wheelock AHWP, ASWP, MTWP, RSSWP Service Manual

FIRE ALARM SYSTEMS
Description:
Wheelock’s Weatherproof Strobe, Audible Strobe, Multitone Strobe and Audible appliances all have an extended temperature range of -35°C to 66°C (-31°F to 150°F) and will satisfy virtually all outdoor and severe environment applications. All strobes are Indoor/Out door UL Listed and rated for 75 candela @ -35°C (-31°F).
Series RSSWP Strobes, Series ASWP Audible S trobes Series AHWP Audibles and Series MTWP Strobe may be synchronized when used in conjunction with the Wheelock SM and DSM Sync Module(s).
Weatherproof Strobes - Series RSSWP
ULC Listed under St andard CAN/ULC-S526-02 for Indoor/Outdoor use. The strobes use a Xenon flashtube with solid state circuitry enclosed in a rugged Lexan® lens to provide maximum visibility and reliability for effective visual signaling. The Series RSSWP has a 75 cd intensity on axis at -35°C and Low Current Draw (180 cd @ 25°C). For outdoor application the RSSWP must be wall mounted to a Weatherproof backbox (WPSBB).
INC.
Helping People Take Action
SERIES RSSWP, ASWP, AHWP, and MTWP
WEATHERPROOF STROBE
WEATHERPROOF AUDIBLE STROBE
WEATHERPROOF AUDIBLE HORN
SERIES RSSWP Mounted to WPSBB
SERIES ASWP Mounted to WPBB
SM
Weatherproof Audible Strobes and Audibles- Series ASWP and AHWP
ULC Listed under Standard CAN/ULC-S526-02 for Visual Signaling Appliances and Standard CAN/ULC-S525-99 for Audible Signaling Appliances. Indoor/Out door use and offer a field selectable choice of continuous horn or temporal pattern (Code 3) when constant voltage from the Fire Alarm Control Panel (FACP) is applied. Additionally , the audible has three (3) selectable dBA settings of 99, 95, and 90 dBA in both tones and, when used with Wheelock sync modules, SM or DM the audible may be silenced while maintaining strobe activation on the Series ASWP. For outdoor applications the ASWP must be Wall Mounted to the Weatherproof Backbox (WPBB).
Weatherproof Multitone Strobe and Multitone Horn ­Series MTWP and MT-12/24
Is ULC Listed for indoor and outdoor applications under Standard CAN/ULC-S526-02 for Visual Signaling and under Standard CAN/ULC-S5255-99 for Audible Signal Devices for Fire Alarm Systems. The Multitone S trobe Appliances use a Xenon flash tube with solid state circuitry enclosed in a rugged Lexan® lens to provide maximum visibility and reliability for effective visible signaling. The Multitone electronic appliance offers a choice of eight (8) internationally recognized alerting sounds: Horn, Bell, March T ime Horn, Code 3 T one, Code 3 Horn, Slow Whoop, Siren or Hi/Lo Tone. Additionally, the audible has two installer selectable sound output levels; Standard and High covering a range (depending on selected signal) or 85-100 dBA anechoic. The series MTWP is a true 4-wire appliance. The strobe portion can by synchronized and non synchronized. The Multitone (audible) portion can be synchronized, but it can be connected to a coded fire alarm system. The series MTWP and the MT-12/24 mount to a series IOB out door backbox.
Copyright 2005 Wheelock, Inc. All rights reserved.
SERIES AHWP
SERIES MTWP Mounted to IOB
FEATURES
Approvals include: ULC, UL 1638, UL 464
Meets OSHA 29 Part 1910.165.
ULC Listed with an extended temperature range
of -35°C to 66°C (-31°F to 150°F).
24 VDC with wide UCL Listed Voltage Range using filtered (DC) or unfiltered VRMS voltage.
Synchronize with Wheelock Series SM or DSM, Sync Module(s).
36
NOTE: All CAUTIONS and WARNINGS are identified by the symbol All WARNINGS are printed in bold capital letters.
WARNING: PLEASE READ THESE SPECIFICATIONS AND ASSOCIATED INSTALLATION INSTRUCTIONS CAREFULLY
BEFORE USING, SPECIFYING OR APPLYING THIS PRODUCT. FAILURE TO COMPLY WITH ANY OF THESE INSTUCTIONS, CAUTIONS, OR WARNINGS COULD RESULT IN IMPROPER APPLICATION, INSTALLATION, AND/OR OPERATION OF THESE PRODUCTS IN AN EMERGENCY SITUATION, WHICH COULD RESULT IN PROPERTY DAMAGE, AND SERIOUS INJURY OR DEATH TO YOU AND/OR OTHERS.
General Notes:
Wheelock CAN/ULC-S526-M87 Strobes are designed to produce 30-62 flashes per minute over the Voltage Range.
Series RSSWP, AHWP, MTWP and MT12/24 are listed for indoor and outdoor use with a temperature range of -35°C to 66°C (-31°F to
150°F) and maximum humidity of 93% RH ±2%. Series AHWP temperature range -35°C to 66°C (-31°F to 150°F) and maximum humidity of 98% RH±2%.
All Canadian Installations should be in accordance with the Canadian Standard for the Installation of Fire Alarm Systems -
CAN/ULC-S524-01 and Canadian Electrical Code, Part 1.
PWTMniebortS
ledoM
)dc57(
detalugeR
0.02
egnaRegatloV
CD
V
RF-W5742-PWSSRCDV0.13-0.02831.490.760.
*tnerruCCLU:3elbaT
PWHAseireSrof)SPMA(
egatloVPW42-HA
PW42-HAwoL/deM/iH CDV0.02 CDV0.42
0./050.
CDV0.13
* Average current per actual Wheelock production testing. For rated average, peak and in rush current across the UL listed voltage range for both filtered DC and unfiltered VRMS, see Installation Instructions.
410./020./530.
710./52
120./030./560.
dnaPWSSRseireSrof*tnerruCegarevA:1elbaT
*tnerruC.gvA
0.42
0.13
CDV
CDV
#
egatloV
CDV0.02861.551.051. CDV0.42231.901.201. CDV0.13321.090.080.
Audible and Visual combined.
noitpircseDemuloV
suounitnoC
nroH
3edoC
nroH
ABdhgiH
gnitteS
ABd)99(
hgiH1999
deM8859
woL2809
hgiH5899
deM2859
woL5709
CDV0.02CDV0.42CDV0.13
)SPMA(*tnerruCegarevA:2elbaT
ebortSelbiduARF-W5742-PWSAseireSroF
ABdmuideM
g
nitteS
ABd)59(
ABdtnarebreveR
.tf01@464LUreP
CDV42C
ABdwoL
gnitteS
ABd)09(
PWHA&PWSAseireSrofsgnitaRABd:4elbaT
ABdciohcenA
.tf01@
DV42
PWTMseireSCDV,42rof)SPMA(sgnitaRtnerruCCLU:5elbaT
37
detaRCLU
egarevA
831.0490.0760
.0
tnerruC
enoTdradnatShgiHdradnatShgiHdradnatShgiH
nroH120.0630.0320.0040.0920.0050.0
lleB110.0310.0210.0410.0510.0810.0
emiThcraM1
20.0630.0320.0040.0920.0050.0 nroH3edoC120.0630.0320.0040.0920.0050.0 enoT3edoC510.0520.0710.0820.0120.0530.0
poohWwolS320
.0340.0620.0840.0330.0060.0 neriS120.0230.0320.0630.0920.0540.0 oL/iH310.0810.0410.0020.0810.0520.0
PWTMfoelbiduadna42/21-TM
enoTCDV0.21CDV0.42
dradnatShgiHdradnatShgiH
nroH020.0001.0320.0040.0
lleB010.0130.0210.0410.0
emiThcraM020.0001.0320.0040.0
nroH3edoC020.0001.0320.0040.0
.0060.0710.0820.0
enoT3edoC510
poohWwolS520.0001.0620.0840.0 neriS020.0280.0320.0630.0 oL/iH210.0440.0410.0020.0
seireSrof)SPMA(sgnitaR*tnerruCCLU:6elbaT
ABdCDV42CLU:7elbaT
rePsgnitaRciohcenA
teeF01ta99-525SCLU/NAC
ledoM
enoT
nroH
lleB
emiThcraM
doC
nroH3e enoT3edoC poohWwolS
neriS
OL/IH
V42
IHDTS 9939 2978 9939 9939 5909 9949 8939 3988
W5742-PWSA420.13-0.02-57
R-PW42-HA420.13-0.02--
W5742-PWSSR420.13-0.02-57
W5742-PWTM420.13-0.02-57
42/21-TM420.13-0.
sgnitaRCLU:8elbaT
lanimoN
egatloV
-RV/CDV(
)SM
detalugeR
tupnI
)CDV42(
detalugeR
tupnI
)CDV21(
ebortS
aledna
C
CLUreP
026.51-0.9-
38
Wiring Diagrams
SERIES MTWP AUDIBLE APPLIANCE AND STROBE OPERATE INDEPENDENTLY
FROM PRECEDING AUDIBLE OR FACP
FROM PRECEDING STROBE OR FACP
+
--
++
-
--
+
+
AUDIBLESTROBE
TO NEXT
+
AUDIBLE OR EOLR
TO NEXT STROBE OR
-
EOLR
SERIES MTWP AUDIBLE APPLIANCE AND STROBE OPERATE IN UNISON. RED AND BLACK SHUNT-WIRES ARE SUPPLIED.
FROM PRECEDING APPLIANCE OR FACP
+
--
RED
BLACK
TO NEX T
+
APPLIANCE
OR EOLR
SERIES RSSWP, ASWP, AHWP, MTWP AND MT-12/24 APPLIANCES
FROM
PRECEDING
APPLIANCE OR
FACP
+
-
-
+
APPLIANCE
TO NEXT
+
APPLIANCE
-
OR EOLR
-
+
STROBE AUDIBLE
-
+
39
Wiring Diagrams
SERIES MTWP APPLIANCES SYNCHRONIZED STROBE OPERATION WITH CODED FACP
SERIES RSSWP/ASWP APPLIANCES SYNCHRONIZED W/ DSM MODULE SINGLE CLASS “A” NAC CIRCUIT
NAC #1
FACP
NAC #2
SYNC
+
-
Sync
Module
or
Power
Supply
MTWP
Strobe Circuit
Audible
Circuit
TO THE NEXT APPLIANCE OR EOLR
FACP
STROBE
NAC
CIRCUIT
OUT
STROBE
NAC CIRCUIT RETURN
DSM
SYNC
+OUT 1 + IN 1 MINUS 1
+
-
MINUS 2
+ IN 2 + OUT 2
+
-
AUDIBLE
RSSWP
RSS
ASWP
ASWP
RSS
RSS
SERIES RSSWP/ASWP APPLIANCES SYNCHRONIZED W/MULTIPLE DSM MODULES CLASS “B” NAC CIRCUITS
DSM #1
F A C P
Strobe NAC Cir.
Strobe NAC Cir.
Strobe NAC Cir.
Sync
+
DSM #2
Sync
DSM #3
Sync
+
-
+
-
-
RSSWP
ASWP
RSSWP RSSWP
RSS
RSSWP
DSM Interconnecting wiring shown. Maximum of
twenty (20)
40
WARNING: CONTACT WHEELOCK FOR THE CURRENT “INSTALLATION INSTRUCTIONS” AND “GENERAL INFORMATION” SHEET (P82380) ON THESE PRODUCTS. THE INSTALLATION INSTRUCTIONS ARE AS FOLLOWS: P84135 FOR SERIES RSSWP, P83957 FOR SERIES ASWP, P83641 FOR SERIES AH-WP, P84150 FOR SEREIS MTWP AND P824671 FOR SERIES MT-12/24-R. THESE DOCUMENTS UNDERGO PERIODIC CHANGES. IT IS IMPORTANT THAT YOU HAVE CURRENT INFORMATION ON THESE PRODUCTS. THESE MATERIALS CONTAIN IMPORTANT INFORMATION THAT SHOULD BE READ PRIOR TO SPECIFYING OR INSTALLING THESE PRODUCTS, INCLUDING:
TOTAL CURRENT REQUIRED BY ALL APPLIANCES CONNECTED TO SYSTEM SECONDARY POWER
SOURCES.
FUSE RATINGS ON NOTIFICATION APPLIANCE CIRCUITS TO HANDLE PEAK CURRENTS FROM ALL
APPLIANCES ON THOSE CIRCUITS.
ADDING, REPLACING OR CHANGING APPLIANCES WILL EFFECT CURRENT DRAW. RECALCULATE
CURRENT DRAW TO INSURE THAT THE TOTAL AVERAGE CURRENT AND TOTAL PEAK REQUIRED BY ALL APPLIANCES DO NOT EXCEED THE RATED CAPACITY OF THE POWER SOURCE OR FUSES.
COMPOSITE FLASH RATE FROM MULTIPLE STROBES WITHIN A PERSON’S FIELD OF VIEW.
THE VOLTAGE APPLIED TO THESE PRODUCTS MUST BE WITHIN THEIR “REGULATED VOLTAGE
RANGE”.
USE STROBES ONLY ON CIRCUITS WITH CONTINUOUSLY APPLIED OPERATING VOLTAGE. DO NOT
USE STROBES ON CODED OR INTERRUPTED CIRCUITS IN WHICH THE APPLIED VOLTAGE IS CYCLED ON AND OFF AS THE STROBE MAY NOT FLASH.
FAILURE TO COMPLY WITH THE INSTALLATION INSTRUCTIONS OR GENERAL INFORMATION SHEETS
COULD RESULT IN IMPROPER INSTALLATION, APPLICATION, AND/OR OPERATION OF THESE PRODUCTS IN AN EMERGENCY SITUATION, WHICH COULD RESULT IN PROPERTY DAMAGE AND SERIOUS INJURY OR DEATH TO YOU AND/OR OTHERS.
CONDUCTOR SIZE (AWG), LENGTH AND AMPACITY SHOULD BE TAKEN INTO CONSIDERATION PRIOR
TO DESIGN AND INSTALLATION OF THESE PRODUCTS, PARTICULARLY IN RETROFIT INSTALLATIONS.
SPECIFICATIONS AND ORDERING INFORMATION
ledoM
ebortS
-W5742-PWSSR3109seYseYdc57- CDV42T
RF WF-W5742-PWSSR4303seYseYdc57- CDV42T
WN-W5742-PWSSR8779seYseYdc57- CDV42T
ebortSelbiduA
42-PWSA2109seYseYdc5799/59/09CDV42I
R-BBSPW1579PWSSR
R-BBPW4109PWSA
R-BOI6405
R-BBW9592PWHA
RF-W57
ebortSenotitluM
RF-W5742-PWTM0248seYylnOebortS,seYdc5749-57CDV42M WF-W5742-PWTM2113s WN-W5742-PWTM4479seYylnOebortS,seYdc5749-57CDV42M
selbiduA/snroH
R-PW42-HA6147seYseYA/N99
R-42/21-TM3205seYoNA/NM
sexoBkcaBU
redrO
edoC
-noN
cnyS
eYylnOebortS,seYdc5749-57CDV42M
SEWITH
&PWTM
R-42/21-TM
,MS/wcnyS
MSD
dcebortS C°53-@ )F°13-(
ABd
/59/09CDV42K
tupnI
egatloV
roodtuO gnitnuoM
*snoitpO
41
*Refer to data sheet S7000 for mounting options
Project
Notification Appliance Circuit
Layout and Design
No. By Date
42
ARCHITECTS AND ENGINEERS SPECIFICATIONS
The Weatherproof Strobe appliances shall be Wheelock Series RSSWP-2475W strobes or approved equals. The Series RSSWP shall meet and be listed for ULC and S526-02 S tandard 1638 (St andard for Visual Signaling Appliances) for Indoor/Outdoor use. The strobe appliances shall produce a flash rate of 30-62 flashes per minute over the Regulated Volt age Range of 20.0 to 31.0 VDC and shall incorporate a Xenon flashtube inclosed in a rugged Lexan® lens. The strobe shall be rated at 75cd and shall operate over an extended temperature range of -35°C to 66°C (-31°F to 150°F). All input s shall be polarized for compatibility with standard reverse polarity supervision of circuit wiring by a Fire Alarm Control Panel. When synchronization is required, the appliances shall be compatible with the Wheelock Series SM and DSM Sync Module(s). The strobes shall not drift out of synchronization at any time during operation. If the sync module fails to operate, (i.e., contacts remain closed), the strobe shall revert to a non-synchronized flash rate.
The Weatherproof Audible Strobe and Audible appliances shall be Wheelock Series ASWP-2475W Audible Strobes and Wheelock Series AHWP Audible Horns or approved equals. The Series ASWP and Series AHWP shall meet and be listed for ULC and S526-02 Standard 1638 (Standard for V isual Signaling Appliances) for Indoor/Outdoor use. The strobe appliances shall produce a flash rate of 30-62 flashes per minute over the Regulated Voltage Range of 20.0 to 31.0 VDC and shall incorporate a Xenon flashtube enclosed in a rugged Lexan® lens. The strobe shall be rated at 75cd and shall operate over an extended temperature range of -35°C to 66°C (-31°F to 150°F). All inputs shall be polarized for compatibility with standard reverse polarity supervision of circuit wiring by a Fire Alarm Control Panel (FACP).
The weatherproof audible strobe appliances shall be designed for two-wire operation and shall provide either a continuous or temporal (Code 3) tone when constant voltage from a Notification Appliance Circuit (NAC) of the Fire Alarm Control Panel (FACP) is applied. They shall be designed so that the audible signal may be silenced while maintaining strobe activation. When synchronization is required, the appliances shall be compatible with the WheelockSeries SM and DSM Sync Module(s). The strobes shall not drift out of synchronization at any time during operation. If the sync fails to operate, (i.e., contacts remain closed), the strobe shall revert to a non-synchronized flash rate.
The Weatherproof Multitone Strobe and Multitone Audible appliances shall be a Wheelock Series MTWP and MT-12/24 or equivalent. The Series MTWP shall meet and be listed for ULC and S526-02 S tandard 1638 (S tandard for Visual Signaling Appliances) for indoor/outdoor use. The strobe portion of the appliance shall produce a flash rate of 30­62 flashes per minute over the listed voltage range of 20-31 VDC and shall incorporate a Xenon flash tube enclosed in a rugged Lexan® lens. The strobe shall be rated at 75cd. The series MTWP shall operate over an extended temperature range of -35°C to 66°C (-31°F to 150°F). All input s shall be polarized for compatibility with industry standard reverse polarity of circuit wiring by a Fire Alarm Control Panel. The audible portion of the Series MTWP as well as the Series MT ­12/24 shall provide eight field selectable alarm signals. The signals shall consists of: Horn, Bell, March Time, Code 3 Horn, Code 3 Tone, Slow Whoop, Siren and Hi/Lo. T one selection shall be by a durable dip switch assembly. Clips or Jumpers are not acceptable. The appliance shall provide two output sound levels: S tandard and High dBA. The range of dBA shall be 75 to 94 dBA. The Series MTWP shall have an operating voltage of 24 VDC (nominal) while the Series MT ­12/24 shall operate at either 12 or 24 VDC (nominal) using filtered power or unfiltered power (full wave rectified). Both models shall have provisions for In/Out field wiring using terminals that accept #12 to #18 A WG wiring. When synchronization is required, the Series MTWP shall be compatible with the Series SM and DSM Sync Modules. Note: The Strobe
portion of the Series MTWP may be synchronized. The audible portion of the appliance cannot. The audible portion of the appliance can be connected to a coded fire alarm system. The Series MTWP and the Series MT-12/24 shall be mounted only to the IOB-R Backbox.
Due to continuous development of our products, specifications and offerings are subject to change without notice in accordance with Wheelock Inc. standard terms and conditions.
NATIONAL SALES OFFICE
800-631-2148
Canada 800-397-5777
E-Mail: Info@wheelockinc.com
http://www.wheelockinc.com
273 BRANCHPORT AVENUE LONG BRANCH, NJ 07740 TEL: 732-222-6880 FAX: 732-222-2588
43
WE ENCOURAGE AND SUPPORT NICET CERTIFICATION
ASSEMBLED IN THE USA
3 YEAR WARRANTY
Distributed By:
S9004C Rev 02/05