wheelock PS-12-24-8 INSTALLATION INSTRUCTIONS

Page 1
POWERPATH
PS-12/24-8
(108114)
POWER BOOSTER
POWER SUPPLY
Installation Instructions
273 Branchport Avenue, Long Branch, NJ 07740-6899 Ph: (800) 631-2148 Fax: (732) 222-8707 Web Site: www.wheelockinc.com e-mail: info@wheelockinc.com
P83862 M
Copyright 2002 Wheelock, Inc. All rights reserved.
Page 2
Thank you for using our products.
Use this product according to this instruction manual. Please keep this instruction manual for future reference.
TABLE OF CONTENTS
1.0 - INTRODUCTION AND SPECIFICATIONS
1.1 - INTRODUCTION 2
1.2 - SPECIFICATIONS 3
1.3 - TERMINOLOGY 3
1.4 - TERMINAL IDENTIFICATION 5
1.5 - LED STATUS 7
1.6 - BATTERY MAINTENANCE 7
2.0 - INSTALLATION INSTRUCTIONS 7
2.1 - UNPACKING 7
2.2 - MOUNTING 7
2.3 - WIRING 9
2.4 - RELAY STATUS CONNECTIONS 10
3.0 - OPERATION 11
3.1 - MODES OF OPERATION 11
3.2 - DIP SWITCH SETTINGS 11
3.3 - CLASS “B” OPERATION 12
3.4 - CLASS “A” OPERATION 15
3.5 - MASTER REMOTE OPERATION 19
4.0 - TROUBLESHOOTING 21
5.0 - COMPATIBLE APPLIANCES 22
6.0 - WARRANTY STATEMENT 23
FIGURE 1: POWERPATH PS-12/24-8 4
FIGURE 2: TERMINAL LOCATIONS 6
FIGURE 3: MOUNTING DIMENSIONS 8
FIGURE 4: BAT FAIL/AC FAIL DIAGRAM 10
LIST OF FIGURES
FIGURE 5: OUTPUT DIP SWITCH(S) 11
TABLE 1: TERMINAL IDENTIFICATION 5
TABLE 2: LED STATUS DESCRIPTION 7
TABLE 3: DIP SWITCH SELECTION 9
LIST OF TABLES
TABLE 4: TROUBLESHOOTING 19
P83862 M Sheet 1 of 23
Page 3
NOTE: All CAUTIONS and WARNINGS are identified by the symbol
. All WARNINGS are printed in bold capital
letters.
WARNING: READ THIS INSTRUCTION MANUAL CAREFULLY. FAILURE TO COMPLY WITH ANY OF THE FOLLOWING INSTRUCTIONS, CAUTIONS, AND WARNINGS COULD RESULT IN IMPROPER APPLICATION AND/OR OPERATION OF THESE PRODUCTS IN AN EMERGENCY SITUATION, WHICH COULD RESULT IN PROPERTY DAMAGE AND SERIOUS INJURY OR DEATH TO YOU AND/OR OTHERS.
1.0 INTRODUCTION AND SPECIFICATIONS
1.1 INTRODUCTION
The PS-12/24-8 POWERPATH is an 8 AMP, 12/24VDC, filtered and regulated, supervised remote power supply/charger used for supervision and expanded power driving capability for Fire Alarm Notification Appliance Circuits. The PS-12/24-8 may be connected to any 12 or 24VDC Fire Alarm Control Panel (FACP) by using a Notification Appliance Circuit (NAC) or a “Dry Contact”. Primary applications include NAC expansion (supports ADA requirements) and auxiliary power to support system accessories. This unit provides filtered and regulated 12 or 24VDC, 8 AMP supply to up to four (4) Class B, two (2) Class “A”, or two (2) Class “B” and one (1) Class “A” Notification Appliance Circuits. Additionally, an auxiliary power output that can be reset is provided. The PS-12/24-8 also contains a battery charger capable of charging either 7 or 12 AMP/Hour (AH) of battery backup. The PS-12/24-8 can only provide a maximum load of 8 amperes for 5 minutes with a 7AH battery or 15 minutes with a 12AH battery.
Two FACP NAC circuits or two “Dry” contact closures can be connected to the POWERPATH inputs. These inputs can then be directed to control supervision and power delivery to any combination of the four (4) outputs.
Each output is rated at 2 AMPS (either Class "A" or Class "B") and can be programmed to generate a steady or Code 3 Temporal horn sound and a strobe output under alarm condition. A maximum 4 AMP output is achieved by paralleling 2 outputs (Class "B" only).
The PS-12/24-8 under non-alarmed condition provides independent loop supervision for Class “A” and Class “B” FACP NAC circuits. In the event of a loop trouble, the FACP will be notified via the POWERPATH steered input (IN1 or IN2). In addition there are common trouble output terminals (used to indicate a loop trouble) and common trouble input terminals (used generically by any initiating circuit).
Wheelock horns/strobes, strobes and horns with synchronizing capability can be utilized with the PS-12/24-8. Audibles can be silenced with only two wires. Additionally, the POWERPATH can provide a temporal coded signal for appliances that can utilize it.
P83862 M Sheet 2 of 23
Page 4
1.2 SPECIFICATIONS
Approvals:
UL Listed 864 Control for use with Fire Protective Signaling
MEA approved – NYC Dept. of Buildings
California State Fire Marshall (CSFM) approved
NFPA 72 compliant
Inputs:
115VAC, 60Hz, 3.2 AMP Operating Power in Alarm
12/24VDC Battery Backup Connection
Two (2), 12 or 24VDC NAC Initiating Circuits (9-30VDC at 5mA)
Two (2) “Dry” Contact initiating Circuits
Accepts two Class “A” or two Class “B” circuit inputs
Built in battery charger for sealed lead acid or gel type batteries
Outputs:
Switch selectable 12VDC or 24VDC power limited outputs
8 AMP continuous supply current at 12VDC or 24VDC for 5 minutes with 7AH battery or 15 minutes with 12AH
battery.
Capable of four (4), Class "B" circuits (2 Amps each)
Two outputs may be paralleled for a maximum output of 4 AMPS on a circuit (Class "B" only)
Capable of two (2) Class “A” circuits (2 Amps each).
Capable of one (1) Class “A” circuit (2 Amps) and two (2) Class “B” circuits (2 Amps each)
Code 3 or constant voltage output generation
Built-in Wheelock synchronization mode that can be fed to any or all of the output circuits
Input and output can be synchronized with “IN>OUT SYNC” mode (SM, DSM or 2
Audible silence capability
Filtered and electronically regulated output
50mA auxiliary output with reset capability
Supervision:
Compatible with 12 or 24VDC FACP
Signaling appliance loops are supervised and steered to either IN1 or IN2
22K OHM, ¼ Watt End-of-Line-Resistor (EOLR) for supervision of all outputs
Common input and output trouble circuits
Automatic switchover to standby battery when AC fails
Thermal and short circuit protection with auto reset
Input and output status LED indicators
AC fail supervision (Form “C” contact, 1 AMP 28VDC)
Battery presence and low battery supervision (Form “C” contact, 1 AMP 28VDC)
Auxiliary output fail supervision (Form “C” contact, 1 AMP 28VDC)
Ground Fault Detection (factory installed UL Listed 22K OHM resistor /wire assembly connected from positive (+)
1.3 TERMINOLOGY
AUX to chassis ground)
CLASS “A” = STYLE Z CLASS “B” = STYLE Y FACP = Fire Alarm Control Panel EOLR = End-of-Line Resistor NAC = Notification Appliance Circuit SM = Wheelock Sync Module with single output. DSM = Wheelock Sync Module with two outputs. C = Common NC = Normally Closed NO = Normally Open AH = Ampere/Hour
nd
PS-12/24-8 is required)
P83862 M Sheet 3 of 23
Page 5
Figure 1:
POWERPATH PS-12/24-8
22K OHM RESISTOR/WIRE ASSEMBLY
BAT FAIL
NC C NO
AC FAIL
NC C NO
OPEN = 24V SW1 CLOSED = 12V
POWER SUPPLY
TRANSFORMER
DC
SW1
SW2
+
DETAIL A
_
NO "REMOTE" C
AUX
+
AUX RESET
LOGIC BOARD
_
_
OUT2
OUT1
+
CLOSED
OUT2
INP2
AC
OUT3
AC
UPPER
LOWER
OUT4
FAULT
"FAULT" NC C
NO
WHITE LEAD
BLACK LEAD
C
NC
115 VAC, 60Hz
GREEN LEAD
GROUND
+
-
IN1 IN2
+
OUT3
OUT4
_
RET1
_
BAT+-
ON
ON
ON OFF
+
RET2
+
AC
4
2 3
1
OUT1
4
2 3
1
INP1
_
C "DRY1" NC
IN2
_
RET2
C "DRY2" NC
DC
_
DC
+
_
OUT3
+
+
OUT
ON
4
ON
ON
OFF
_
OUT1
4
INPUT SELECT
TEMPORAL
2 3
STROBE SYNC
1
IN>OUT SYNC
OUT2
4
INPUT SELECT
TEMPORAL
2 3
STROBE SYNC
1
IN>OUT SYNC
IN1
+
RET1
3.2 AMP
OPEN
DETAIL B
P83862 M Sheet 4 of 23
Page 6
1.4 TERMINAL IDENTIFICATION
b
Table 1: Terminal Identification
Balloon Identification Terminal Function/Description
Numbers (Figure 2) Identification Logic Board
1
2
3 4 5
6
7
8
9
10
11 Power Supply Board 12
13
14
IN1+,IN1- These terminals connect to the input voltage source (i.e. 12VDC or 24VDC
FACP). The FACP will supply a voltage from 9-30VDC at 5mA. During the alarm condition these inputs will cause the designated outputs to drive the notification appliances (designated outputs are set by output DIP switch banks). During Stand-by on a FACP, a trouble condition on the designated loop will cause these inputs to trip the FACP by opening the FACP loop. Alarm condition always overrides trouble to drive output indicating appliances.
RET1+, RET1- EOLR is connected on these terminals corresponding to IN1+ and IN1-, or the
loop may be continued to other power supplies or appliances before terminating. IN2+, IN2- Same as IN1+, IN1- for corresponding terminals. RET2+, RET2- Same as RET1+, RET1- for corresponding terminals. C “DRY1” NC Dry contacts are used to actuate the designated outputs. Contacts are normally
closed and actuate the power supply on contact Open. Designated outputs
correspond to IN1+,IN1-. NOTE: FACP NAC circuit cannot energize the power
supply by these contacts. NOTE: When these terminals are not in use, a jumper
must be connected across them. C “DRY2” NC Operates the same as IN2+,IN2- for corresponding terminals. When these
terminals are not in use, a jumper must be connected across them.
+OUT1­+OUT2­+OUT3­+OUT4-
Indicating appliances are connected to these outputs (See Examples in Operation
Section). Each output can supply a maximum load of 2 AMPS and can be
individually programmed for Normal Mode, Temporal Mode, IN>OUT SYNC
Mode, or WHEELOCK SYNC Mode. The outputs can be configured as four
Class "B" circuits, two Class "A" circuits, or two Class "B" and one Class "A"
circuits. Each Class "A" or Class "B" circuit is 2 Amps. Outputs are controlled
by a designated input (INPUT 1 or 2) as selected by the DIP switch for that
output. NOTE: When the panel has been set to synchronization mode, IN1 is
used for strobe activation and IN2 is used for audible silence. Individual output
control is disabled. “NC” “C” “NO (COMMON
Typically used to trigger remote alerts or other reporting appliances. Form “C”
contacts rated 28VDC at 1 AMP. TROUBLE OUTPUT) C “FAULT” NC (COMMON TROUBLE
Typically used to report AC or BAT Fail. An open circuit across this pair of
terminals will cause IN1 and IN2 to simultaneously signal a trouble condition to
the FACP. INPUT)
- AUX + This output is capable of 50mA and can be reset by a momentary switch on the
logic board or can be reset remotely by using the NO “REMOTE”C terminals. NO”REMOTE”C Dry contact closure on these terminals causes –AUX+ output to reset.
+BAT- Stand-by battery input. Use two 12VDC batteries connected in series for 24VDC
operation, or a single 12VDC battery for 12VDC operation. BAT FAIL NO, C, NC
Form “C” dry contacts used to signal low battery or loss of battery voltage. With
attery voltage present terminals NO, C are open, terminals C, NC are closed. With no battery voltage present terminals NO, C are closed, terminals C, NC are open. Form “C” contacts rated at 28VDC at 1 AMP.
AC FAIL NO, C, NC
Form “C” dry contacts used to signal loss of AC voltage. With AC present terminals NO, C are open, terminals C, NC are closed. With no AC present terminals NO, C are closed, terminals C, NC are open. Form “C” contacts rated at 28VDC at 1 AMP
P83862 M Sheet 5 of 23
Page 7
Figure 2:
Terminal Locations
N
B A
C
13
14
T
C
F A
N
I
L
O
N
A
C
C
C
F A
N
I
L
O
D
A
E
C
L
T
A
R
Y
O
O
U
P
B
T
L
I
E
O N
OPEN = 24V SW1 CLOSED = 12V
J1
SW2
DC
SW1
10 11
_
AUX
NO "REMOTE" C
+
AUX RESET
+
DC
+
BAT
-
AC
AC
AC
12
_
DC
+
ON
ON
ON
OFF
4
3
2
1
4
3
2
1
OUT1
INPUT SELECT
TEMPORAL STROBE SYNC IN>OUT SYNC
OUT2
INPUT SELECT
TEMPORAL STROBE SYNC IN>OUT SYNC
1
OUT3
OUT4
ON
ON
ON OFF
3
4
3
2
1
OUT1
4
3
2
1
INP1
5
OUT2
INP2
OUT3
OUT4
FAULT
C N " T
L U A F
" C
O N
C
C N
9
8
+
OUT1
+
OUT2
_
+
OUT3
_
_
7
+
OUT4
_
_
IN1
IN1 IN2
+
RET1
_
RET1
+
2
+
RET2
IN2
+
4
_
RET2
C "DRY1" NC
_
C "DRY2" NC
6
UPPER
LOWER
P83862 M Sheet 6 of 23
Page 8
1.5 LED STATUS
Table 2 lists status of the LED indicators. The ALARM condition occurs when the input causes the output circuits to energize. TROUBLE condition occurs when the circuit is no longer supervised correctly. NOTE: An alarm condition overrides a trouble condition.
Table 2: LED Status Description
LED
Logic Board
OUT1 STANDBY ALARM TROUBLE OUT2 STANDBY ALARM TROUBLE OUT3 STANDBY ALARM TROUBLE OUT4 STANDBY ALARM TROUBLE INP1 STANDBY ALARM TROUBLE INP2 STANDBY ALARM TROUBLE FAULT -------- TROUBLE --------
Power Supply Board
AC No AC AC Present -------­DC No DC DC Present --------
1.6 BATTERY MAINTENANCE
Battery Replacement: Power-Sonic (or equal) 12VDC, replace with new batteries every four (4) years or as needed if battery will no longer accept full charge. Two 12V batteries are required for 24VDC setting. Use either a 7AH battery for 5 minutes of alarm or a 12AH battery for 15 minutes of alarm.
NOTE: Battery compartment measures 4-1/2" High X 11-1/2" Wide X 4-1/2" Deep.
2.0 INSTALLATION INSTRUCTIONS
NOTE: The PS-12/24-8 POWERPATH shall be installed in accordance with the National Electrical Code (NEC) and all
applicable state and local regulations.
2.1 UNPACKING
The POWERPATH was carefully checked before leaving the factory. Inspect shipping container and unit carefully for indications of improper handling. If damage is detected, make an immediate claim to the carrier.
Remove the POWERPATH from the shipping container and check that the door lock keys, door lock, and battery connection wires are inside. Make sure the transformer, Power Board and Logic Board are securely mounted to the rear of the enclosure.
2.2 MOUNTING
WARNING: TO REDUCE THE RISK OF FIRE OR ELECTRIC SHOCK, DO NOT EXPOSE THIS UNIT TO RAIN
OR MOISTURE.
CAUTION: This product is not intended for use in hazardous locations as defined by the National Electrical Code (NEC) and
by the National Fire Protection Association (NFPA).
Mount the POWERPATH in the desired location using the mounting dimensions in Figure 3.
Mount the panel in a location that does not exceed a temperature range of 0° C to 49° C (32° F to 120° F) and a humidity equal to 10% to 85% at 30° C (86° F) non-condensing.
When mounting on interior walls, use proper screw anchors in plaster. When mounting to concrete, especially when moisture is expected, first attach a piece of ¾ inch plywood to the concrete surface. Attach the POWERPATH to the plywood.
CAUTION: The POWERPATH panel shall be mounted in a location within the environmental limits specified in the latest
UL Standard for indoor control panels.
OFF
ON
Blinking
-------- -------- --------
P83862 M Sheet 7 of 23
Page 9
Figure 3:
TOP
Mounting Dimensions
LEFT
FRONT VIEW
RIGHT SIDESIDE
BOTTOM
NOTE: All dimensions shown are measured in inches.
P83862 M Sheet 8 of 23
Page 10
2.3 WIRING
Review the Operation Section (3.0) in order to select the proper hookup and use of the POWERPATH
Set switches and wire the POWERPATH as follows: Terminal locations are shown in Figure 2.
A. Set Power Supply switch (SW1) for desired output voltage (Open for 24VDC, Closed for 12VDC). See Figure 1 (Detail A
and B).
B. Set output DIP Switch(s) to follow corresponding input (IN1, IN2) and desired output mode. See Table 3 DIP Switch
Selection and DIP Switch Settings Section (3.2).
C. Set Logic Board switches SW1 and SW2 to select Class “A” or Class “B” operation (Open for Class B, Closed for Class A).
See Figure 1 (Detail A and B).
CAUTION: The PS-12/24-8 POWERPATH can provide a full 8 AMPS of current during an alarm condition for 5 minutes with a 7AH battery or 15 minutes with 12AH battery . (A 7AH or 12AH battery is required.). Exceeding these limits may result in loss of power.
D. Connect notification appliances to desired outputs OUT1 – OUT4. See Operation Section (3.0).
The POWERPATH has in-out wiring terminals that accept two #18 to #12 American Wire Gauge (AWG) wires at each
screw terminal. Strip leads 3/8 inches and connect to screw terminals.
Separate all in-out wire runs on supervised circuits to insure integrity of circuit supervision. The polarity shown in the
wiring diagrams and on the circuit boards is for operation of the appliances. The polarity is reversed by the FACP during supervision.
Total load of any output circuit shall not exceed 2 AMPS.
Terminate unused outputs with a 22K OHM EOLR.
E. Connect the indicating circuit(s) from the FACP to the desired input(s), IN1 and IN2. Connect End-of Line Resistors to
RET1 and RET2. Value is determined by FACP.
F. Connect desired auxiliary equipment to the auxiliary output terminals –AUX+.
CAUTION: For the Ground Fault Detection Circuit to operate, the 22K OHM RESISTOR/WIRE ASSEMBLY must remain connected between (+) AUX and chassis ground as shown in Figure 1. If this connection is broken or disconnected, the Ground Fault Detection Circuit will be DISABLED and ground faults will NOT result in a TROUBLE condition.
G. Select AC Trouble Delay Option. (Unit is factory set for 1 minute. Remove J1 for 6 hour delay.)
H. Connect trouble relays as desired.
I. Connect backup batteries. Observe correct polarity and voltage. For 12VDC, use a single 12V battery. For 24VDC, use two
of the same connected in series. Use either a 7AH battery for 5 minutes of alarm or a 12AH battery for 15 minutes of alarm.
J. Connect AC source. The AC must first be wired into the buildings main electrical power. The conduit entry can be either
from the top using knock-outs or right side in the transformer area. See Figure 3.
Table 3: DIP Switch Selection
Function Switch Position Description Note
INPUT SELECT TEMPORAL ON Generates Code 3 temporal signal on this output. 1
STROBE SYNC N/A Used only in the Wheelock sync mode. 2 IN>OUT SYNC ON Allows a sync signal on the input to be used by the output. -----­WHEELOCK SYNC MODE
STROBE SYNC “ON”
IN>OUT SYNC “ON”
NOTE 1: Use only with appliances that can operate using a coded horn appliance. (Example: Wheelock Series CH, and Series
NOTE 2: Used to synchronize Wheelock Sync products in the Wheelock sync mode.
MT)
NOTE 3: Use only with Wheelock Series AS/AH, Series NS/NS4/NH, Series RSS, Series HS4 and products with SL/SLM
strobes.
P83862 M Sheet 9 of 23
ON
OFF
Selected output to be controlled by Input 1 (IN1+, IN1-) (DRY1) Selected output to be controlled by Input 2 (IN2+, IN2-) (DRY2)
Generates Wheelock sync signal for synchronizing Wheelock horns and strobes.
------
------
3
Page 11
2.4 RELAY STATUS CONNECTIONS
POWER SUPPLY BOARD
WARNING: BAT FAIL AND AC FAIL CONTACTS MUST BE USED TO REPORT A TROUBLE CONDITION TO THE FACP IN THE EVENT THAT AC OR BATTERY POWER FAILS. FAILURE TO DO THIS WILL CAUSE THE PS-12/24-8 TO NOT REPORT ALL TROUBLE CONDITIONS. FIGURE 4 SHOWS A CIRCUIT THAT WILL REPORT TROUBLE THROUGH THE IN1 AND/OR IN2 NAC CIRCUITS WHEN AC FAILS, BATTERY IS LOW OR BATTERY IS NOT PRESENT.
BAT FAIL – When the battery (12VDC or 24VDC) is applied to the +DC- terminals, the NC C terminals on the BAT FAIL will be shorted, and the C NO terminals will be open. If the battery is removed, is low or fails with AC power present the NC C terminal will open and the C NO will short. The low battery condition is reported at approximately 21VDC (24VDC output setting) or approximately 10.5VDC (12VDC output setting). Refer to Figure 4.
AC FAIL – When AC Power is applied the NC C terminals on the AC FAIL will be shorted, and the C NO terminals will be open. If the AC Power is removed or fails with battery power present, the NC C terminals will open and the C NO will short after 1 minute or 6 hours depending on the condition of J1. (J1 in line = 1 minute. J1 removed = 6 hours.) Refer to Figure 4.
LOGIC BOARD
COMMON TROUBLE TERMINALS – The common trouble terminals are located on the right side of the Logic Board. The bottom three terminals are labeled “ NC, C and NO”. When the PS-12/24-8 is operating normally the NC C terminals are shorted, and the C NO terminals are open. There are two trouble conditions that will cause these terminals to change state.
Supervision trouble on any output (+OUT1-, +OUT2-, +OUT3-, +OUT4-)
Terminals C ”FAULT” NC open
NOTE: If terminals C “FAULT” NC are not used, a jumper shall be installed across the terminals.
Figure 4.
BAT FAIL/AC FAIL
BAT FAIL
NC C NO
NC C NO
AC FAIL
DETAIL A
DETAIL B
G
F
CLOSED
OPEN
C
NC C NO
NC C NO
DELAY OPTION
SW2
BAT FAIL
AC FAIL
AC TROUBLE
J1
DC
SW1
+
POWER SUPPLY
_
AUX
NO "REMOTE" C
+
AUX RESET
LOGIC BOARD
_
OUT2
OUT1
+
A
OPEN = 24V SW1 CLOSED = 12V
+
DC
+
BAT
-
_
DC
OUT1
+
_
_
OUT4
OUT3
+
+
OUT3
4
INPUT SELECT
TEMPORAL
23
STROBE SYNC
1
IN>OUT SYNC
ON
OUT2
4
INPUT SELECT
TEMPORAL
23
STROBE SYNC
1
IN>OUT SYNC
ON
OFF
ON
_
IN1
+
RET1
IN1 IN2
+
4
23
1
OUT1
ON
OUT4
4
23
1
ON
ON OFF
_
_
IN2
+
_
_
RET2
RET2
RET1
+
AC
OUT2
INP1
C "DRY1" NC
C "DRY2" NC
AC
AC
OUT4
OUT3
FAULT
INP2
C "FAULT" NC
NO
C
NC
UPPER
LOWER
B
D
E
P83862 M Sheet 10 of 23
Page 12
3.0 OPERATION
3.1 MODES OF OPERATION
The PS-12/24-8 POWERPATH can provide a 12 or 24VDC output when initiated by a 9 to 30VDC appliance (IN1 or IN2) or an open contact (DRY1 or DRY2). The output will remain on until the deactivation of the input returns it to its normal mode.
The outputs can be configured as four Class “B” circuits, two Class “A” circuits, or two Class “B” and one Class “A” circuits.
Each Class "A" or Class "B" circuit is 2 Amps.
There are four output modes which can be used with either Class “A” or Class “B” circuits.
NORMAL MODE Used for a constant 12 or 24VDC output.
TEMPORAL MODE Provides a temporal output for appliances that can utilize a coded signal. (i.e. single
stroke bells and chimes and some horns) (NOTE: Do not use with Wheelock AS, NS, RSS appliances.)
IN>OUT SYNC MODE Allows a coded signal or synchronization signal input to be utilized by the
POWERPATH. These appliances may come from a FACP, another PS-12/24-8 or a Wheelock Synchronization Module (SM-12/24 or DSM-12/24). Audibles can also be silenced.
WHEELOCK SYNC MODE Activates the built-in Wheelock Synchronization Mode for use with patented
synchronized horns and strobes. Audibles can also be silenced.
3.2 DIP SWITCH SETTINGS
The following is the DIP Switch settings for Output 1. Each of the remaining outputs is controlled similarly.
Figure 5:
Output DIP Switch(s)
OUT1-4
4
INPUT SELECT
3
TEMPORAL
2
STROBE SYNC
1
ON
MODE DIP SWITCH SETTING
NORMAL MODE INPUT SELECT (4) “ON” for “IN1” or “DRY1” “OFF” for “IN2” or “DRY2” TEMPORAL (3) “OFF” STROBE SYNC (2) “OFF” IN>OUT SYNC (1) “OFF”
TEMPORAL INPUT SELECT (4) “ON” for “IN1” or “DRY1” “OFF” for “IN2” or “DRY2” TEMPORAL (3) “ON” STROBE SYNC (2) “OFF” IN>OUT SYNC (1) “OFF”
IN>OUT SYNC INPUT SELECT (4) “ON” for “IN1” or “DRY1” “OFF” for “IN2” or “DRY2” TEMPORAL (3) “OFF” STROBE SYNC (2) “OFF” IN>OUT SYNC (1) “ON”
WHEELOCK SYNC INPUT SELECT (4) “ON” for “IN1” or “DRY1” “OFF” for “IN2” or “DRY2” TEMPORAL (3) “OFF” STROBE SYNC (2) “ON” IN>OUT SYNC (1) “ON”
IN>OUT SYNC
P83862 M Sheet 11 of 23
Page 13
3.3 CLASS “B” OPERATION
Class “B” outputs can be controlled from either IN1 or IN2. Switches SW1 and SW2 on the Logic Board are in the “OPEN” position.
The following are examples of Class “B” connections. A FACP is used as a representative input.
IN1 and/or IN2 can be used for connection to the FACP. The INPUT SELECT Switch (4) selects which input is to be used
to activate the output.
Logic Board switches SW1 and SW2 control Class “A” or Class “B” configuration. SW1 controls Outputs 1 and 3. SW2
controls Outputs 2 and 4.
The PS-12/24-8 requires a 22K OHM EOLR on each output for proper supervision. Use two 22K OHM EOLR’s when two
Class “B” outputs are paralleled.
Example 1: NORMAL MODE (CLASS B)
OUT1
OUT2
OUT3
OUT4
+
TO NEXT APPLIANCE OR EOLR
-
+
(2.2K OHMS)
TO NEXT APPLIANCE OR EOLR
-
+
(2.2K OHMS)
TO NEXT APPLIANCE OR EOLR
-
+
(2.2K OHMS)
TO NEXT APPLIANCE OR EOLR
-
(2.2K OHMS)
OUT1-4
4
INPUT SELECT
3
TEMPORAL
2
ON
STROBE SYNC
1
IN>OUT SYNC
+
IN1
-
F A C
TO NEXT APPLIANCE OR EOLR
+
RET1
-
POWERPATH
P
LOGIC BOARD
SWI "OPEN" SW2 "OPEN"
LEGEND
STROBE
Example 2: TEMPORAL MODE (CLASS B)
OUT1
4
INPUT SELECT TEMPORAL
23
ON
ON
STROBE SYNC
1
IN>OUT SYNC
OUT2-4
4
INPUT SELECT
3
TEMPORAL
2
STROBE SYNC
1
IN>OUT SYNC
F A C
TO NEXT APPLIANCE OR EOLR
+
IN1
-
+
RET1
-
POWERPATH
P
LOGIC BOARD
SWI "OPEN" SW2 "OPEN"
OUT1
OUT2
OUT3
OUT4
+
-
+
-
+
-
+
-
EOLR
2.2K OHMS
EOLR
2.2K OHMS
AUDIBLE
TO NEXT APPLIANCE OR EOLR
(2.2K OHMS)
TO NEXT APPLIANCE OR EOLR
(2.2K OHMS)
CAUTION: Strobes require constant voltage and will not operate properly in the TEMPORAL MODE. A second output set in the NORMAL MODE will provide the constant voltage.
CAUTION: Only use audible appliances that can use a coded signal. Do not use with Wheelock Series AS/AH or NS/NS4/NH appliances.
P83862 M Sheet 12 of 23
Page 14
Example 3: IN>OUT SYNC MODE from CODED INPUT SOURCE (CLASS B)
F A C
P
CODED
TO NEXT APPLIANCE OR EOLR
CONSTANT
TO NEXT APPLIANCE OR EOLR
+
IN1
-
+
RET1
-
+
IN2
-
POWERPATH
+
RET2
-
ON
ON
OUT1
4
INPUT SELECT TEMPORAL
23
STROBE SYNC
1
IN>OUT SYNC
OUT2-4
4
INPUT SELECT
3
TEMPORAL
2
STROBE SYNC
1
IN>OUT SYNC
OUT1
OUT2
OUT3
+
-
+
-
+
EOLR
-
2.2K OHMS
TO NEXT APPLIANCE OR EOLR
(2.2K OHMS)
TO NEXT APPLIANCE OR EOLR
(2.2K OHMS)
LOGIC BOARD SWI "OPEN" SW2 "OPEN"
OUT4
+
-
EOLR
2.2K OHMS
CAUTION: Strobes require constant voltage and will not operate properly in the IN>OUT SYNC MODE with a coded input source. A second constant input with a second output set in the NORMAL MODE will provide the constant voltage.
CAUTION: Only use audible appliances that can use a coded signal. Do not use with Wheelock Series AS/AH or NS/NS4/NH appliances.
Example 4: IN>OUT SYNC MODE with External Sync Module without Audible Silence (CLASS B)
SM/DSM
OUT1
OUT2
OUT3
+
-
+
-
+
-
TO NEXT APPLIANCE OR EOLR
(2.2K OHMS)
EOLR
2.2K OHMS
EOLR
2.2K OHMS
F A C
P
+ OUT1
+ IN1
MINUS 1
+ AUDIBLE
- AUDIBLE
TO NEXT APPLIANCE OR EOLR
ON
OUT1-4
4
INPUT SELECT
TEMPORAL
2 3
STROBE SYNC
1
IN>OUT SYNC
+
IN1
-
+
RET1
-
POWERPATH
LOGIC BOARD SWI "OPEN" SW2 "OPEN"
OUT4
+
-
EOLR
2.2K OHMS
NOTE: When using the Wheelock external Sync Module (SM or DSM), synchronization will only occur
with Wheelock sync
appliances.
P83862 M Sheet 13 of 23
Page 15
Example 5: IN>OUT SYNC MODE with External Sync Module with Audible Silence (CLASS B)
F A C
P
SM/DSM
+ OUT1
+ IN1
MINUS 1
+ AUDIBLE
EOLR
- AUDIBLE
TO NEXT APPLIANCE OR EOLR
OUT1-4
4
ON
INPUT SELECT
TEMPORAL
2 3
STROBE SYNC
1
IN>OUT SYNC
+
IN1
-
+
RET1
-
POWERPATH
LOGIC BOARD SWI "OPEN" SW2 "OPEN"
OUT1
OUT2
OUT3
OUT4
+
-
+
-
+
-
+
-
EOLR
2.2K OHMS
EOLR
2.2K OHMS
EOLR
2.2K OHMS
NOTE: When using the Wheelock external Sync Module (SM or DSM), synchronization will only occur appliances.
Example 6: WHEELOCK SYNC MODE without Audible Silence (CLASS B)
TO NEXT APPLIANCE OR EOLR
(2.2K OHMS)
with Wheelock sync
OUT1
OUT2
+
-
+
-
TO NEXT APPLIANCE OR EOLR
(2.2K OHMS)
EOLR
2.2K OHMS
F
+
-
-
+
IN1
RET1
ON
OUT1-4
4
INPUT SELECT
TEMPORAL
2 3
STROBE SYNC
1
IN>OUT SYNC
A
POWERPATH
C P
+
IN2
­+
TO NEXT APPLIANCE
RET2
OR EOLR
-
LOGIC BOARD
SWI "OPEN" SW2 "OPEN"
This mode will only synchronize Wheelock horns, horn strobes, and strobes with the synchronization capability.
If only strobes are connected to the POWERPATH outputs, the initiating input to IN2 is not required.
When synchronized horns are used on the two wire output of the POWERPATH, IN2 must be connected as shown or the
horns will not operate.
OUT3
OUT4
+
-
+
-
EOLR
2.2K OHMS
EOLR
2.2K OHMS
P83862 M Sheet 14 of 23
Page 16
Example 7: WHEELOCK SYNC MODE with Audible Silence (CLASS B)
F A C
P
TO NEXT APPLIANCE OR EOLR
AUDIBLE SILENCE
TO NEXT APPLIANCE OR EOLR
+
IN1
-
+
-
RET1
ON
OUT1-4
4
INPUT SELECT
TEMPORAL
2 3
STROBE SYNC
1
IN>OUT SYNC
POWERPATH
+
IN2
-
+
RET2
-
LOGIC BOARD
SWI "OPEN" SW2 "OPEN"
OUT1
OUT2
OUT3
OUT4
+
TO NEXT APPLIANCE OR EOLR
-
+
-
+
-
+
-
EOLR
2.2K OHMS
EOLR
2.2K OHMS
EOLR
2.2K OHMS
(2.2K OHMS)
This mode will only synchronize Wheelock horns, horn strobes, and strobes with the synchronization capability.
3.4 CLASS “A” OPERATION
Class “A” circuit 1 uses “OUT1” and “OUT3”. Class “A” circuit 2 uses “OUT2” and “OUT4”. When operating in Class “A” the two circuits must have the same switch settings for the operational mode selected. Switches SW1 and SW2 on the logic board are in the “CLOSED” position.
IN1 and/or IN2 can be used for connection to the FACP. The INPUT SELECT Switch (4) selects which input is to be used
to activate the output.
Logic Board switches SW1 and SW2 control Class “A” or Class “B” configuration. SW1 controls Outputs 1 and 3. SW2
controls Outputs 2 and 4.
DIP Switch settings for each circuit in the Class “A” output must be set identically.
Example 8: NORMAL MODE (CLASS A)
F A
TO NEXT APPLIANCE OR EOLR OR RETURN TO FACP (CLASS "A")
+
IN1
-
+
RET1
-
ON
OUT1-4
4
INPUT SELECT
3
TEMPORAL
2
STROBE SYNC
1
IN>OUT SYNC
OUT1
OUT2
+
-
+
-
POWERPATH
C
OUT3
­+
P
LOGIC BOARD SWI "CLOSED" SW2 "CLOSED"
P83862 M Sheet 15 of 23
OUT4
­+
Page 17
Example 9: TEMPORAL MODE (CLASS A)
F A C
TO NEXT APPLIANCE OR EOLR OR RETURN TO FACP (CLASS "A")
OUT1 OUT3
ON
ON
4
INPUT SELECT
3
TEMPORAL
2
STROBE SYNC
1
IN>OUT SYNC
OUT2
4
3
2
1
ON
OUT4
ON
+
IN1
-
+
RET1
-
POWERPATH
4
3
2
1
4
3
2
1
OUT1
OUT2
OUT3
+
-
+
-
-
+
P
LOGIC BOARD SWI "CLOSED" SW2 "CLOSED"
CAUTION: Strobes require constant voltage and will not operate properly in the TEMPORAL MODE. A second Class “A” output set in the NORMAL MODE will provide the constant voltage for the strobe circuit. Only use sounding appliances that can use a coded signal. Do not use Wheelock AS/AH or NS/NS4/NH appliances with TEMPORAL MODE.
Example 10: IN>OUT SYNC MODE from CODED INPUT SOURCE (CLASS A)
OUT4
-
+
F A C
P
CODED
TO NEXT APPLIANCE OR EOLR OR RETURN TO FACP (CLASS "A")
CONSTANT
TO NEXT APPLIANCE OR EOLR OR RETURN TO FACP (CLASS "A")
+
IN1
-
+
RET1
-
+
IN2
-
+
RET2
-
LOGIC BOARD SWI "CLOSED"
OUT1 OUT3
ON
ON
4
INPUT SELECT
3
TEMPORAL
2
STROBE SYNC
1
IN>OUT SYNC
OUT2
4
3 2 1
OUT4
4
OUT1
3 2 1
ON
OUT2
4
3 2 1
ON
OUT3
POWERPATH
OUT4
+
-
+
-
­+
­+
SW2 "CLOSED"
CAUTION: Strobes require constant voltage and will not operate properly in the IN>OUT SYNC MODE with a coded input. A second Class “A” output set in the NORMAL MODE will provide the constant voltage for the strobe circuit. Only use audible appliances that can use a coded signal. Do not use Wheelock AS/AH or NS/NS4/NH appliances with a coded input.
P83862 M Sheet 16 of 23
Page 18
Example 11: IN>OUT SYNC MODE with External Sync Module without Audible Silence (CLASS A)
SM/DSM
F A C
P
+ OUT1
+ IN1
MINUS 1
+ AUDIBLE
- AUDIBLE
TO NEXT APPLIANCE OR EOLR
+
IN1
-
+
RET1
-
POWERPATH
ON
OUT1-4
4
INPUT SELECT
3
TEMPORAL
2
STROBE SYNC
1
IN>OUT SYNC
OUT1
OUT2
OUT3
+
-
+
-
-
+
LOGIC BOARD SWI "CLOSED" SW2 "CLOSED"
OUT4
-
+
NOTE: When using the Wheelock external Sync Module (SM or DSM), synchronization will only occur
with Wheelock sync
appliances.
Example 12: IN>OUT SYNC MODE with External Sync Module with Audible Silence (CLASS A)
SM/DSM
F A C
P
AUDI BLE
SILENCE
EOLR
+ OUT1
+ IN1
MINUS 1
+ AUDIBLE
- AUDIBLE
TO NEXT APPLIANCE OR EOLR
+
IN1
-
+
RET1
-
POWERPATH
ON
OUT1-4
4
INPUT SELECT
3
TEMPORAL
2
STROBE SYNC
1
IN>OUT SYNC
OUT1
OUT2
OUT3
+
-
+
-
­+
LOGIC BOARD SWI "CLOSED" SW2 "CLOSED"
OUT4
­+
NOTE: When using the Wheelock external Sync Module (SM or DSM), synchronization will only occur
with Wheelock sync
appliances.
P83862 M Sheet 17 of 23
Page 19
Example 13: WHEELOCK SYNC MODE without Audible Silence (CLASS A)
F A C
P
TO NEXT APPLIANCE OR EOLR OR RETURN TO FACP (CLASS "A")
OUT1-4
4
INPUT SELECT
3
TEMPORAL
2
ON
STROBE SYNC
1
IN>OUT SYNC
+
-
­+
IN1
RET1
POWERPATH
+
IN2
-
-
RET2
+
LOGIC BOARD
SWI "CLOSED"
OUT1
OUT2
OUT3
OUT4
+
-
+
-
­+
­+
SW2 "CLOSED"
This mode will only synchronize Wheelock horns, horn strobes, and strobes with the synchronization capability.
If only strobes are connected to the POWERPATH outputs, the initiating input to IN2 is not required.
When synchronized horns are used on the two wire output of the POWERPATH, IN2 must be connected as shown or the
horns will not operate.
Example 14: WHEELOCK SYNC MODE with Audible Silence (CLASS A)
+
F A C
P
TO NEXT APPLIANCE OR EOLR OR RETURN TO FACP (CLASS "A")
AUDIBLE SIL ENCE
TO NEXT APPLIANCE OR EOLR OR RETURN TO FACP (CLASS "A")
IN1
-
+
RET1
-
POWERPATH
+
IN2
-
+
RET2
-
LOGIC BOARD SWI "CLOSED"
ON
OUT1-4
4
INPUT SELECT
3
TEMPORAL
2
STROBE SYNC
1
IN>OUT SYNC
OUT1
OUT2
OUT3
OUT4
+
-
+
-
-
+
-
+
SW2 "CLOSED"
This mode will only synchronize Wheelock horns, horn strobes, and strobes with the synchronization capability.
COMBINATION CLASS “A” AND CLASS “B” HOOKUP
The PS-12/24-8 POWERPATH can be configured to have one Class “A” (2 Amps) and two Class “B” (2 Amps each circuit) Outputs at the same time. This is done by opening or closing switches SW1 and SW2 on the logic board. NOTE: When SW1 is “Closed”, OUTPUTS 1 and 3 are the Class “A” circuit. When SW2 is “Closed”, OUTPUTS 2 and 4 are the Class “A” circuit.
COMBINATION OF MODES
In Class “B” configuration, each output can be set to an independent mode as desired.
In Class “B”, IN1 or IN2 can be selected to activate any of the outputs desired.
In Class “A”, OUTPUT DIP Switches must be set identically for each Class “A” output.
P83862 M Sheet 18 of 23
Page 20
3.5 MASTER REMOTE OPERATION:
NOTE 2
Example 15: Synchronized Multiple PS-12/24-8 Using a Master PS-12/24-8 (in the WHEELOCK SYNC MODE) Without Audible Silence, and Using Input #1.
FACP
NAC Input in Alarm Condition
NOTE 1
_
AUX
+
AUX RESET
­+
SW1
SW2
MASTER
NO "REMOTE" C
_
DC
OUT1
+
OUT3
4
INPUT SELECT
TEMPORAL
2 3
STROBE SYNC
1
IN>OUT SYNC
ON
OUT2
4
INPUT SELECT
TEMPORAL
2 3
STROBE SYNC
1
IN>OUT SYNC
ON
OFF
ON
+
OUT4
-
ON
ON
ON OFF
JUMPERS
4
2 3
1
OUT1
4
2 3
1
INP1
OUT2
OUT4
OUT3
FAULT
INP2
C "FAULT" NC
NO
C
NC
NOTE 3
NOTE 5
_
_
OUT2
OUT1
+
OUT3
+
+
NOTE 4
_
AUX
NO "REMOTE" C
+
AUX RESET
REMOTE
SW1
SW2
_
_
IN1
+
OUT4
+
RET1
-
+
_
DC
OUT1
+
4
INPUT SELECT
2 3
STROBE SYNC
1
IN>OUT SYNC
ON
OUT2
4
INPUT SELECT
2 3
STROBE SYNC
1
IN>OUT SYNC
ON
OFF
ON
+
IN1 IN2
+
TEMPORAL
TEMPORAL
_
_
IN2
+
_
_
RET2
RET2
RET1
+
FACP EOLR
NOTE 6
OUT3
4
2 3
1
OUT1
ON
OUT4
4
2 3
1
ON
ON OFF
-
C "DRY1" NC
C "DRY2" NC
OUT2
INP1
UPPER
LOWER
OUT4
OUT3
FAULT
INP2
C "FAULT" NC
NO
C
NC
NOTE 5
_
_
OUT2
OUT1
+
OUT3
+
+
_
_
IN1
+
OUT4
+
RET1
+
IN1 IN2
+
-
_
_
IN2
+
_
_
RET2
RET2
RET1
+
C "DRY1" NC
C "DRY2" NC
UPPER LOWER
NOTE 6
_
AUX
+
AUX RESET
REMOTE
SW1
SW2
NO "REMOTE" C
_
DC
OUT1
+
OUT3
4
INPUT SELECT
TEMPORAL
2 3
STROBE SYNC
1
IN>OUT SYNC
ON
OUT2
4
INPUT SELECT
TEMPORAL
2 3
STROBE SYNC
1
IN>OUT SYNC
ON
OFF
ON
+
4
2 3
1
OUT1
ON
OUT4
4
2 3
1
ON
ON OFF
INP1
-
OUT2
OUT4
OUT3
FAULT
INP2
C "FAULT" NC
NO
C
NC
NOTE 5
+
+
_
_
OUT2 OUT3
OUT1
+
_
_
IN1
+
OUT4
+
RET1
ADDITIONAL PS-12/24-8 APPLIANCES OR
2.2K OHM EOLR
IN1 IN2
+
_
_
IN2
+
_
_
RET2
RET2
RET1
+
C "DRY1" NC
C "DRY2" NC
UPPER LOWER
NOTE 1: NAC Input Voltage 9.0 to 30.0VDC Constant. NOTE 2: OBSERVE DIP SWITCH SETTINGS
Input Selection Switch (Position 1) on OUT1 to OUT4 DIP Switches are shown in the "ON" Position allowing Input #1 to activate Outputs 1-4, Positions 2-4 are set for "WHEELOCK SYNC MODE"
NOTE 3: Jumper "RET 1-" to "IN 2-" and "RET 1+" to "IN 2+ " only on the Master PS-12/24-8. NOTE 4: Diagram shown with an output circuit (OUT4) on Master PowerPath used to synchronized the Remote PowerPaths. In
this configuration the Master PowerPath can only have three NAC circuits.
NOTE 5: Jumpers must be placed across "DRY 1" and "DRY 2" terminals when operating Power Supply using "IN 1" or "IN 2". NOTE 6: OBSERVE DIP SWITCH SETTINGS
Input Selection Switch (Position 1) on OUT 1 to OUT 4 DIP Switches are shown in the "ON" Position allowing Input #1 to activate Outputs 1-4. Positions 2-4 are set for "IN>OUT SYNC MODE".
P83862 M Sheet 19 of 23
Page 21
Example 16: Synchronized Multiple PS-12/24-8 Using a Master PS-12/24-8 (in the WHEELOCK SYNC MODE) With Audible Silence, and Using Input #1.
absolutely
NOTE 2
FACP
Programmed Audible Silence NAC
NOTE 1
NAC Input in Alarm Condition
_
AUX
+
-
+
AUX RESET
MASTER
-
+
SW1SW2
_
OUT2
OUT1
+
+
_
AUX
+
AUX RESET
REMOTE
SW1
SW2
_
OUT2
OUT1
+
+
_
AUX
+
AUX RESET
REMOTE
SW1SW2
_
OUT2 OUT3
OUT1
+
+
NO "REMOTE" C
_
NOTE 3
NO "REMOTE" C
_
NO "REMOTE" C
_
_
DC
OUT1
+
OUT3
4
INPUT SELECT
TEMPORAL
2 3
STROBE SYNC
1
IN>OUT SYNC
ON
OUT2
4
INPUT SELECT
TEMPORAL
2 3
STROBE SYNC
1
IN>OUT SYNC
ON
OFF
ON
+
4
2 3
1
OUT1
ON
OUT4
4
2 3
1
ON
ON OFF
INP1
-
OUT2
OUT4
OUT3
FAULT
INP2
C "FAULT" NC
NO
C
NC
NOTE 5
_
_
OUT3
+
IN1
+
OUT4
+
RET1
-
+
FACP EOLR
+
_
IN1 IN2
RET1
_
IN2
+
_
_
RET2
RET2
+
FACP EOLR
C "DRY1" NC
C "DRY2" NC
UPPER LOWER
NOTE 4
_
DC
OUT1
+
OUT3
4
INPUT SELECT
TEMPORAL
2 3
STROBE SYNC
1
IN>OUT SYNC
ON
OUT2
4
INPUT SELECT
TEMPORAL
2 3
STROBE SYNC
1
IN>OUT SYNC
ON
OFF
ON
+
4
2 3
1
OUT1
ON
OUT4
4
2 3
1
ON
ON OFF
INP1
-
OUT2
OUT4
OUT3
FAULT
INP2
C "FAULT" NC
NO
C
NC
NOTE 5
_
_
IN1
+
OUT4
OUT3
+
+
RET1
+
IN1 IN2
+
_
_
IN2
+
_
_
RET2
RET2
RET1
+
C "DRY1" NC
C "DRY2" NC
UPPER LOWER
-
NOTE 4
_
DC
OUT1
+
OUT3
4
INPUT SELECT
TEMPORAL
2 3
STROBE SYNC
1
IN>OUT SYNC
ON
OUT2
4
INPUT SELECT
TEMPORAL
2 3
STROBE SYNC
1
IN>OUT SYNC
ON
OFF
ON
+
4
2 3
1
OUT1
ON
OUT4
4
2 3
1
ON
ON OFF
INP1
-
OUT2
OUT4
OUT3
FAULT
INP2
C "FAULT" NC
NO
C
NC
NOTE 5
_
_
IN1
+
OUT4
+
+
RET1
+
_
IN1 IN2
RET1
_
IN2
+
_
_
RET2
RET2
+
C "DRY1" NC
C "DRY2" NC
UPPER LOWER
ADDITION AL PS-12/24-8 , APPLIACES OR
NOTE 1: NAC Input Voltage 9.0 to 30.0VDC Constant. NOTE 2: OBSERVE DIP SWITCH SETTINGS
Input Selection Switch (Position 1) on OUT1 to OUT4 DIP Switches are shown in the "ON" Position allowing Input #1 to activate Outputs 1-4, Positions 2-4 are set for "WHEELOCK SYNC MODE"
NOTE 3: Diagram shown with an output circuit (OUT4) on Master PowerPath used to synchronize the Remote PowerPaths. In
this configuration the Master PowerPath can only have three NAC circuits.
NOTE 4: OBSERVE DIP SWITCH SETTINGS
Input Selection Switch (Position 1) on OUT 1 to OUT 4 DIP Switches are shown in the "ON" Position allowing Input #1 to activate Outputs 1-4. Positions 2-4 are set for "IN>OUT SYNC MODE".
NOTE 5: Jumpers must be placed across “DRY1” and “DRY2” terminals when operating Power Supply using “IN1” or “IN2”.
P83862 M Sheet 20 of 23
Page 22
4.0 TROUBLESHOOTING
WARNING: THE PS-12/24-8 POWERPATH CONTAINS VOLTAGES THAT CAN CAUSE DEATH OR SERIOUS INJURY. ALWAYS OBSERVE PROPER ELECTRICAL SAFETY PRECAUTIONS AND WARNINGS.
Always follow good troubleshooting procedures:
When trouble occurs, observe all visual indications and note them.
If the problem is obvious or it can be located on the Troubleshooting Table, note it.
Always de-energize the POWERPATH completely (Remove both AC and DC power) before making changes to switch
settings or repairs.
NOTE: Changes in switch settings will not take affect until all power is removed and then restored to the POWERPATH.
While the POWERPATH is de-energized, perform a visual and hands on check of all terminals and wires to ensure proper
termination.
Table 4: Troubleshooting
Trouble Cause Action
INP1, INP2 LED’s do not light in ALARM INP1, INP2 LED’s Flashing Trouble on input Check input supervision Voltage.
OUT1,OUT2,OUT3,OUT4 LED’s do not light in ALARM FAULT LED Flashing INP1 INP2 trouble
AC LED OFF No AC power input Check AC Power Source. DC LED OFF No DC output Check wiring to the battery.
AC FAIL relay energizes (indication in remote location) No audible output in WHEELOCK SYNC MODE Horn, horn strobes, or strobes do not synchronize
CLASS “A” circuit is not functioning properly
CLASS “B” circuit is not functioning properly
BAT FAIL relay does not change state within 5 minutes.
No input signal on terminals
Check input and input wiring.
IN1+IN1-, IN2+IN2-
Check input EOLR.
No output Check INPUT SELECT DIP Switch on
corresponding OUTPUT DIP Switch.
Check inputs. (If LED’s INP1 or INP2 OUT1,OUT2,OUT3,OUT4 Trouble C “FAULT” NC terminals OPEN
flashing.)
Check outputs (if LED’s OUT1, OUT2,
OUT3, OUT4 flashing).
Check circuit connected to C “FAULT”
NC terminals.
Check wiring to AC power source. No AC power Check AC power source.
No input to IN2+,IN2- See Example 13 and 14 for proper
input connections. Improper MODE selection Improper appliances
Check MODE selection.
Check appliances to ensure proper type
for synchronization. For IN>OUT
MODE check input appliance (DSM,
SM or PS-12/24-8). Improper MODE selection or SW1/SW2 setting
Check to be certain MODE selection is
identical for each CLASS “A” output
circuit. CLASS “A” OUT1 uses outputs
1 and 3. Class “A” OUT2 uses outputs
2 and 4.
Check SW1 and SW2 on Logic Board
for “CLOSED” position. Improper MODE selection or SW1/SW2 setting
Power Supply voltage improperly set.
Check for proper MODE selection.
Check SW1 and SW2 on Logic Board
for “OPEN” position.
Set Potentiometer on Power Supply
Board to 28.0VDC for 24VDC
applications and 14.0VDC for 12VDC
applications.
P83862 M Sheet 21 of 23
Page 23
5.0 WHEELOCK INC. COMPATIBLE APPLIANCES
The Following is a list of appliances produced by Wheelock that are compatible with the PS-12/24-8 POWERPATH.
SYNCHRONIZING HORNS
AH-12 AH-24 AH-12WP AH-24WP NH-12/24 ----------
SYNCHRONIZING HORN STROBES AS-1215W AS-121575W AS-2415W AS-241575W AS-2430W AS-2475W AS-24110W AS-2415C AS-2430C AS-2475C AS-24100C AS-24MCW ASWP-2475W ---------­NS-1215W NS-121575W NS-2415W NS-241575W NS-2430W NS-2475W NS-24110W NS-24MCW
---------- NS4-241575W
---------- NS4-24MCW
SYNCHRONIZING STROBES RSS-1215W RSS-121575W RSS-2415W RSS-241575W RSS-2430W RSS-2475W RSS-24110W RSS-2415C RSS-2430C RSS-2475C RSS-24100C RSS-24MCW
APPLIANCES WITH SYNCHRONIZING STROBES MT-24-SLM CH70-24MCW CH70-2415W CH70-241575W CH70-2430W CH70-2475W CH70-24110W CH70-24MCW CH90-24100C CH90-2475C E70-2415W E70-24MCW E70-2430W E70-241575W E70-24110W E70-2475W E90-2430C E90-2415C E90-24100C E90-2475C ET70-2415W ET70-24MCW ET70-2430W ET70-241575W ET70-24110W ET70-2475W ET90-2430C ET70-24MCW ET90-24100C ET90-2415C SA-70-24-SL ET90-2475C SA-90-24-SL SA-70-SLM
CODED AUDIBLE APPLIANCES MIZ-12 MIZ-24 MT-12-LS MT-12/24 MT-24-LS MT-12-LSM MT-24-MS MT-24-LSM MT-12-SLM MT-24-IS CH70 MT-24-SLM CH70-2415W CH90 CH70-2430W CH70-241575W CH70-24110W CH70-2475W CH90-24100C CH90-2475C CSX10-24-DC CSXG10-24-DC
NON-SYNCHRONIZING APPLIANCES
MIZ-TC12 MIZ-TC24
P83862 M Sheet 22 of 23
Page 24
ANY MATERIAL EXTRAPOLATED FROM THIS DOCUMENT OR FROM WHEELOCK MANUALS OR OTHER DOCUMENTS DESCRIBING THE PRODUCT FOR USE IN PROMOTIONAL OR ADVERTISING CLAIMS, OR FOR ANY OTHER USE, INCLUDING DESCRIPTION OF THE PRODUCT’S APPLICATION, OPERATION. INSTALLATION AND TESTING IS USED AT THE SOLE RISK OF THE USER, AND WHEELOCK WILL NOT HAVE ANY LIABILITY FOR SUCH USE.
6.0 WARRANTY STATEMENT
Limited Warranty
Wheelock products must be used within their published specifications and must be PROPERLY specified, applied, installed, operated, maintained and operationally tested in accordance with these instructions at the time of installation and at least twice a year or more often and in accordance with local, state and federal codes, regulations and laws. Specification, application, installation, operation, maintenance and testing must be performed by qualified personnel for proper operation in accordance with all of the latest National Fire Protection Association (NFPA), Underwriters' Laboratories (UL), Underwriters’ Laboratories of Canada (ULC), National Electrical Code (NEC), Occupational Safety and Health Administration (OSHA), local, state, county, province, district, federal and other applicable building and fire standards, guidelines, regulations, laws and codes including, but not limited to, all appendices and amendments and the requirements of the local authority having jurisdiction (AHJ). Wheelock products when properly specified, applied, installed, operated, maintained and operationally tested as provided above are warranted against mechanical and electrical defects for a period of three years from date of manufacture (as determined by date code). Correction of defects by repair or replacement shall be at Wheelock's sole discretion and shall constitute fulfillment of all obligations under this warranty. THE FOREGOING LIMITED WARRANTY SHALL IMMEDIATELY TERMINATE IN THE EVENT ANY PART NOT FURNISHED BY WHEELOCK IS INSTALLED IN THE PRODUCT. THE FOREGOING LIMITED WARRANTY SPECIFICALLY EXCLUDES ANY SOFTWARE REQUIRED FOR THE OPERATION OF OR INCLUDED IN A PRODUCT. WHEELOCK MAKES NO REPRESENTATION OR WARRANTY OF ANY OTHER KIND, EXPRESS, IMPLIED OR STATUTORY WHETHER AS TO MERCHANTABILITY, FITNESS FOR A PARTICULAR PURPOSE OR ANY OTHER MATTER.
USERS ARE SOLELY RESPONSIBLE FOR DETERMINING WHETHER A PRODUCT IS SUITABLE FOR THE USER'S PURPOSES, OR WHETHER IT WILL ACHIEVE THE USER'S INTENDED RESULTS. THERE IS NO WARRANTY AGAINST DAMAGE RESULTING FROM MISAPPLICATION, IMPROPER SPECIFICATION, ABUSE, ACCIDENT OR OTHER OPERATING CONDITIONS BEYOND WHEELOCK'S CONTROL.
SOME WHEELOCK PRODUCTS CONTAIN SOFTWARE. WITH RESPECT TO THOSE PRODUCTS, WHEELOCK DOES NOT WARRANTY THAT THE OPERATION OF THE SOFTWARE WILL BE UNINTERRUPTED OR ERROR-FREE OR THAT THE SOFTWARE WILL MEET ANY OTHER STANDARD OF PERFORMANCE, OR THAT THE FUNCTIONS OR PERFORMANCE OF THE SOFTWARE WILL MEET THE USER'S REQUIREMENTS. WHEELOCK SHALL NOT BE LIABLE FOR ANY DELAYS, BREAKDOWNS, INTERRUPTIONS, LOSS, DESTRUCTION, ALTERATION, OR OTHER PROBLEMS IN THE USE OF A PRODUCT ARISING OUT OF OR CAUSED BY THE SOFTWARE.
THE LIABILITY OF WHEELOCK ARISING OUT OF THE SUPPLYING OF A PRODUCT, OR ITS USE, WHETHER ON WARRANTIES, NEGLIGENCE, OR OTHERWISE, SHALL NOT IN ANY CASE EXCEED THE COST OF CORRECTING DEFECTS AS STATED IN THE LIMITED WARRANTY AND UPON EXPIRATION OF THE WARRANTY PERIOD ALL SUCH LIABILITY SHALL TERMINATE. WHEELOCK IS NOT LIABLE FOR LABOR COSTS INCURRED IN REMOVAL, REINSTALLATION OR REPAIR OF THE PRODUCT BY ANYONE OTHER THAN WHEELOCK OR FOR DAMAGE OF ANY TYPE WHATSOEVER, INCLUDING BUT NOT LIMITED TO, LOSS OF PROFIT OR INCIDENTAL OR CONSEQUENTIAL DAMAGES. THE FOREGOING SHALL CONSTITUTE THE SOLE REMEDY OF THE PURCHASER AND THE EXCLUSIVE LIABILITY OF WHEELOCK.
IN NO CASE WILL WHEELOCK'S LIABILITY EXCEED THE PURCHASE PRICE PAID FOR A PRODUCT.
Limitation of Liability
WHEELOCK'S LIABILITY ON ANY CLAIM OF ANY KIND, INCLUDING NEGLIGENCE AND BREACH OF WARRANTY, FOR ANY LOSS OR DAMAGE RESULTING FROM, ARISING OUT OF, OR CONNECTED WITH THIS CONTRACT, OR FROM THE MANUFACTURE, SALE, DELIVERY, RESALE, REPAIR OR USE OF ANY PRODUCT COVERED BY THIS ORDER SHALL BE LIMITED TO THE PRICE APPLICABLE TO THE PRODUCT OR PART THEREOF WHICH GIVES RISE TO THE CLAIM. WHEELOCK'S LIABILITY ON ANY CLAIM OF ANY KIND SHALL CEASE IMMEDIATELY UPON THE INSTALLATION IN THE PRODUCT OF ANY PART NOT FURNISHED BY WHEELOCK. IN NO EVENT SHALL WHEELOCK BE LIABLE FOR ANY CLAIM OF ANY KIND UNLESS IT IS PROVEN THAT OUR PRODUCT WAS A DIRECT CAUSE OF SUCH CLAIM. FURTHER, IN NO EVENT, INCLUDING IN THE CASE OF A CLAIM OF NEGLIGENCE, SHALL WHEELOCK BE LIABLE FOR INCIDENTAL OR CONSEQUENTIAL DAMAGES. SOME STATES DO NOT ALLOW THE EXCLUSION OR LIMITATION OF INCIDENTAL OR CONSEQUENTIAL DAMAGES, SO THE PRECEDING LIMITATION MAY NOT APPLY TO ALL PURCHASERS.
1/02
P83862 M Sheet 23 of 23
Loading...