wheelock AS-24MCC, AS-24MCW, AH-12, AS-121575, AS-24MCCH Service Manual

...
Series AS Audible Strobe Appliances and Series AH Auddibles
THE CITY OF NEW YORK
DEPARTMENT OF BUILDINGS
U
L
®
SERIES AS
Description
The Wheelock patented 2-wire Series AS Audible Strobe Appliances and Series AH Audibles offer more features with low current draw.
Strobe options for wall mount models include 1575cd or the Wheelock patented MCW multi-candela wall strobes with field selectable candela settings of 15/30/75/110cd, or the high intensity MCWH strobe with field selectable 135/185cd.
Ceiling mount models incorporate Wheelock’s patented MCC multi-candela ceiling strobe with field selectable intensities of 15/30/75/95cd or the high intensity MCCH strobe with field selectable 115/177cd.
The audibl e pro vides a sel ecta ble choi ce of either a co n tinuo u s horn or temp o ral patt e rn (Cod e 3) when co nstan t volta ge fro m a Fire Alarm Panel (FACP) is applied. Each tone has 3 dBA settings to choose from.
When used with the Wheelock Series SM or DSM Sync Module or Wheelock PS-24-8MC Power Supplies with Patented Sync Protocol, synchronization of the continuous horn tone provides the temporal (code 3) tone (mandated by NFPA 72) simultaneously for all audible appliances. This ensures a distinct temporal (code 3) pattern when 2 or more audibles are within hearing distance. If not synchronized the temporal sound could overlap and not be distinctive. At the same time the strobes will be synchronized. This provides the ability to comply with ADA guidelines concerning photosensitive epilepsy and the NFPA standards when installing 2 or more visual appliances within the field of view all of this plus the ability to silence the audible is achieved by using only 2 wire.
SERIES AH
Features
Approvals include: UL Standard 1971, UL Standard 464 New York City (MEA), California State Fire Marshal (CSFM), Factory Mutual (FM), and Chicago (BFP). See approvals by model in Specifications and Ordering Information
ADA/NFPA/UFC/ANSI Compliant
Wall mount models are available with Field Selectable
Candela Settings of 15/30/75/110cd or 135/185cd (Multi- Candela models) or 1575cd (single candela model)
Ceiling mount models are available with field selectable candela settings of 15/30/75/95cd or 115/177cd (multi-candela ceiling models)
Selectable Continuous Horn or Temporal (Code 3).
3 Selectable dBA settings (99, 95 and 90 dBA) in both tones
Patented 2-Wire Audible Strobe Appliance.
Patented Universal Mounting Plate
Weatherproof models are available for outdoor use
Strobes produce 1 flash per second over the regulated
voltage range
12 and 24 VDC models with wide UL “Regulated Voltage Range” using filtered DC or unfiltered FWR input voltage
The strobes can be synchronized using Wheelock’s sync modules or power supplies with built in sync protocol
Fast installation with IN/OUT screw terminals using #12 to #18 AWG wires
E5946 S5391
151-92-E
For Weatherproof Series AS, See Datasheet S9004
7125-0785:131
NOTE: All CAUTIONS and WARNINGS are identified by the symbol . All warnings are printed in bold capital letters.
WARNING: PLEASE READ THESE SPECIFICATIONS AND ASSOCIATED INSTALLATION INSTRUCTIONS CAREFULLY BEFORE USING, SPECIFYING OR
APPLYING THIS PRODUCT. VISIT WWW.COOPERWHEELOCK.COM OR CONTACT COOPER WHEELOCK FOR THE CURRENT INSTALLATION INSTRUCTIONS. FAILURE TO COMPLY WITH ANY OF THESE INSTRUCTIONS, CAUTIONS OR WARNINGS COULD RESULT IN IMPROPER APPLICATION, INSTALLATION AND/OR OPERATION OF THESE PRODUCTS IN AN EMERGENCY SITUATION, WHICH COULD RESULT IN PROPERTY DAMAGE, AND SERIOUS INJURY OR DEATH TO YOU AND/OR OTHERS.
General Notes:
Strobes are designed to flash at 1 flash per second minimum over their “Regulated Voltage Range”. Note that NFPA-72 specifies a flash rate of 1
to 2 flashes per second and ADA Guidelines specify a flash rate of 1 to 3 flashes per second.
All candela ratings represent minimum effective Strobe intensity based on UL Standard 1971.
Series NS Strobe products are listed under UL Standard 1971 for indoor use with a temperature range of 32°F to 120°F (0°C to 49°C) and maximum humidity of 93% (± 2%).
Series NH horns are listed under UL Standard 464 for audible signal appliances (Indoor use only).
“Regulated Voltage Range” is the newest terminology used by UL to identify the voltage range. Prior to this change UL used the
terminology “Listed Voltage Range”.
Table 1: Ratings Per UL 1971
Model
Number
Input
Voltage
VDC
Regulated
Voltage Range
VDC/FWR
Strobe
Candela (cd)
AS-24MCW 24 16.0 - 33.0 15/30/75/110
AS-24MCCH 24 16.0 - 33.0 115/177
AS-241575W 24 16.0 - 33.0 15 (75 on Axis)
AS-121575W 12 8.0 – 17.5 15 (75 on Axis)
AS-24MCC 24 16.0 - 33.0 15/30/75/95
AS-24MCWH 24 16.0 - 33.0 135/185
ASWP-2475W 24 16.0 - 33.0 75 @ -31°F
Table 3: Average RMS Current
Audible Wall Mount Audible Strobe Models Ceiling Mount Audible Strobe Models
24 VDC Models
High (99)
dBA
Med (95)
dBA
24 vdc 0.062 0.100 0.080 0.102 0.150 0.194 0.250 0.320 0.088 0.114 0.165 0.205 0.250 0.320
UL max* 0.080 0.121 0.088 0.125 0.200 0.267 0.355 0.480 0.095 0.138 0.221 0.285 0.355 0.480
24 vdc 0.033 0.080 0.060 0.084 0.132 0.173 0.230 0.305 0.066 0.092 0.145 0.186 0.230 0.305
UL max* 0.043 0.107 0.074 0.110 0.190 0.253 0.340 0.465 0.080 0.122 0.201 0.269 0.340 0.465
AH-24 AS-241575W AS-24MCW AS-24MCWH AS-24MCC AS-24MCCH
1575cd 15cd 30cd 75cd 110cd 135cd 185cd 15cd 30cd 75cd 95cd 115cd 177cd
Table 2: dBA Ratings for 12 VDC and 24 VDC Series AS/AH 12 and 24 VDC Audible
Description Volume
Reverberant
dBA
Per UL 464
@ 10 ft.
Anechoic
dBA
@ 10 ft.
High 91 99
Continuous
Horn
Medium 88 95
Low 83 90
High 87 99
Code 3 Horn
Medium 84 95
Low 79 90
Low (90)
dBA
12 VDC Models
High (99)
dBA
Med (95)
dBA
Low (90)
dBA
24 vdc 0.017 0.072 0.052 0.076 0.121 0.158 0.220 0.295 0.056 0.082 0.132 0.173 0.220 0.295
UL max* 0.021 0.100 0.068 0.105 0.182 0.245 0.335 0.460 0.074 0.113 0.198 0.263 0.335 0.460
Wall Mount
Audible
AH-12 AS-121575W
12 vdc 0.163 0.260
UL max* 0.192 0.320
12 vdc 0.076 0.195
UL max* 0.108 0.275
Audible
Strobe
Table 4: Average Current* (AMPS) For Series ASWP
Voltage
High dBA
Setting
(99) dBA
Medium dBA
Setting
(95) dBA
Low dBA
(90) dBA
#
Setting
24.0 VDC 0.128 0.105 0.098
UL Max* 0.168 0.155 0.150
* RMS current ratings are per UL average RMS method. UL max current rating is the maximum RMS current within the listed voltage range (16-33v
12 vdc 0.039 0.175
UL max* 0.058 0.265
for 24v units). For strobes the UL max current is usually at the minimum listed voltage (16v for 24v units). For audibles the max current is usually at the maximum listed voltage (33v for 24v units). For unfiltered FWR ratings, see installation instructions.