273 Branchport Ave.
Long Branch, N.J. 07740 Thank you for using our products.
(800) 631-2148
(800) 397-5777
www.cooperwheelock.com
INSTALLATION INSTRUCTIONS
SERIES E50 SPEAKERS
Use this product according to this instruction manual. Please keep this instruction manual for future reference.
GENERAL:
Wheelock’s Series E50 Speakers are UL Listed under UL Standard 1480 for Speaker Appliances. They are designed for multiple
power requirements with high dBA output at each power tap. All models offer a choice of field selectable taps, 1/8W to 2W, for
either 25.0VRMS or 70.0VRMS audio systems. The design incorporates a high efficiency speaker for maximum output at minimum
power across a frequency range of 400Hz to 4000Hz, and features a sealed back construction for extra protection and improved
audibility. All models are UL Listed for
indoor use only with the backboxes specified in these instructions (see Mounting Options).
NOTE: All CAUTIONS and WARNINGS are identified by the symbol
. All warnings are printed in bold capital letters.
WARNING: THE SPEAKER APPLIANCE IS A "FIRE ALARM DEVICE - DO NOT PAINT".
WARNING: PLEASE READ THESE INSTRUCTIONS CAREFULLY. FAILURE TO COMPLY WITH ANY OF THE
FOLLOWING INSTRUCTIONS, CAUTIONS AND WARNINGS COULD RESULT IN IMPROPER APPLICATION,
INSTALLATION AND/OR OPERATION OF THESE PRODUCTS IN AN EMERGENCY SITUATION, WHICH COULD
RESULT IN PROPERTY DAMAGE AND SERIOUS INJURY OR DEATH TO YOU AND/OR OTHERS.
SPECIFICATIONS:
Table 1: UL Listed Models and Ratings
Speaker
Model Voltage
(VRMS)
1/8 1/4 1/2 1 2
E50 25/70 77.0 79.5 82.5 85.0 88.0 A,B
dBA at 10 Feet
(Rated Watts)
Mounting
Options
NOTES:
1. All models are UL Listed for indoor use with a temperature range of +32ºF to +120ºF (0ºC to +49ºC) and maximum
humidity of 85% RH.
2. dBA is rated per UL Standard 1480 for Speaker Appliances. Frequency range of speakers is 400 – 4000HZ
Copyright 2007 Cooper Wheelock, Inc. All rights reserved
P84590 E
Sheet 1 of 5
WIRING INFORMATION:
A 1.5µF blocking capacitor for DC supervision of audio lines by the FACP is factory wired in series with the speaker input.
Supervision voltage must not exceed 33 volts DC.
Figure 1: Figure 2:
FROM PRECEDING SPEAKER
OR FIRE ALARM
CONTROL P AN EL (FACP)
TO NEXT SPEAKER
OR END OR LINE RESISTOR
(EOLR)
1. Series E50 Speaker models have in-out wiring
terminals that accept two #12 to #18 American
Wire Gauge (AWG) wires at each screw
terminal. Strip leads 3/8 inches and connect to
screw terminals.
2. Break all in-out wire runs on supervised
circuits to assure integrity of circuit
supervision as shown in Figure 2. The polarity
shown in the wiring diagrams is for operation
of the appliances.
*
GROUNDING
COM+
: Connect ground wire to backbox. Install signaling appliance to backbox using mounting screws provided.
NOTE: Check electrical ratings specified in tables 1 and 2 (as appropriate) to ensure proper electrical input. Be sure that speaker
wiring is connected to speaker terminals only and strobe wiring is connected to strobe terminals only. Check to insure that wiring at
FACP is correct.
WARNING: IMPROPER ELECTRICAL INPUT CAN DAMAGE THE PRODUCT OR CAUSE IT TO MALFUNCTION.
Figure 3: Jumper plug is used to select dBA loudness. Figure 4: Tap Settings (Factory setting is 70V @ 1/2W (F))
AB
DE F GH
A
B
C
D
E
F
G
H
: Use needle nose pliers to pull and properly insert the jumper plug to the desired tap setting.
NOTE
Connect speaker wires to common and positive of terminal block and select the power tap terminal for 1/8W, 1/4W, 1/2W, 1W or
2W; 25V or 70V as required (see Figures 1, 2, 3, 4 and Table 2). Each doubling of rated Watts increases sound output by 3 dBA.
Each letter corresponds to a plug position of the header located on the printed circuit board. Select voltage and wattage as shown in
Table 2 below.
Table 2: Speaker Voltage and Wattage Connection Chart
Position 25V 70V
A 2 -----B 1 -----C 1/2 -----D 1/4 2
E 1/8 1
F ------ 1/2
G ------ 1/4
H ------ 1/8
NOTE: The speaker strobe appliances must be set to the desired dBA sound output level before they are installed. This is done by
properly inserting jumper plugs in accordance with these instructions.
WARNING: INCORRECT SETTINGS WILL RESULT IN IMPROPER PERFORMANCE.
P84590 E
Sheet 2 of 5