wheelock CH70-2415W, CH70-24110W, CH70-2430W, CH70-2475W, CH90-24100C-FW INSTALLATION INSTRUCTIONS

...
273 Branchport Avenue Thank you for using our products. Long Branch, N.J. 07740 (800) 631-2148 www.wheelockinc.com
INSTALLATION INSTRUCTIONS
Use this product according to this instruction manual. Please keep this instruction manual for future reference.
GENERAL:
Wheelock’s Series CH70/90 Electronic Chimes and Chime Strobes are UL Listed under Standard 1971 for Signaling Devices for the Hearing Impaired and UL Standard for Private Mode Audible Signal Appliances. CH70/90 Chimes are designed for low current draw and versatile performance. All models offer a choice of single stroke or vibrating operation, have adjustable sound level to 83dBA (peak anechoic) at 10 feet, and have a chime tone adjustable from 800 to 1200Hz. The Series CH70/90 appliances also incorporate a Chime Mounting Plate attached to the chime for ease of installation. CH70 Chime Strobe models can provide a non-synchronized strobe appliance when connected directly to a Fire Alarm Control Panel (FACP), or provide a synchronized strobe appliance when used in conjunction with a Sync Module (SM) or a Dual Sync Module (DSM). The strobes use a Xenon flashtube with solid state circuitry enclosed in a rugged Lexan lens to provide maximum visibility and reliability for effective visible signaling. The 241575W candela wall mounted strobes are listed at 15 candela under UL Standard 1971 and meet 75 candela intensity on axis with low current draw. The CH70 Chime Strobes for wall mounting only 2415W, 241575W, 2430W, 2475W and 24110W. The CH90 Chime Strobes for ceiling mounting only
are available with a choice of five UL Listed strobe options:
are available with a choice of
two UL Listed strobe options: 2475C and 24100C. The CH90 Chime is for wall or ceiling mounting. All models are Listed for
indoor use only
: All
NOTE
WARNING: READ THESE INSTRUCTIONS CAREFULLY. FAILURE TO COMPLY WITH ANY OF THE FOLLOWING INSTRUCTIONS, CAUTIONS AND WARNINGS COULD RESULT IN IMPROPER APPLICATION, INSTALLATION AND/OR OPERATION OF THESE PRODUCTS IN AN EMERGENCY SITUATION, WHICH COULD RESULT IN PROPERTY DAMAGE AND SERIOUS INJURY OR DEATH TO YOU AND/OR OTHERS.
SPECIFICATIONS:
Models (VDC/VRMS) For Chimes (AMPS) Peak Anechoic Reverberant Candela Options
CH70 20 24 31 .020 .022 80 52 58 ---- A,C CH70-2415W 20 24 31 .020 .022 80 52 58 15 B,D CH70-241575W 20 24 31 .020 .022 80 52 58 15* B,D CH70-2430W 20 24 31 .020 .022 80 52 58 30 B,D CH70-2475W 20 24 31 .020 .022 80 52 58 75 B,D CH70-24110W 20 24 31 .020 .022 80 52 58 110 B,D CH90 20 24 31 .020 .022 80 52 58 ---- A CH90-2475C 20 24 31 .020 .022 80 52 58 75 A,B CH90-24100C 20 24 31 .020 .022 80 52 58 100 A,B
with the backboxes specified in these instructions (see Mounting Options).
CAUTIONS
Voltage Rated Average Current dBA at 10 Feet Mounting
Min Nom Max Nom Max 24VDC Min Max
and
WARNINGS
are identified by the symbol . All warnings are printed in bold capital letters.
Table 1: UL Listed Models and Ratings
* 241575W models are UL Listed at 15cd and meet 75cd on axis.
Notes:
1. Models with strobe will produce 1 flash per second over the listed voltage range.
2. All models are UL Listed for indoor use with a temperature range of +32oF to +120oF (0oC to +49oC) and maximum humidity
of 85% RH.
3. Chimes must be set at maximum volume for Private Mode Fire Protective Service per UL 1638 listing requirements (see Wiring
Information Note 2).
4. Anechoic dBA is measured in an anechoic chamber with peak meter response. Reverberant dBA is rated per UL Standard 464.
5. The chimes produce a brief inrush current of 0.100 Amps with filtered DC input (0.140 Amps with full-wave-rectified (VRMS)
input) with a time duration of 100 milliseconds.
The UL Listed "Rated Input Voltage" is 20.0-31.0VDC using either filtered (DC) input or unfiltered full-wave-rectified (VRMS) voltage.
Check the minimum and maximum output of the power supply and standby battery and subtract the voltage drop from the circuit wiring resistance to determine the applied voltage to the strobes. Copyright 1997, 1998 Wheelock, Inc. All rights reserved.
P83599 C
Sheet 1 of 8
WARNING: ALTHOUGH UL TESTING HAS VERIFIED THAT THESE STROBES FUNCTION EVEN AT 80% OF THEIR MINIMUM RATING AND 110% OF THEIR MAXIMUM RATING, WHEELOCK STRONGLY RECOMMENDS THAT THE VOLTAGE APPLIED TO THESE PRODUCTS BE WITHIN THEIR RATED INPUT VOLTAGE RANGE. THE APPLICATION OF IMPROPER VOLTAGE MAY RESULT IN DEGRADED OPERATION OR DAMAGE TO THESE PRODUCTS, WHICH COULD RESULT IN PROPERTY DAMAGE AND SERIOUS INJURY OR DEATH TO YOU AND/OR OTHERS.
Table 2: Wall and Ceiling Mount Mount Strobe Current Requirements (AMPS)
Rated Average Current *
Voltage 2415W 241575W 2430W 2475W 24110W 2475C 24100C
20.0VDC .063 .080 .100 .165 .209 0.260 0.300
24.0VDC .053 .068 .085 .140 .169 0.215 0.250
31.0VDC .045 .055 .069 .114 .138 0.165 0.200
20.0VRMS .083 .105 .131 .217 .274 0.338 0.400
24.0VRMS .076 .097 .121 .200 .241 0.314 0.350
31.0VRMS .069 .084 .105 .176 .217 0.289 0.315 Rated Peak Current **
Voltage 2415W 241575W 2430W 2475W 24110W 2475C 24100C
20.0VDC .169 .205 .240 .400 .495 0.690 0.780
24.0VDC .173 .210 .250 .400 .510 0.700 0.790
31.0VDC .178 .215 .255 .425 .525 0.710 0.800
20.0VRMS .173 .210 .250 .410 .510 0.700 0.790
24.0VRMS .178 .215 .255 .410 .525 0.710 0.800
31.0VRMS .182 .220 .265 .435 .535 0.720 0.810
Rated Inrush Current ***
Voltage 2415W 241575W 2430W 2475W 24110W 2475C 24100C
20.0VDC .135 .135 .135 .135 .135 0.135 0.135
24.0VDC .165 .165 .165 .165 .165 0.165 0.165
31.0VDC .210 .210 .210 .210 .210 0.210 0.210
20.0VRMS .175 .175 .175 .175 .175 0.175 0.175
24.0VRMS .210 .210 .210 .210 .210 0.210 0.210
31.0VRMS .275 .275 .275 .275 .275 0.275 0.275
W = Wall C = Ceiling
* Rated Average Current is measured using mean value.
** The time duration for the peak current is 100 microseconds.
*** The time duration for the inrush current is 4 milliseconds.
WARNING: MAKE SURE THAT THE TOTAL AVERAGE CURRENT, TOTAL PEAK CURRENT AND TOTAL INRUSH CURRENT REQUIRED BY ALL APPLIANCES THAT ARE CONNECTED TO THE SYSTEM’S PRIMARY AND SECONDARY POWER SOURCES, NAC CIRCUITS, SM AND DSM SYNC MODULES DO NOT EXCEED THE POWER SOURCES’ RATED CAPACITY OR THE CURRENT RATINGS OF ANY FUSES ON THE CIRCUITS TO WHICH THESE APPLIANCES ARE WIRED. OVERLOADING POWER SOURCES OR EXCEEDING FUSE RATINGS COULD RESULT IN LOSS OF POWER AND FAILURE TO ALERT OCCUPANTS DURING AN EMERGENCY, WHICH COULD RESULT IN PROPERTY DAMAGE AND SERIOUS INJURY OR DEATH TO YOU AND/OR OTHERS.
When calculating the total average, peak and inrush currents: Use Table 2 to determine the highest value of “Rated Average Current” for an individual chime strobe (across the expected operating voltage range of the chime strobe), and the highest value of “Rated Inrush Current” or “Rated Peak Current” (whichever is higher) of an individual chime strobe (across the expected voltage range of the chime strobe), then multiply these values by the total number of chime strobes; be sure to add the currents for the chimes and any other appliances, including audible signaling appliances, powered by the same source and include any required safety factors.
If the inrush current or peak current exceeds the power supplies’ inrush capacity, the output voltage provided by the power supplies may drop below the listed voltage range of the appliances connected to the supply and the voltage may not recover in some types of power supplies. For example, an auxiliary power supply that lacks filtering at its output stage (either via lack of capacitance and/or lack of battery backup across the output) may exhibit this characteristic.
:
CAUTION
Chime Strobes are not designed to be used on coded systems in which the applied voltage is cycled on and off.
P83599 C
Sheet 2 of 8
LIGHT DISTRIBUTION:
Horizontal 15W 1575W* 30W 75W 110W
Angle
(in deg.)
0 15.0 24 94 30.0 46 75.0 103 110.0 149 5 13.5 24 93 27.0 46 67.5 103 99.0 152 10 13.5 24 88 27.0 45 67.5 104 99.0 151 15 13.5 24 87 27.0 46 67.5 100 99.0 151 20 13.5 23 85 27.0 43 67.5 101 99.0 148 25 13.5 23 80 27.0 43 67.5 98 99.0 140 30 11.3 21 75 22.5 41 56.3 94 82.5 135 35 11.3 20 71 22.5 40 56.3 89 82.5 129 40 11.3 19 62 22.5 39 56.3 83 82.5 124 45 11.3 18 52 22.5 41 56.3 81 82.5 133 50 8.3 18 35 16.5 36 41.3 77 60.5 121 55 6.8 12 32 13.5 27 33.8 60 49.5 85 60 6.0 11 34 12.0 30 30.0 59 44.0 95 65 5.3 13 27 10.5 35 26.3 71 38.5 113 70 5.3 17 19 10.5 29 26.3 73 38.5 81 75 4.5 13 11 9.0 22 22.5 53 33.0 72 80 4.5 8 9 9.0 17 22.5 35 33.0 50 85 3.8 7 10 7.5 15 18.8 30 27.5 38 90 3.8 6 10 7.5 15 18.8 30 27.5 43
Vertical 15W 1575W* 30W 75W 110W
Angle
(in deg.)
0 15.0 24 94 30.0 46 75.0 103 110.0 149 5 13.5 24 83 27.0 46 67.5 103 99.0 149 10 13.5 24 30 27.0 46 67.5 103 99.0 137 15 13.5 24 19 27.0 45 67.5 102 99.0 120 20 13.5 24 17 27.0 41 67.5 104 99.0 110 25 13.5 21 16 27.0 48 67.5 89 99.0 129 30 13.5 23 15 27.0 40 67.5 96 99.0 114 35 9.8 22 12 19.5 45 48.8 91 71.5 119 40 6.9 13 11 13.8 39 34.3 57 50.6 109 45 5.1 9 10 10.2 24 25.5 36 37.4 66 50 4.0 9 9 8.1 16 20.0 33 29.7 45 55 3.3 8 9 6.6 15 16.3 31 24.2 43 60 2.7 8 9 5.4 15 13.5 31 19.8 40 65 2.4 8 9 4.8 14 12.0 31 17.6 40 70 2.3 8 10 4.5 15 11.3 31 16.5 39 75 2.0 8 10 4.0 14 10.0 31 14.3 39 80 1.8 8 9 3.6 13 9.0 27 13.2 36 85 1.8 7 9 3.6 13 9.0 27 13.2 37 90 1.8 3 9 3.6 9 9.0 12 13.2 16
Table 3: Horizontal Plane (Wall Mount)
UL
Min.
Typ. 15W
Typ.
1575W
UL
Min.
Typ. 30W
UL
Min.
Table 3A: Vertical Plane (Wall Mount)
UL
Min.
Typ.
15W
Typ.
1575W
UL
Min.
Typ. 30W
UL
Min.
* 1575W models are UL Listed for 15cd and meet 75cd on axis.
Typ. 75W
Typ. 75W
UL
Min.
UL
Min.
Typ.
110W
Typ.
110W
P83599 C
Sheet 3 of 8
Loading...