GENERAL:
115VAC Multitone Appliances are UL Listed for Fire Protective Service and for General Signaling Service. They are listed for both indoor and outdoor use with the backboxes specified in these instructions (see Mounting Options). 115VAC Multitone Appliances can be field set to produce any one of eight commonly used alarm tones. Sound output can be field set to provide either HIGH (HI) dBA or STANDARD (STD) dBA sound output level. All inputs have DC blocking capacitor for compatibility with supervision when used with a Fire Alarm Control Panel (FACP).
NOTE: All CAUTIONS and WARNINGS are identified by the symbol
. All warnings are printed in bold capital letters.
WARNING: PLEASE READ THESE INSTRUCTIONS CAREFULLY BEFORE USING THIS PRODUCT. THE 115VAC MULTITONE APPLIANCE MUST BE FIELD SET TO THE DESIRED dBA SOUND OUTPUT LEVEL AND ALARM TONE BEFORE THEY ARE INSTALLED. THIS IS DONE BY PROPERLY ADJUSTING A FOUR POSITION SWITCH IN ACCORDANCE WITH THESE INSTRUCTIONS. INCORRECT SETTINGS WILL RESULT IN IMPROPER PERFORMANCE AND COULD RESULT IN PROPERTY DAMAGE AND SERIOUS INJURY OR DEATH TO YOU AND/OR OTHERS.
SPECIFICATIONS:
Table 1: UL Listed Models and Ratings
Model Regulated
Voltage
(VRMS)
MT4-115 120 96-132 A, B
Voltage
Range
(VRMS)
Mounting
Options
Table 1A: dBA and Current Ratings for Multitone Appliances
dBA Reverberant
Tone at 10 Feet
HI STD HI STD
Horn 0.050 0.042 88 82
Bell 0.041 0.039 82 75
March Time Horn 0.050 0.040 85 79
Code-3 Horn 0.050 0.042 85 75
Code-3 Tone 0.042 0.040 79 75
Slow Whoop 0.050 0.042 88 82
Siren 0.045 0.041 85 82
HI/LO 0.042 0.039 82 79
Maximum RMS Current
(AMPS)
Per UL 464
WARNING: FOR UL APPLICATIONS THESE APPLIANCES WERE TESTED TO THE OPERATING VOLTAGE LIMITS OF 96-132 VOLTS. DO NOT APPLY 80% AND 110% OF THESE VOLTAGE VALUES FOR SYSTEM OPERATION.
All models are UL Listed for indoor/outdoor use with a temperature range of -31
o
F to +150oF (-35oC to +66oC) and maximum
humidity of 95% RH.
Copyright 2004 Wheelock, Inc. All rights reserved.
P83159 B
Sheet 1 of 6
WARNING: MAKE SURE THAT THE TOTAL RMS CURRENT REQUIRED BY ALL APPLIANCES THAT ARE CONNECTED TO THE SYSTEM’S PRIMARY AND SECONDARY POWER SOURCES DO NOT EXCEED THE POWER SOURCES’ RATED CAPACITY OR THE CURRENT RATINGS OF ANY FUSES ON THE CIRCUITS TO WHICH THESE APPLIANCES ARE WIRED. OVERLOADING POWER SOURCES OR EXCEEDING FUSE RATINGS COULD RESULT IN LOSS OF POWER AND FAILURE TO ALERT OCCUPANTS DURING AN EMERGENCY, WHICH COULD RESULT IN PROPERTY DAMAGE AND SERIOUS INJURY OR DEATH TO YOU AND/OR OTHERS.
When calculating the total currents: Use Table 1 to determine the highest value of “RMS Current” for an individual audible (across the expected operating voltage range of the audible), then multiply these values by the total number of audibles; be sure to add the currents for any other appliances, including audible signaling appliances, powered by the same source and include any required safety factors.
WARNING: MAKE SURE THAT ALL FUSES USED ON SIGNALING CIRCUITS ARE RATED TO HANDLE THE MAXIMUM INRUSH OR PEAK CURRENT FROM ALL APPLIANCES ON THOSE CIRCUITS. FAILURE TO DO THIS MAY RESULT IN LOSS OF POWER TO THE SIGNALING CIRCUIT AND THE FAILURE OF ALL APPLIANCES ON THAT CIRCUIT TO OPERATE, WHICH COULD RESULT IN PROPERTY DAMAGE AND SERIOUS INJURY OR DEATH TO YOU AND/OR OTHERS.
The Multitone audible appliances produce a brief inrush current that lasts for just 50 microseconds but can reach a peak value of 5.0 Amps.
WARNING: IF 115VAC MULTITONE APPLIANCES ARE OPERATED WITHIN 15 INCHES OF A PERSON'S EAR, THEY CAN PRODUCE A SOUND PRESSURE LEVEL THAT EXCEEDS THE MAXIMUM 120 dBA PERMITTED BY ADA AND OSHA RULES. EXPOSURE TO SUCH SOUND LEVELS CAN RESULT IN DAMAGE TO A PERSON'S HEARING.
SETTINGS:
The Switch (SW1) of the Multitone Appliance, shown in Figure 1, is used to set the desired dBA sound output level and alarm tone. The factory settings are shown below. Read these instructions carefully before changing any of these factory settings.
Figure 1:
PC Board Layout Showing Location of Switch (SW1)
SLIDE HERE FOR (0)
SLIDE HERE FOR (1)
The factory settings are:
SW1
4
123
O N
SW1
432
1
O N
HIGH dBA SW1 POS 1 set on 1
HORN TONE SW1 POS 2, 3, 4 set on 1, 1, 1