wheelock NH INSTALLATION INSTRUCTIONS

273 Branchport Avenue Long Branch, NJ 07740 Thank you for using our products. (800) 631-2148 (USA) (800) 397-5777 (CANADA) INSTALLATION INSTRUCTIONS www.wheelockinc.com SERIES NH AUDIBLE APPLIANCES
Use this product according to this instruction manual. Please keep this instruction manual for future reference.
GENERAL:
Wheelock’s Series NH Audible Appliances provide a selectable continuous or Code 3 Horn tone when connected directly to the Fire Alarm Control Panel (FACP). They can also provide a synchronized Code 3 Horn tone when used in conjunction with a Sync Module (SM), Dual Sync Module (DSM) or the Power Supply (PS-12/24-8 UL ONLY). The NH Appliances are UL Listed under Standard 464 for Audible Signal Appliances. The NH Appliances are also ULC Listed under Standard CAN/ULC-S525-99 for Audible Signaling Devices for Fire Alarm Systems. They are listed for indoor use only
and equipped with a NH Mounting Plate that can be mounted to single-gang, double-gang, 4” backbox, 100mm European backbox or SHBB surface backbox (See Mounting Options).
Series NH Appliances can be field set for High (HI) or Low (LO) dBA sound output.
The NH models are designed for use with either filtered DC (VDC) or unfiltered Full-Wave-Rectified (VRMS) input voltage. All inputs are polarized for compatibility with standard reverse polarity supervision of circuit wiring by a FACP.
NOTE: All CAUTIONS and WARNINGS are identified by the symbol
. All warnings are printed in bold capital letters
WARNING: THE NH AUDIBLE APPLIANCE IS A "FIRE ALARM DEVICE - DO NOT PAINT."
NOTE: All Canadian Installations should be in accordance with the Canadian Standard for the Installation of Fire Alarm Systems
- CAN/ULC-S524-01 and Canadian Electrical Code, Part 1. Final acceptance is subject to Authorities Having Jurisdiction.
WARNING: PLEASE READ THESE INSTRUCTIONS CAREFULLY BEFORE USING THIS PRODUCT. FAILURE TO COMPLY WITH ANY OF THE FOLLOWING INSTRUCTIONS, CAUTIONS AND WARNINGS COULD RESULT IN IMPROPER APPLICATION, INSTALLATION AND/OR OPERATION OF THESE PRODUCTS IN AN EMERGENCY SITUATION, WHICH COULD RESULT IN PROPERTY DAMAGE AND SERIOUS INJURY OR DEATH TO YOU AND/OR OTHERS.
WARNING: THE AUDIBLE HORN APPLIANCES MUST BE FIELD SET TO THE DESIRED TONE AND dBA
SOUND OUTPUT LEVEL BEFORE THEY ARE INSTALLED. THIS IS DONE BY PROPERLY INSERTING A JUMPER PLUG IN ACCORDANCE WITH THESE INSTRUCTIONS. INCORRECT SETTINGS WILL RESULT IN IMPROPER PERFORMANCE, WHICH COULD RESULT IN PROPERTY DAMAGE AND SERIOUS INJURY OR DEATH TO YOU AND/OR OTHERS.
SPECIFICATIONS:
Table 1: UL/ULC Listed Models and Ratings
Model
NH-12/24 24 16.0-33.0VDC 20.0-31.0VDC 0.018 0.044 0.018 0.033
16.0-33.0VRMS 20.0-31.0VRMS 0.045 0.075 0.045 0.075 12 8.0-17.5VDC 10.5-15.6VDC 0.012 0.021 0.012 0.021
8.0-17.5VRMS 10.5-15.6VRMS 0.030 0.054 0.030 0.054
Regulated
Voltage
(VDC/VRMS)
UL
Voltage
ULC Voltage
CAN/ULC-S525-99
UL Max RMS Current
(AMPS)
Lo Hi Lo Hi
ULC Rated Average
Current (AMPS)
Copyright 2005 Wheelock, Inc. All rights reserved.
P83600 K
Sheet 1 of 6
Table 2: dBA Sound Output for 24VDC Models
Description
Continuous Horn
Code 3 Horn
Volume
16.0VDC 24VDC 33.0VDC 20.0VDC 24VDC 31.0VDC Low 77 81 83 88 90 91 High 83 87 90 93 95 96 Low 72 76 79 88 90 91 High 79 82 86 93 95 96
Reverberant dBA
Per UL 464
ULC Anechoic dBA Per CAN/ULC-
S525-99
Table 2A: dBA Sound Output for 12VDC Models
Description
Continuous Horn
Code 3 Horn
Volume
8.0VDC 12VDC 17.5VDC 10.5VDC 12VDC 15.6VDC Low 72 76 80 83 84 85 High 78 83 86 88 89 90 Low 67 72 74 83 84 85 High 75 79 82 88 89 90
Reverberant dBA
Per UL 464
ULC Anechoic dBA Per CAN/ULC-
S525-99
Table 2B: ULC Directional Characteristics
20.0-31.0V Rated output 95dBA
10.5-15.6V Rated output 89 dBA
NOTES:
-3 dBA: 48 degrees left, 41 degrees right
-6 dBA: 50 degrees left, 58 degrees right
-3 dBA: 45 degrees left, 33 degrees right
-6 dBA: 52 degrees left, 45 degrees right
1. Regulated Voltage: NH Audible Appliances are UL Listed to operate over a Voltage Range Limit from 8.0VDC to
17.5VDC for 12VDC applications or 16.0VDC to 33.0VDC for 24VDC applications using filtered DC or unfiltered Full­Wave-Rectified (FWR) input voltage. The ULC Voltage Range for NH Audible Appliances is 10.5-15.6 for 12VDC applications and 20.0-31.0 for 24VDC applications using filtered DC or unfiltered Full-Wave-Rectified (FWR) input voltage.
2. All models are UL Listed for indoor use with a temperature range of +0oC to +49oC (+32oF to +120o F) and maximum humidity of 93% ± 2% RH.
WARNING: CHECK THE MINIMUM AND MAXIMUM OUTPUT OF THE POWER SUPPLY AND STANDBY
BATTERY AND SUBTRACT THE VOLTAGE DROP FROM THE CIRCUIT WIRING RESISTANCE TO DETERMINE THE APPLIED VOLTAGE TO THE SIGNALING APPLIANCE.
WARNING: MAKE SURE THAT THE TOTAL RMS CURRENT AND TOTAL AVERAGE CURRENT REQUIRED BY ALL APPLIANCES THAT ARE CONNECTED TO THE SYSTEM’S PRIMARY AND SECONDARY POWER SOURCES, SIGNALING CIRCUITS, SM, DSM SYNC MODULES AND WHEELOCK’S POWER SUPPLIES DO NOT EXCEED THE POWER SOURCES’ RATED CAPACITY OR THE CURRENT RATINGS OF ANY FUSES ON THE CIRCUITS TO WHICH THESE APPLIANCES ARE WIRED. OVERLOADING POWER SOURCES OR EXCEEDING FUSE RATINGS COULD RESULT IN LOSS OF POWER AND FAILURE TO ALERT OCCUPANTS DURING AN EMERGENCY, WHICH COULD RESULT IN PROPERTY DAMAGE AND SERIOUS INJURY OR DEATH TO YOU AND/OR OTHERS.
When calculating the total current: Use Table 1 to determine the highest value of “RMS Current” or “Rated Average Current” for an individual horn (across the expected operating voltage range of the horn) then multiply these values by the total number of horns; be sure to add the currents for any other appliances, including visual (strobe) signaling appliances, powered by the same source and include any required safety factors.
CAUTION: Audible Horn appliances set for Code 3 tone are not designed to be used on coded systems in which the applied
voltage is cycled on and off.
WARNING: FOR UL APPLIANCES THESE APPLIANCES WERE TESTED TO THE OPERATING VOLTAGE LIMITS OF 16-33 VOLTS FOR 24V APPLICATIONS AND 8.0-17.5 VOLTS FOR 12V APPLICATIONS USING FILTERED (DC) OR UNFILTERED FULL-WAVE-RECTIFIED (FWR). DO NOT APPLY 80% AND 110% OF THESE VOLTAGE VALUES FOR SYSTEM OPERATION.
P83600 K
Sheet 2 of 6