wheelock NPS INSTALLATION INSTRUCTIONS

273 Branchport Avenue Long Branch, NJ 07740 (800) 631-2148 www.wheelockinc.com Thank you for using our products.
INSTALLATION INSTRUCTIONS
Use this product according to this instruction manual. Please keep this instruction manual for future reference.
MODEL: SERIES NPS
GENERAL:
Multipurpose Push Stations (NPS) for applications that need Normally Open or Normally Closed contacts. The NPS can be used for manual activation of SAFEPATH and SAFEPATH4 Voice Evacuation Systems prerecorded messages. The NPS can also be used to manually activate a message in the event of an emergency or for alerting.
NOTE: All CAUTIONS and WARNINGS are identified by the symbol . All warnings are printed in bold capital letters.
NOTE: Push Stations with the suffix code –039 with the wording “Fire” have not been tested to any UL Standard.
WARNING: PLEASE READ THESE INSTRUCTIONS CAREFULLY BEFORE USING THIS PRODUCT. FAILURE TO COMPLY WITH ANY OF THE FOLLOWING INSTRUCTIONS, CAUTIONS AND WARNINGS COULD RESULT IN IMPROPER APPLICATION, INSTALLATION AND/OR OPERATION OF THESE PRODUCTS IN AN EMERGENCY SITUATION, WHICH COULD RESULT IN PROPERTY DAMAGE AND SERIOUS INJURY OR DEATH TO YOU AND/OR OTHERS.
WIRING INFORMATION:
OUT
1
3
OUT
NO
IN
2
4
NC
IN
Figure 1: Terminal Block
All terminals accept (2) two #12 to #18 American Wire Gauge (AWG).
250VDC - 1 AMP 600VAC - 3 AMPS
WARNING: DO NOT USE THE SERIES NPS PUSH STATIONS IN INSTALLATIONS WHERE TEMPERATURES MAY FALL OUTSIDE OF THE UL LISTED TEMPERATURE [0˚ C (32˚ F) TO 49˚ C (120˚ F)] RANGE AS DAMAGE TO, OR FAILURE MAY RESULT.
WARNING: FAILURE TO FOLLOW THE INSTALLATION INSTRUCTIONS OR TO SUBSTITUTE ELECTRICAL RIGID CONDUIT FITTINGS THAT DO NO COMPLY WITH CURRENT PRACTICES ADAPTED BY NEC, NFPA AND ANSI CODES MAY RESULT IN LOSS OF PROTECTION FROM WATER OR DUST.
WARNING: IN ALL AREAS WHERE FREQUENT WASH DOWNS OCCUR, STAND OFF BLOCK MUST BE INSTALLED.
Copyright 2006 Cooper Wheelock, Inc. All rights reserved.
P84249 F
Sheet 1 of 4
FEATURES:
- Available in five colors: Red, Green, Yellow, White
or Blue
- Custom wording available
- Polycarbonate faceplate
- Stainless steel backplate
- UL 2017 listed switch assembly
- ADA Compliant
MOUNTING INSTRUCTIONS:
WHEELOCK RECOMMENDS THE USE OF THIS SPACER (NOT PROVIDED) FOR SWITCH CLEARANCE ON STANDARD SINGLE GANG BOXES
BACKPLATE ASSEMBLY
(2) 6-32 X 1" SCREWS (SUPPLIED)
- Mounts to single-gang electrical backbox.
- Interchangeable or replaceable Normally Open (NO) and Normally Closed (NC) single pole, single throw gold plated contact blocks rated for 3 amps @ 600 VAC or 1 amp @ 250 VDC.
- Can be reset by depressing the "Push" button, and turning clockwise a 1/4 turn.
- Measurements: 5" H x 3-1/4" W x 1-1/2" D.
STATION HOUSING GREEN, YELLOW, WHITE, BLUE OR RED
STATION LABEL
MOUNTING SCREW
(SUPPLIED) PUSH/TURN RESET BUTTON
Figure 2: Overview of Assembly
SEPARATION OF TERMINAL ASSEMBLY. FROM BUTTON ASSEMBLY IS AS FOLLOWS. GRASP TERMINAL HOUSING AND USING THUMB APPLY PRESSURE DOWNWARD. REMOVE TERMINAL.
REMOVAL OF TERMINAL BLOCK FROM TERMINAL HOUSING. INSERT SMALL SCREWDRIVER AS SHOWN AND PRY UPWARD, REMOVE TERMINAL.
Figure 3: Back view of Push Station
.
NOTE: To provide adequate clearance for installation, one of the following is recommended: System Tech. Inc. (STI) #102722
Spacer, or Raco #660 W/1/2" K.O. and Raco #653 Extension Ring. Also Raco #696 Masonry Box.
NOTE: Additional Normally Open, NPS-NO (0523) or Normally Closed, NPS-NC (0524) can be purchased separately.
P84249 F
Sheet 2 of 4
Loading...
+ 2 hidden pages