
SW5
ON OFF
D70
SW8
P84230 REV.
TB4
IN1+
IN1-
RET1+
MH8
See Figure 1 on Sheet 5 for larger view of PC Board.
OUTPUT3
IN>OUT SYNC
WHEELOCK SYNC
TEMPORAL
INPUT SELECT
OUTPUT4
IN>OUT SYNC
WHEELOCK SYNC
TEMPORAL
INPUT SELECT
SW6
ON OFF
SW9
NCC
RET2-
RET2+
IN2+
RET1-
IN2-
DRY1
TB5
REMOTE
NOTE 6
R40
SW4
12V 24V
AUX
RESET
SW7
NC
C
+ -
TB6
OUT1
DRY2
+ -
+ -
+ -
OUT4
OUT3
OUT2
TB2
DC
­+
TB3
W1
-
+
NC
NO
C
MH9
AUX
NOTE
NOTE 1: NAC Input Voltage 8.0VDC to 33.0VDC Constant. NOTE 2: OBSERVE DIP SWITCH SETTINGS
Input Selection Switch (Position 1) on OUT1 to OUT4 DIP Switches are shown in the "ON" Position allowing Input #1 to activate Outputs 1-4, Positions 2-4 are set for "WHEELOCK SYNC MODE"
NOTE 3: Jumper "RET 1-" to "IN 2-" and "RET 1+" to "IN 2+ " only on the Master PS-12/24-8MP. NOTE 4: Diagram shown with an output circuit (OUT4) on Master POWERPATH used to synchronized the Remote
POWERPATHS. NOTE 5: Jumpers must be placed across "DRY 1" and "DRY 2" terminals when operating Power Supply using "IN 1" or "IN 2". NOTE 6: OBSERVE DIP SWITCH SETTINGS
Input Selection Switch (Position 1) on OUT 1 to OUT 4 DIP Switches are shown in the "ON" Position allowing Input #1 to
activate Outputs 1-4. Positions 2-4 are set for "IN>OUT SYNC MODE".
P84333 K Sheet 19 of 23
Page 20
Example 16: Synchronized Multiple PS-12/24-8MP or PS-12/24-8CP Using a Master PS-12/24-8MP
or PS-12/24-8CP (in the WHEELOCK SYNC MODE) With Audible Silence, and Using Input #1
FACP
AUDIBLE SILENCE
ALARM CONDITION
FACP
PROGRAMMED
NAC
NAC INPUT IN
NOTE 2
GND L2
GND
L1
TB1
F1
115V
SW1 D10 AC
OUT TRB
D9
D8
INP1
OUT1
D15
D13
OUT2
INP2
D14
D16
OUT3
FAULT
D18
D19
OUT4
BATT
SW3
SW2
OUTPUT1
IN>OUT SYNC
WHEELOCK SYNC
TEMPORAL
INPUT SELECT
OUTPUT2
IN>OUT SYNC
WHEELOCK SYNC
TEMPORAL
INPUT SELECT
SW5
P84230 REV.
IN>OUT SYNC
WHEELOCK SYNC
TEMPORAL
INPUT SELECT
IN>OUT SYNC
WHEELOCK SYNC
TEMPORAL
INPUT SELECT
P84230 REV.
OUTPUT1
OUTPUT2
TB4
F1
ON OFF
TB4
ON OFF
MH8
TB1
SW2
SW5
IN1+ MH8
F1
D70
SW8
IN1-IN1+
L1
OUT TRB
D8
D13
D14
D18
D70
SW8
IN1-
L1
TB1
-
+
-
+
OUTPUT3
IN>OUT SYNC
WHEELOCK SYNC
TEMPORAL
INPUT SELECT
OUTPUT4
IN>OUT SYNC
WHEELOCK SYNC
TEMPORAL
INPUT SELECT
SW6
ON OFF
SW9
NCC
SW3
SW6
ON OFF
GND
RET2-
C
RET2+
IN2+
IN2-
TB5
DRY2
115V
SW1
D10 AC
NOTE 4
OUTPUT3
IN>OUT SYNC
WHEELOCK SYNC
TEMPORAL
INPUT SELECT
OUTPUT4 IN>OUT SYNC
WHEELOCK SYNC
TEMPORAL
INPUT SELECT
SW9
NCC
RET2-
C
RET2+
IN2+
IN2-
TB5
DRY2
115V
SW1
RET1+
RET1-
DRY1
GND L2
GND
D9
INP1
OUT1
D15
OUT2
INP2
D16
OUT3
FAULT
D19
OUT4
BATT
RET1+
RET1-
DRY1
GND L2
MASTER
R40
SW4
12V 24V
AUX
RESET
SW7
NC
+ -
+ -
TB6
OUT1
OUT2
NOCNC
+ -
+ -
OUT4
OUT3
NOTE 5
TB2
DC
­+
TB3
W1
-
+
MH9
AUX
NOTE 3
REMOTE
R40
SW4
12V 24V
AUX
RESET
SW7
NC
+ -
+ -
TB6
OUT1
OUT2
NO
+ -
+ -
OUT4
OUT3
TB2
DC
­+
TB3
W1
-
+
NC
C
MH9
AUX
NOTE 5
REMOTE
D10
OUT TRB
AC
D9
D8
INP1
OUT1
D15
D13
OUT2
INP2
D14
D16
OUT3
FAULT
D18
D19
OUT4
BATT
SW3
SW2
OUTPUT1
IN>OUT SYNC
WHEELOCK SYNC
TEMPORAL
INPUT SELECT
OUTPUT2
IN>OUT SYNC
WHEELOCK SYNC
TEMPORAL
INPUT SELECT
SW5
ON OFF
SW8
P84230 REV.
TB4
IN1+
IN1-
MH8
See Figure 1 on Sheet 5 for larger view of PC Board.
OUTPUT3
IN>OUT SYNC
WHEELOCK SYNC
TEMPORAL
INPUT SELECT
OUTPUT4 IN>OUT SYNC
WHEELOCK SYNC
TEMPORAL
INPUT SELECT
SW6
ON OFF
D70
NC
C
RET1+
IN2+
RET1-
IN2-
DRY1
TB5
R40
NOTE 4
SW4
12V 24V
AUX
RESET
SW7
SW9
NC
RET2-
C
RET2+
+ -
+ -
TB6
OUT1
OUT2
DRY2
NOCNC
+ -
+ -
OUT4
OUT3
TB2
DC
­+
TB3
W1
-
+
MH9
AUX
NOTE 5
NOTE 1: NAC Input Voltage 8.0 to 33.0VDC Constant. NOTE 2: OBSERVE DIP SWITCH SETTINGS
Input Selection Switch (Position 1) on OUT1 to OUT4 DIP Switches are shown in the "ON" Position allowing Input #1 to activate Outputs 1-4, Positions 2-4 are set for "WHEELOCK SYNC MODE"
NOTE 3: Diagram shown with an output circuit (OUT4) on Master POWERPATH used to synchronize the Remote PowerPaths.
In this configuration the Master PowerPath can only have three NAC circuits.
NOTE 4: OBSERVE DIP SWITCH SETTINGS
Input Selection Switch (Position 1) on OUT 1 to OUT 4 DIP Switches are shown in the "ON" Position allowing Input #1 to activate Outputs 1-4. Positions 2-4 are set for "IN>OUT SYNC MODE".
NOTE 5: Jumpers must be placed across “DRY1” and “DRY2” terminals when operating Power Supply using “IN1” or “IN2”.
P84333 K Sheet 20 of 23
Page 21
4.0 TROUBLESHOOTING:
WARNING: THE PS-12/24-8MP POWERPATH CONTAINS VOLTAGES THAT CAN CAUSE DEATH OR
SERIOUS INJURY. ALWAYS OBSERVE PROPER ELECTRICAL SAFETY PRECAUTIONS AND WARNINGS.
Always follow good troubleshooting procedures:
AUX power is available after a 30 second delay on power up and when coming out of alarm.
When trouble occurs, observe all visual indications and note them.
If the problem is obvious or it can be located on the Troubleshooting Table, note it.
Press SYS RESET (SW8) and wait 30 seconds check for a trouble indication.
Always de-energize the POWERPATH completely (Remove both AC and DC power) repairs.
While the POWERPATH is de-energized, perform a visual and hands on check of all terminals and wires to
ensure proper termination.
Table 4: Troubleshooting
Trouble Cause Action
INP1, INP2 LED’s do not light in ALARM. GND FAULT LED ON GND FAULT Check output circuits. DC LED OFF No DC output. Check wiring to AC power source. AC LED OFF No AC power. Check AC power source. No audible output in WHEELOCK SYNC MODE. Horn, horn strobes, or strobes do not synchronize.
CLASS “A” circuit is not functioning properly.
CLASS “B” circuit is not functioning properly. OUT1, OUT2, OUT3, OUT4 LED's on during standby.
No input signal on terminals IN1+IN1-, IN2+IN2-.
No input to IN2+,IN2-. See Example 13 and 14 for proper
Improper MODE selection Improper appliances.
Improper MODE selection or SW9 settings.
Improper MODE selection or SW9 settings. Trouble on output. Check output supervision voltage.
Check input and input wiring.
input connections. Check MODE selection. Check appliances to ensure proper type for synchronization. For IN>OUT MODE check input appliance (DSM, SM or PS-12/24­8MP). Check to be certain MODE selection is identical for each Class “A” output circuit. Class “A” OUT1 uses outputs 1 and 3. Class “A” OUT2 uses outputs 2 and 4. Check SW9 POS 1 and POS 2 on board for “ON” position. Check SW9 POS 1 and POS 2 on board for “OFF” position.
Check output EOLR.
P84333 K Sheet 21 of 23
Page 22
5.0 BATTERY CALCULATION SHEET:
PS-12/24-8MP BATTERY CALCULATION SHEET
STANDBY CURRENT CALCULATIONS
Amps
1. The Standby Current for the PS-12/24-8MP is .060 Amps. Amps
2. Multiply by the number of hours required.
60 Hours - Multiply by 60
TOTAL STANDBY CURRENT IN Amp HOURS. AH
ALARM CURRENT CALCULATIONS
1. List notification appliance requirements.
CURRENT
ALARM CURRENT FOR THE PS-12/24-8MP 0.100
NOTIFICATION APPLIANCE
2. Calculate total notification appliance current plus alarm current for PS-12/24-8MP. Amps
3. Multiply Step 2 by alarm time required. AH
BACKUP BATTERY REQUIREMENTS
1. Enter Standby Current. AH
2. Enter Alarm Current from Step 3 above. AH
3. Add Steps 1 and 2 together. AH
Multiply Step 3 by 1.2 for minimum Backup Battery Requirements. AH
24 Hours - Multiply by 24
15 Min – Multiply by 0.25
5 Min – Multiply by 0.0833
P84333 K Sheet 22 of 23
Page 23
ANY MATERIAL EXTRAPOLATED FROM THIS DOCUMENT OR FROM WHEELOCK MANUALS OR OTHER DOCUMENTS DESCRIBING THE PRODUCT FOR USE IN PROMOTIONAL OR ADVERTISING CLAIMS, OR FOR ANY OTHER USE, INCLUDING DESCRIPTION OF THE PRODUCT’S APPLICATION, OPERATION. INSTALLATION AND TESTING IS USED AT THE SOLE RISK OF THE USER, AND WHEELOCK WILL NOT HAVE ANY LIABILITY FOR SUCH USE.
6.0 WARRANTY STATEMENT:
Limited Warranty
Wheelock products must be used within their published specifications and must be PROPERLY specified, applied, installed, operated, maintained and operationally tested in accordance with these instructions at the time of installation and at least twice a year or more often and in accordance with local, state and federal codes, regulations and laws. Specification, application, installation, operation, maintenance and testing must be performed by qualified personnel for proper operation in accordance with all of the latest National Fire Protection Association (NFPA), Underwriters' Laboratories (UL), Underwriters’ Laboratories of Canada (ULC), National Electrical Code (NEC), Occupational Safety and Health Administration (OSHA), local, state, county, province, district, federal and other applicable building and fire standards, guidelines, regulations, laws and codes including, but not limited to, all appendices and amendments and the requirements of the local authority having jurisdiction (AHJ). Wheelock products when properly specified, applied, installed, operated, maintained and operationally tested as provided above are warranted against mechanical and electrical defects for a period of three years from date of manufacture (as determined by date code). Correction of defects by repair or replacement shall be at Wheelock's sole discretion and shall constitute fulfillment of all obligations under this warranty.
THE FOREGOING LIMITED WARRANTY SHALL IMMEDIATELY TERMINATE IN THE EVENT ANY PART NOT FURNISHED BY WHEELOCK IS INSTALLED IN THE PRODUCT. THE FOREGOING LIMITED WARRANTY SPECIFICALLY EXCLUDES ANY SOFTWARE REQUIRED FOR THE OPERATION OF OR INCLUDED IN A PRODUCT. WHEELOCK MAKES NO REPRESENTATION OR WARRANTY OF ANY OTHER KIND, EXPRESS, IMPLIED OR STATUTORY WHETHER AS TO MERCHANTABILITY, FITNESS FOR A PARTICULAR PURPOSE OR ANY OTHER MATTER.
USERS ARE SOLELY RESPONSIBLE FOR DETERMINING WHETHER A PRODUCT IS SUITABLE FOR THE USER'S PURPOSES, OR WHETHER IT WILL ACHIEVE THE USER'S INTENDED RESULTS. THERE IS NO WARRANTY AGAINST DAMAGE RESULTING FROM MISAPPLICATION, IMPROPER SPECIFICATION, ABUSE, ACCIDENT OR OTHER OPERATING CONDITIONS BEYOND WHEELOCK'S CONTROL.
SOME WHEELOCK PRODUCTS CONTAIN SOFTWARE. WITH RESPECT TO THOSE PRODUCTS, WHEELOCK DOES NOT WARRANTY THAT THE OPERATION OF THE SOFTWARE WILL BE UNINTERRUPTED OR ERROR-FREE OR THAT THE SOFTWARE WILL MEET ANY OTHER STANDARD OF PERFORMANCE, OR THAT THE FUNCTIONS OR PERFORMANCE OF THE SOFTWARE WILL MEET THE USER'S REQUIREMENTS. WHEELOCK SHALL NOT BE LIABLE FOR ANY DELAYS, BREAKDOWNS, INTERRUPTIONS, LOSS, DESTRUCTION, ALTERATION, OR OTHER PROBLEMS IN THE USE OF A PRODUCT ARISING OUT OF OR CAUSED BY THE SOFTWARE.
THE LIABILITY OF WHEELOCK ARISING OUT OF THE SUPPLYING OF A PRODUCT, OR ITS USE, WHETHER ON WARRANTIES, NEGLIGENCE, OR OTHERWISE, SHALL NOT IN ANY CASE EXCEED THE COST OF CORRECTING DEFECTS AS STATED IN THE LIMITED WARRANTY AND UPON EXPIRATION OF THE WARRANTY PERIOD ALL SUCH LIABILITY SHALL TERMINATE. WHEELOCK IS NOT LIABLE FOR LABOR COSTS INCURRED IN REMOVAL, REINSTALLATION OR REPAIR OF THE PRODUCT BY ANYONE OTHER THAN WHEELOCK OR FOR DAMAGE OF ANY TYPE WHATSOEVER, INCLUDING BUT NOT LIMITED TO, LOSS OF PROFIT OR INCIDENTAL OR CONSEQUENTIAL DAMAGES. THE FOREGOING SHALL CONSTITUTE THE SOLE REMEDY OF THE PURCHASER AND THE EXCLUSIVE LIABILITY OF WHEELOCK.
IN NO CASE WILL WHEELOCK'S LIABILITY EXCEED THE PURCHASE PRICE PAID FOR A PRODUCT.
Limitation of Liability
WHEELOCK'S LIABILITY ON ANY CLAIM OF ANY KIND, INCLUDING NEGLIGENCE AND BREACH OF WARRANTY, FOR ANY LOSS OR DAMAGE RESULTING FROM, ARISING OUT OF, OR CONNECTED WITH THIS CONTRACT, OR FROM THE MANUFACTURE, SALE, DELIVERY, RESALE, REPAIR OR USE OF ANY PRODUCT COVERED BY THIS ORDER SHALL BE LIMITED TO THE PRICE APPLICABLE TO THE PRODUCT OR PART THEREOF WHICH GIVES RISE TO THE CLAIM. WHEELOCK'S LIABILITY ON ANY CLAIM OF ANY KIND SHALL CEASE IMMEDIATELY UPON THE INSTALLATION IN THE PRODUCT OF ANY PART NOT FURNISHED BY WHEELOCK. IN NO EVENT SHALL WHEELOCK BE LIABLE FOR ANY CLAIM OF ANY KIND UNLESS IT IS PROVEN THAT OUR PRODUCT WAS A DIRECT CAUSE OF SUCH CLAIM. FURTHER, IN NO EVENT, INCLUDING IN THE CASE OF A CLAIM OF NEGLIGENCE, SHALL WHEELOCK BE LIABLE FOR INCIDENTAL OR CONSEQUENTIAL DAMAGES. SOME STATES DO NOT ALLOW THE EXCLUSION OR LIMITATION OF INCIDENTAL OR CONSEQUENTIAL DAMAGES, SO THE PRECEDING LIMITATION MAY NOT APPLY TO ALL PURCHASERS.
5/05
P84333 K Sheet 23 of 23
Loading...