wheelock MTWP-2475, MTWP-24MCCH, MTWP-24MCWH INSTALLATION INSTRUCTIONS

273 Branchport Avenue Long Branch, NJ 07740 Thank you for using our products. (800) 631-2148 (USA) (800) 397-5777 (CANADA) INSTALLATION INSTRUCTIONS www.cooperwheelock.com MULTITONE STROBE WEATHERPROOF APPLIANCES
Use this product according to this instruction manual. Please keep this instruction manual for future reference.
The Multitone Strobe Weatherproof Appliances are UL Listed under Standard 1638 (Visual Signaling Appliances) and Standard 1971 (Signaling Devices for the Hearing Impaired) for indoor/outdoor use, Fire Protective Service and UL Standard 464 for Audible Signal Appliances. Models with amber, blue, green or red lens are not UL approved. The MTWP-2475W is ULC Listed under Standard CAN/ULC-S526-02 for Visual Signaling and under Standard CAN/ULC-S525-99 for Audible Signal Devices for Fire Alarm Systems Appliance . The Multi-High-Candela strobe provides two selectable light output intensities in one unit. An outdoor backbox is required for outdoor installation. The Multitone Strobe Appliances use a xenon flashtube with solid state circuitry enclosed in a polycarbonate lens to provide maximum visibility and reliability for effective visible signaling.
Multitone Strobe Appliances can be field set to produce any one of eight commonly used alarm tones. Sound output can be field set to provide either HIGH (HI) dBA or STANDARD (STD) dBA sound output level.
All Multitone Strobe models are designed for use with either filtered DC or unfiltered full-wave-rectified (FWR) input voltage. The Multitone Strobe Appliances have separate input terminals for alarm tone activation and strobe activation. Shunt wires are provided to operate both the alarm tone and the strobe simultaneously on a single input circuit (See Wiring Diagram). All inputs are polarized for compatibility with standard reverse polarity supervision of circuit wiring by a fire alarm control panel (FACP).
NOTE: All Canadian installations should be in accordance with the Canadian Standard for the Installation of Fire Alarm Systems, CAN/ULC-S524-01 and the Canadian Electrical Code, Part 1. Final acceptance is subject to authorities having jurisdiction (AHJ).
WARNING: PLEASE READ THESE INSTRUCTIONS CAREFULLY BEFORE USING THIS PRODUCT. FAILURE TO COMPLY WITH ANY OF THE FOLLOWING INSTRUCTIONS, CAUTIONS AND WARNINGS COULD RESULT IN IMPROPER APPLICATION, INSTALLATION AND/OR OPERATION OF THESE PRODUCTS IN AN EMERGENCY SITUATION, WHICH COULD RESULT IN PROPERTY DAMAGE AND SERIOUS INJURY OR DEATH TO YOU AND/OR OTHERS.
CAUTION: NOT RECOMMENDED FOR USE AT REFRIGERATOR / FREEZER DOOR ENTRANCES OR OTHER AREA WITH PERSISTENT CONDENSATION.
SPECIFICATIONS:
Table 1: UL Listed Models and Ratings
Voltage
(VDC/VRMS)
Regulated
Rated
Voltage
(VDC/VRMS)
Rated Strobe Candela (cd) Model
At -40° C (UL1638)
(UL1971)
Reverberant
dBA
at 10 Feet
MTWP-2475W 24 16.0-33.0 115 30/180* 76-94 MTWP-2475C 24 16.0-33.0 115 30/180* 76-94 MTWP-24MCCH 24 16.0-33.0 50/75 115/177 76-94 MTWP-24MCWH 24 16.0-33.0 65/90 135/185 76-94
*180 is on Axis only.
Table 1A: ULC Listed Models and Ratings
Rated Strobe
Candela
(cd)
Anechoic
dBA at 10
Feet
NOTES:
Model
Regulated
Voltage
(VDC/VRMS)
Rated
Voltage
(VDC/VRMS)
MTWP-2475W 24 20-31.0 30 85-100
1. Strobes will produce 1 flash per second over the "Regulated Voltage" range.
2. All models are listed for indoor and outdoor use. UL 1971 is tested from a temperature range of 32ºF to 120ºF (0ºC to 49ºC). UL 1638 is tested from a temperature range of -40ºF to +150ºF (-40ºC to +66ºC) with a maximum humidity of 98% ±2% RH.. The effect of shipping and storage temperatures shall not adversely affect the performance of the appliances when it is stored in the original cartons and is not subjected to misuse or abuse
3. Candela ratings in Table 1 are rated for clear lens. Derate approximately 24% for amber, 55% for green, 70% for blue and 80% for red.
WARNING: THESE APPLIANCES WERE TESTED TO THE REGULATED VOLTAGE LIMITS OF 16.0-33.0 VOLTS FOR 24V MODELS USING FILTERED DC OR
UNFILTERED FULL-WAVE-RECTIFIED VOLTAGE. DO NOT APPLY VOLTAGE OUTSIDE OF THIS RANGE.
WARNING: CHECK THE MINIMUM AND MAXIMUM OUTPUT OF THE POWER SUPPLY AND STANDBY BATTERY AND SUBTRACT THE VOLTAGE DROP FROM THE CIRCUIT WIRING RESISTANCE TO DETERMINE THE APPLIED VOLTAGE TO THE STROBES. THE MAXIMUM WIRE IMPEDENCE BETWEEN STROBES SHALL NOT EXCEED 35 OHMS.
CAUTION: These notification appliances are UL Listed as “Regulated”. They are intended to be used with FACPs whose notification circuits are ULListed as
“Regulated.” These appliances shall not be used on UL Listed “Special Application” notification circuits unless the appliances are identified to be compatible in the installation instructions of the FACP or unless the FACP is identified to be compatible in this instruction manual.
Use Tables 2, 2A and 2B to determine the highest value of “Rated Current” for an individual Multitone Strobe (across the expected operating voltage range of the Multitone Strobe). Add strobe current from Table 2B a audible appliance current from Table 2 and Table 2A to obtain total current for each unit, if the strobe and
Copyright 2007 Cooper Wheelock. All rights reserved. P84870 E
Sheet 1 of 6
audible are wired to operate in unison on a single circuit. Be sure to add the currents for any other appliances, including audible signaling appliances, powered by the
A
same source and include any required safety factors.
NOTE: The maximum number of strobes on a single notification appliance circuit shall not exceed 50.
WARNING: MAKE SURE THAT THE TOTAL RATED CURRENT REQUIRED BY ALL APPLIANCES THAT ARE CONNECTED TO THE SYSTEM’S PRIMARY AND SECONDARY POWER SOURCES, APPLIANCE CIRCUITS, SM, DSM SYNC MODULES AND WHEELOCK POWER SUPPLIES DOES NOT EXCEED THE POWER SOURCES’ RATED CAPACITY OR THE CURRENT RATINGS OF ANY FUSES ON THE CIRCUITS TO WHICH THESE APPLIANCES ARE WIRED. OVERLOADING POWER SOURCES OR EXCEEDING FUSE RATINGS COULD RESULT IN LOSS OF POWER AND FAILURE TO ALERT OCCUPANTS DURING AN EMERGENCY, WHICH COULD RESULT IN PROPERTY DAMAGE AND SERIOUS INJURY OR DEATH TO YOU AND/OR OTHERS.

Table 2: UL Current Ratings for Multitone only (AMPS)

Maximum RMS Current
(AMPS)
Tone Tone
Description 16-33VDC 16-33VRMS HI
STD dBA HI dBASTD dB
dBA Horn Broadband Horn (Continuous) 0.108 0.044 0.087 0.045 Bell 1560 Hz Modulated (0.07 Sec. ON/Re peat) 0.053 0.024 0.051 0.028 March Time Horn (0.25 Sec. ON/0.25 Sec. OFF/Repeat) 0.104 0.087 0.087 0.045 Code 3 Horn Horn (ANSI S3.41 Temporal Pattern) 0.091 0.035 0.087 0.045 Code 3 Tone 500 Hz (ANSI S3.41 Temporal Pattern) 0.075 0.025 0.056 0.029 Slow Whoop 500-1200Hz Sweep (4.0 Sec. ON/0.5 Sec. OFF/Repeat) 0.098 0.037 0.092 0.042 Siren 600-1200Hz Sweep (1.0 Sec. ON/Repeat) 0.104 0.036 0.092 0.040 HI/LO 1000/800 Hz (0.25 Sec. ON/Alternate) 0.057 0.025 0.058 0.032
Table 2A: ULC Current Ratings for 24VDC Multitone only (AMPS)
Tone
Horn
Bell
March Time
Code 3 Horn
Code 3 Tone
Slow Whoop
Siren
HI/LO
HI/LO
Volume
20VDC 24VDC 31VDC
HI 0.036 0.040 0.050
STD 0.021 0.023 0.029
HI 0.013 0.014 0.018
STD 0.011 0.012 0.015
HI 0.036 0.040 0.050
STD 0.021 0.023 0.029
HI 0.036 0.040 0.050
STD 0.021 0.023 0.029
HI 0.025 0.028 0.035
STD 0.015 0.017 0.021
HI 0.043 0.048 0.060
STD 0.023 0.026 0.033
HI 0.032 0.036 0.045
STD 0.021 0.023 0.029
HI 0.018 0.020 0.025
STD 0.013 0.014 0.018
DC
Table 2B: Strobe Current Ratings (AMPS)
Maximum RMS Current
UL Voltage 2475 24115 24135 24177 24185 DC 16-33VDC 0.138 0.300 0.300 0.420 0.420 FWR 16-33VRMS 0.222 0.455 0.455 0.645 0.645
AUDIBILITY RATINGS:
Table 3: dBA Ratings
Tone
Horn
Bell
March Time
Code 3 Horn
Code 3 Tone
Slow Whoop
Siren
HI/LO
Volume
UL 24VDC dBA Reverberant Ra tings
Per UL 464 at 10 Feet
16V 24V 33V 20V 24V 31V
HI 89 92 94 97 99 100
STD 84 87 90 91 93 94
HI 83 86 88 90 92 93
STD 76 80 83 85 87 88
HI 86 89 91 97 99 100
STD 80 84 87 91 93 94
HI 85 88 90 97 99 100
STD 79 83 86 91 93 94
HI 81 85 86 93 95 96
STD 76 80 82 88 90 91
HI 87 90 92 97 99 100
STD 81 85 87 92 94 95
HI 86 89 92 96 98 99
STD 81 84 87 91 93 94
ULC 24VDC dBA Anechoic Ra tings
Per CAN/ULC S525-99 at 10 Feet
HI/LO HI 83 86 89 91 93 94
P84870E
Sheet 2 of 6