wheelock PS-12-24-8 INSTALLATION INSTRUCTIONS

POWERPATH
PS-12/24-8
(108114)
POWER BOOSTER
POWER SUPPLY
Installation Instructions
273 Branchport Avenue, Long Branch, NJ 07740-6899 Ph: (800) 631-2148 Fax: (732) 222-8707 Web Site: www.wheelockinc.com e-mail: info@wheelockinc.com
P83862 M
Copyright 2002 Wheelock, Inc. All rights reserved.
Thank you for using our products.
Use this product according to this instruction manual. Please keep this instruction manual for future reference.
TABLE OF CONTENTS
1.0 - INTRODUCTION AND SPECIFICATIONS
1.1 - INTRODUCTION 2
1.2 - SPECIFICATIONS 3
1.3 - TERMINOLOGY 3
1.4 - TERMINAL IDENTIFICATION 5
1.5 - LED STATUS 7
1.6 - BATTERY MAINTENANCE 7
2.0 - INSTALLATION INSTRUCTIONS 7
2.1 - UNPACKING 7
2.2 - MOUNTING 7
2.3 - WIRING 9
2.4 - RELAY STATUS CONNECTIONS 10
3.0 - OPERATION 11
3.1 - MODES OF OPERATION 11
3.2 - DIP SWITCH SETTINGS 11
3.3 - CLASS “B” OPERATION 12
3.4 - CLASS “A” OPERATION 15
3.5 - MASTER REMOTE OPERATION 19
4.0 - TROUBLESHOOTING 21
5.0 - COMPATIBLE APPLIANCES 22
6.0 - WARRANTY STATEMENT 23
FIGURE 1: POWERPATH PS-12/24-8 4
FIGURE 2: TERMINAL LOCATIONS 6
FIGURE 3: MOUNTING DIMENSIONS 8
FIGURE 4: BAT FAIL/AC FAIL DIAGRAM 10
LIST OF FIGURES
FIGURE 5: OUTPUT DIP SWITCH(S) 11
TABLE 1: TERMINAL IDENTIFICATION 5
TABLE 2: LED STATUS DESCRIPTION 7
TABLE 3: DIP SWITCH SELECTION 9
LIST OF TABLES
TABLE 4: TROUBLESHOOTING 19
P83862 M Sheet 1 of 23
NOTE: All CAUTIONS and WARNINGS are identified by the symbol
. All WARNINGS are printed in bold capital
letters.
WARNING: READ THIS INSTRUCTION MANUAL CAREFULLY. FAILURE TO COMPLY WITH ANY OF THE FOLLOWING INSTRUCTIONS, CAUTIONS, AND WARNINGS COULD RESULT IN IMPROPER APPLICATION AND/OR OPERATION OF THESE PRODUCTS IN AN EMERGENCY SITUATION, WHICH COULD RESULT IN PROPERTY DAMAGE AND SERIOUS INJURY OR DEATH TO YOU AND/OR OTHERS.
1.0 INTRODUCTION AND SPECIFICATIONS
1.1 INTRODUCTION
The PS-12/24-8 POWERPATH is an 8 AMP, 12/24VDC, filtered and regulated, supervised remote power supply/charger used for supervision and expanded power driving capability for Fire Alarm Notification Appliance Circuits. The PS-12/24-8 may be connected to any 12 or 24VDC Fire Alarm Control Panel (FACP) by using a Notification Appliance Circuit (NAC) or a “Dry Contact”. Primary applications include NAC expansion (supports ADA requirements) and auxiliary power to support system accessories. This unit provides filtered and regulated 12 or 24VDC, 8 AMP supply to up to four (4) Class B, two (2) Class “A”, or two (2) Class “B” and one (1) Class “A” Notification Appliance Circuits. Additionally, an auxiliary power output that can be reset is provided. The PS-12/24-8 also contains a battery charger capable of charging either 7 or 12 AMP/Hour (AH) of battery backup. The PS-12/24-8 can only provide a maximum load of 8 amperes for 5 minutes with a 7AH battery or 15 minutes with a 12AH battery.
Two FACP NAC circuits or two “Dry” contact closures can be connected to the POWERPATH inputs. These inputs can then be directed to control supervision and power delivery to any combination of the four (4) outputs.
Each output is rated at 2 AMPS (either Class "A" or Class "B") and can be programmed to generate a steady or Code 3 Temporal horn sound and a strobe output under alarm condition. A maximum 4 AMP output is achieved by paralleling 2 outputs (Class "B" only).
The PS-12/24-8 under non-alarmed condition provides independent loop supervision for Class “A” and Class “B” FACP NAC circuits. In the event of a loop trouble, the FACP will be notified via the POWERPATH steered input (IN1 or IN2). In addition there are common trouble output terminals (used to indicate a loop trouble) and common trouble input terminals (used generically by any initiating circuit).
Wheelock horns/strobes, strobes and horns with synchronizing capability can be utilized with the PS-12/24-8. Audibles can be silenced with only two wires. Additionally, the POWERPATH can provide a temporal coded signal for appliances that can utilize it.
P83862 M Sheet 2 of 23
1.2 SPECIFICATIONS
Approvals:
UL Listed 864 Control for use with Fire Protective Signaling
MEA approved – NYC Dept. of Buildings
California State Fire Marshall (CSFM) approved
NFPA 72 compliant
Inputs:
115VAC, 60Hz, 3.2 AMP Operating Power in Alarm
12/24VDC Battery Backup Connection
Two (2), 12 or 24VDC NAC Initiating Circuits (9-30VDC at 5mA)
Two (2) “Dry” Contact initiating Circuits
Accepts two Class “A” or two Class “B” circuit inputs
Built in battery charger for sealed lead acid or gel type batteries
Outputs:
Switch selectable 12VDC or 24VDC power limited outputs
8 AMP continuous supply current at 12VDC or 24VDC for 5 minutes with 7AH battery or 15 minutes with 12AH
battery.
Capable of four (4), Class "B" circuits (2 Amps each)
Two outputs may be paralleled for a maximum output of 4 AMPS on a circuit (Class "B" only)
Capable of two (2) Class “A” circuits (2 Amps each).
Capable of one (1) Class “A” circuit (2 Amps) and two (2) Class “B” circuits (2 Amps each)
Code 3 or constant voltage output generation
Built-in Wheelock synchronization mode that can be fed to any or all of the output circuits
Input and output can be synchronized with “IN>OUT SYNC” mode (SM, DSM or 2
Audible silence capability
Filtered and electronically regulated output
50mA auxiliary output with reset capability
Supervision:
Compatible with 12 or 24VDC FACP
Signaling appliance loops are supervised and steered to either IN1 or IN2
22K OHM, ¼ Watt End-of-Line-Resistor (EOLR) for supervision of all outputs
Common input and output trouble circuits
Automatic switchover to standby battery when AC fails
Thermal and short circuit protection with auto reset
Input and output status LED indicators
AC fail supervision (Form “C” contact, 1 AMP 28VDC)
Battery presence and low battery supervision (Form “C” contact, 1 AMP 28VDC)
Auxiliary output fail supervision (Form “C” contact, 1 AMP 28VDC)
Ground Fault Detection (factory installed UL Listed 22K OHM resistor /wire assembly connected from positive (+)
1.3 TERMINOLOGY
AUX to chassis ground)
CLASS “A” = STYLE Z CLASS “B” = STYLE Y FACP = Fire Alarm Control Panel EOLR = End-of-Line Resistor NAC = Notification Appliance Circuit SM = Wheelock Sync Module with single output. DSM = Wheelock Sync Module with two outputs. C = Common NC = Normally Closed NO = Normally Open AH = Ampere/Hour
nd
PS-12/24-8 is required)
P83862 M Sheet 3 of 23
Figure 1:
POWERPATH PS-12/24-8
22K OHM RESISTOR/WIRE ASSEMBLY
BAT FAIL
NC C NO
AC FAIL
NC C NO
OPEN = 24V SW1 CLOSED = 12V
POWER SUPPLY
TRANSFORMER
DC
SW1
SW2
+
DETAIL A
_
NO "REMOTE" C
AUX
+
AUX RESET
LOGIC BOARD
_
_
OUT2
OUT1
+
CLOSED
OUT2
INP2
AC
OUT3
AC
UPPER
LOWER
OUT4
FAULT
"FAULT" NC C
NO
WHITE LEAD
BLACK LEAD
C
NC
115 VAC, 60Hz
GREEN LEAD
GROUND
+
-
IN1 IN2
+
OUT3
OUT4
_
RET1
_
BAT+-
ON
ON
ON OFF
+
RET2
+
AC
4
2 3
1
OUT1
4
2 3
1
INP1
_
C "DRY1" NC
IN2
_
RET2
C "DRY2" NC
DC
_
DC
+
_
OUT3
+
+
OUT
ON
4
ON
ON
OFF
_
OUT1
4
INPUT SELECT
TEMPORAL
2 3
STROBE SYNC
1
IN>OUT SYNC
OUT2
4
INPUT SELECT
TEMPORAL
2 3
STROBE SYNC
1
IN>OUT SYNC
IN1
+
RET1
3.2 AMP
OPEN
DETAIL B
P83862 M Sheet 4 of 23
1.4 TERMINAL IDENTIFICATION
b
Table 1: Terminal Identification
Balloon Identification Terminal Function/Description
Numbers (Figure 2) Identification Logic Board
1
2
3 4 5
6
7
8
9
10
11 Power Supply Board 12
13
14
IN1+,IN1- These terminals connect to the input voltage source (i.e. 12VDC or 24VDC
FACP). The FACP will supply a voltage from 9-30VDC at 5mA. During the alarm condition these inputs will cause the designated outputs to drive the notification appliances (designated outputs are set by output DIP switch banks). During Stand-by on a FACP, a trouble condition on the designated loop will cause these inputs to trip the FACP by opening the FACP loop. Alarm condition always overrides trouble to drive output indicating appliances.
RET1+, RET1- EOLR is connected on these terminals corresponding to IN1+ and IN1-, or the
loop may be continued to other power supplies or appliances before terminating. IN2+, IN2- Same as IN1+, IN1- for corresponding terminals. RET2+, RET2- Same as RET1+, RET1- for corresponding terminals. C “DRY1” NC Dry contacts are used to actuate the designated outputs. Contacts are normally
closed and actuate the power supply on contact Open. Designated outputs
correspond to IN1+,IN1-. NOTE: FACP NAC circuit cannot energize the power
supply by these contacts. NOTE: When these terminals are not in use, a jumper
must be connected across them. C “DRY2” NC Operates the same as IN2+,IN2- for corresponding terminals. When these
terminals are not in use, a jumper must be connected across them.
+OUT1­+OUT2­+OUT3­+OUT4-
Indicating appliances are connected to these outputs (See Examples in Operation
Section). Each output can supply a maximum load of 2 AMPS and can be
individually programmed for Normal Mode, Temporal Mode, IN>OUT SYNC
Mode, or WHEELOCK SYNC Mode. The outputs can be configured as four
Class "B" circuits, two Class "A" circuits, or two Class "B" and one Class "A"
circuits. Each Class "A" or Class "B" circuit is 2 Amps. Outputs are controlled
by a designated input (INPUT 1 or 2) as selected by the DIP switch for that
output. NOTE: When the panel has been set to synchronization mode, IN1 is
used for strobe activation and IN2 is used for audible silence. Individual output
control is disabled. “NC” “C” “NO (COMMON
Typically used to trigger remote alerts or other reporting appliances. Form “C”
contacts rated 28VDC at 1 AMP. TROUBLE OUTPUT) C “FAULT” NC (COMMON TROUBLE
Typically used to report AC or BAT Fail. An open circuit across this pair of
terminals will cause IN1 and IN2 to simultaneously signal a trouble condition to
the FACP. INPUT)
- AUX + This output is capable of 50mA and can be reset by a momentary switch on the
logic board or can be reset remotely by using the NO “REMOTE”C terminals. NO”REMOTE”C Dry contact closure on these terminals causes –AUX+ output to reset.
+BAT- Stand-by battery input. Use two 12VDC batteries connected in series for 24VDC
operation, or a single 12VDC battery for 12VDC operation. BAT FAIL NO, C, NC
Form “C” dry contacts used to signal low battery or loss of battery voltage. With
attery voltage present terminals NO, C are open, terminals C, NC are closed. With no battery voltage present terminals NO, C are closed, terminals C, NC are open. Form “C” contacts rated at 28VDC at 1 AMP.
AC FAIL NO, C, NC
Form “C” dry contacts used to signal loss of AC voltage. With AC present terminals NO, C are open, terminals C, NC are closed. With no AC present terminals NO, C are closed, terminals C, NC are open. Form “C” contacts rated at 28VDC at 1 AMP
P83862 M Sheet 5 of 23
Figure 2:
Terminal Locations
N
B A
C
13
14
T
C
F A
N
I
L
O
N
A
C
C
C
F A
N
I
L
O
D
A
E
C
L
T
A
R
Y
O
O
U
P
B
T
L
I
E
O N
OPEN = 24V SW1 CLOSED = 12V
J1
SW2
DC
SW1
10 11
_
AUX
NO "REMOTE" C
+
AUX RESET
+
DC
+
BAT
-
AC
AC
AC
12
_
DC
+
ON
ON
ON
OFF
4
3
2
1
4
3
2
1
OUT1
INPUT SELECT
TEMPORAL STROBE SYNC IN>OUT SYNC
OUT2
INPUT SELECT
TEMPORAL STROBE SYNC IN>OUT SYNC
1
OUT3
OUT4
ON
ON
ON OFF
3
4
3
2
1
OUT1
4
3
2
1
INP1
5
OUT2
INP2
OUT3
OUT4
FAULT
C N " T
L U A F
" C
O N
C
C N
9
8
+
OUT1
+
OUT2
_
+
OUT3
_
_
7
+
OUT4
_
_
IN1
IN1 IN2
+
RET1
_
RET1
+
2
+
RET2
IN2
+
4
_
RET2
C "DRY1" NC
_
C "DRY2" NC
6
UPPER
LOWER
P83862 M Sheet 6 of 23
1.5 LED STATUS
Table 2 lists status of the LED indicators. The ALARM condition occurs when the input causes the output circuits to energize. TROUBLE condition occurs when the circuit is no longer supervised correctly. NOTE: An alarm condition overrides a trouble condition.
Table 2: LED Status Description
LED
Logic Board
OUT1 STANDBY ALARM TROUBLE OUT2 STANDBY ALARM TROUBLE OUT3 STANDBY ALARM TROUBLE OUT4 STANDBY ALARM TROUBLE INP1 STANDBY ALARM TROUBLE INP2 STANDBY ALARM TROUBLE FAULT -------- TROUBLE --------
Power Supply Board
AC No AC AC Present -------­DC No DC DC Present --------
1.6 BATTERY MAINTENANCE
Battery Replacement: Power-Sonic (or equal) 12VDC, replace with new batteries every four (4) years or as needed if battery will no longer accept full charge. Two 12V batteries are required for 24VDC setting. Use either a 7AH battery for 5 minutes of alarm or a 12AH battery for 15 minutes of alarm.
NOTE: Battery compartment measures 4-1/2" High X 11-1/2" Wide X 4-1/2" Deep.
2.0 INSTALLATION INSTRUCTIONS
NOTE: The PS-12/24-8 POWERPATH shall be installed in accordance with the National Electrical Code (NEC) and all
applicable state and local regulations.
2.1 UNPACKING
The POWERPATH was carefully checked before leaving the factory. Inspect shipping container and unit carefully for indications of improper handling. If damage is detected, make an immediate claim to the carrier.
Remove the POWERPATH from the shipping container and check that the door lock keys, door lock, and battery connection wires are inside. Make sure the transformer, Power Board and Logic Board are securely mounted to the rear of the enclosure.
2.2 MOUNTING
WARNING: TO REDUCE THE RISK OF FIRE OR ELECTRIC SHOCK, DO NOT EXPOSE THIS UNIT TO RAIN
OR MOISTURE.
CAUTION: This product is not intended for use in hazardous locations as defined by the National Electrical Code (NEC) and
by the National Fire Protection Association (NFPA).
Mount the POWERPATH in the desired location using the mounting dimensions in Figure 3.
Mount the panel in a location that does not exceed a temperature range of 0° C to 49° C (32° F to 120° F) and a humidity equal to 10% to 85% at 30° C (86° F) non-condensing.
When mounting on interior walls, use proper screw anchors in plaster. When mounting to concrete, especially when moisture is expected, first attach a piece of ¾ inch plywood to the concrete surface. Attach the POWERPATH to the plywood.
CAUTION: The POWERPATH panel shall be mounted in a location within the environmental limits specified in the latest
UL Standard for indoor control panels.
OFF
ON
Blinking
-------- -------- --------
P83862 M Sheet 7 of 23
Loading...
+ 16 hidden pages