wheelock E50, E50-241575W, E50-MCW, E50-MCWH Service Manual

Series E50 Speaker and Speaker Strobes
THE CITY OF NEW YORK
DEPARTMENT OF BUILDINGS
U
L
®
Description
The Wheelock Series E50 Speakers and Speaker Strobes feature high efficiency sound output, with dual voltage (25/70 VRMS) capability and field selectable taps from 1/8 to 2 watts. They are designed to provide a sleek, aesthetic appearance for emergency voice/alarm communications systems. All Series E50 models mount to standard 4” x 2-1/8” electrical boxes (with no extension ring required) and incorporate a speaker mounting plate for faster installation. The grille cover snaps on so no mounting screws are visible. Attractive surface boxes are also available for surface installations.
Series E50 Speakers and Speaker Strobes provide high audio output with clear audibility and are designed to meet the critical needs of the life safety industry for effective emergency voice communications, tone signaling and visible signaling to alert the hearing impaired.
The strobe portion of all Series E Speaker Strobes may be synchronized when used in conjunction with the Wheelock SM, DSM Sync Modules or the Wheelock’s PS-24-8MC Power Supply with Patented Sync Protocol. Wheelock synchronized strobes offer an easy way to comply with ADA and NFPA regulations concerning photosensitive epilepsy.
Series E50 Speaker Strobes are UL Listed for indoor use under Standard 1971 (Signaling Devices for the Hearing-Impaired) and Standard 1480 (Speaker Appliances). All inputs employ IN/OUT wiring terminals for fast installation using #12 to #18 AWG wiring and are compatible with FACP line supervision.
Color options for the Series E50 Speakers and Speaker Strobes are red or off-white.
SERIES E50
Speaker Strobe
SERIES E50
Speaker
Features
Approvals include: UL Standard 1971, UL Standard 1480, New York City (MEA), California State Fire Marshal (CSFM), Factory Mutual (FM) and Chicago (BFP). See approvals by model in Specifications and Ordering Information
ADA/NFPA/ANSI compliant
Complies with OSHA 29 Part 1910.165
Wall mount speaker strobe models with field selectable candela settings of 15/30/75/110cd or 135/185cd (Multi-Candela models), or 1575cd (Single Candela model)
Field selectable taps for 25 or 70 VRMS operation from 1/8 watt up to 2 watts
High efficiency design for maximum output at minimum wattage across a frequency range of 400 to 4000 HZ
24 VDC strobes produce 1 flash per second with wide UL “Regulated Voltage” of 16 to 33 volts using filtered DC or unfiltered VRMS input voltage
Synchronize with Wheelock SM, DSM or Wheelock PS-12/24-8CP and PS-12/24-8MP Power Supply with built-in sync protocol
Mount to 4” square x 2-1/8” deep backbox with no extension
ring required
Snap on grille cover with no visible mounting screws
Fast installation with IN/OUT screw terminals using #12 to #18 AWG wires
S5391
151-92-E
7125-0785:165 7320-0785:166
NOTE: All CAUTIONS and WARNINGS are identified by the symbol . All warnings are printed in bold capital letters.
WARNING: PLEASE READ THESE SPECIFICATIONS AND ASSOCIATED INSTALLATION INSTRUCTIONS CAREFULLY BEFORE USING, SPECIFYING OR
APPLYING THIS PRODUCT. VISIT WWW.COOPERWHEELOCK.COM OR CONTACT COOPER WHEELOCK FOR THE CURRENT INSTALLATION INSTRUCTIONS. FAILURE TO COMPLY WITH ANY OF THESE INSTRUCTIONS, CAUTIONS OR WARNINGS COULD RESULT IN IMPROPER APPLICATION, INSTALLATION AND/OR OPERATION OF THESE PRODUCTS IN AN EMERGENCY SITUATION, WHICH COULD RESULT IN PROPERTY DAMAGE, AND SERIOUS INJURY OR DEATH TO YOU AND/OR OTHERS.
General Notes:
Strobes are designed to flash at 1 flash per second minimum over their “Regulated Voltage Range”. Note that NFPA-72 specifies a flash rate of 1
to 2 flashes per second and ADA Guidelines specify a flash rate of 1 to 3 flashes per second.
All candela ratings represent minimum effective Strobe intensity based on UL Standard 1971.
Series NS Strobe products are listed under UL Standard 1971 for indoor use with a temperature range of 32°F to 120°F (0°C to 49°C) and maximum humidity of 93% (± 2%).
Series NH horns are listed under UL Standard 464 for audible signal appliances (Indoor use only).
“Regulated Voltage Range” is the newest terminology used by UL to identify the voltage range. Prior to this change UL used the
terminology “Listed Voltage Range”.
Table 1: Average RMS Current
E50
Speaker
Strobes
241575W 24MCW 24MCWH
1575cd 15cd 30cd 75cd 110cd 135cd 185cd
E50 Strobe Current - Wall Mount
24 vdc 0.060 0.041 0.063 0.109 0.140 0.195 0.270
UL max* 0.090 0.060 0.092 0.165 0.220 0.300 0.420
Table 2: E50 UL Reverberant dBA @ 10 Feet**
watts 1/8 1/4 1/2 1 2
E50 Speaker 77 79.5 82.5 85 88
E50 Speaker Strobe 77 79.5 82.5 85 88
**dBA ratings are based on UL testing under UL Standard 1480
* RMS current ratings are per UL average RMS method. UL max current rating is the maximum RMS current within the listed voltage range (16-33v for 24v units). For strobes the UL max current is usually at the minimum listed voltage (16v for 24v units). For unfiltered FWR ratings, see installation instructions.