wheelock AS-24100C-FW, AS-24100C-FR, AS-2415C-FR, AS-2415C-FW, AS-2430C-FW INSTALLATION INSTRUCTIONS

...
273 Branchport Avenue Long Branch, NJ 07740 (800) 631-2148 (USA) Thank you for using our products. (800) 397-5777 (CANADA) INSTALLATION INSTRUCTIONS www.wheelockinc.com SERIES AS AUDIBLE STROBE APPLIANCES
(CEILING MOUNT VERSION)
Use this product according to this instruction manual. Please keep this instruction manual for future reference.
GENERAL:
Wheelock’s AS Audible Strobe Appliances are the industry’s first 2-wire horn strobe alarm appliances that can provide a selectable continuous or code 3 horn tone and continuous strobe when connected directly to the Fire Alarm Control Panel (FACP), or provide a synchronized code 3 and synchronized strobe when used in conjunction with a Sync Module (SM), Dual Sync Module (DSM) or Power Supply (PS-12/24-8 UL Only). The AS Appliances are UL Listed under Standard 1971 for Emergency Appliances for the Hearing Impaired and UL Standard 464 for Audible Signal Appliances. The AS is also ULC Listed under Standard CAN/ULC-S525­M87 for Visual Signaling Appliances and Standard CAN/ULC-S525-99 for Audible Signaling Appliances. They are listed for ceiling
mounting and indoor use only
gang and 4” backbox, 100mm European backbox or SHBB surface backbox (See Mounting Options). The AS Appliances use a Xenon flashtube with solid state circuitry enclosed in a rugged Lexan lens to provide maximum visibility and reliability for effective visible signaling.
Series AS Appliances can be field set to provide either High (HI) dBA, Medium (MED) dBA or Low (LO) dBA sound output.
All Series AS models are designed for use with either filtered DC (VDC) or unfiltered Full-Wave-Rectified (FWR) input voltage. All inputs are polarized for compatibility with standard reverse polarity supervision of circuit wiring by a Fire Alarm Control Panel (FACP).
The code 3 horn incorporates the temporal pattern (1/2 second on, 1/2 second off, 1/2 second on, 1/2 second off, 1/2 second
NOTE:
on, 1-1/2 off and repeat) specified by ANSI/NFPA for standard emergency evacuation signaling. The code 3 horn should be used only for fire evacuation signaling and not for any other purpose.
NOTE: All CAUTIONS and WARNINGS are identified by the symbol
WARNING: THE AS STROBE APPLIANCE IS A "FIRE ALARM DEVICE - DO NOT PAINT."
NOTE: All Canadian Installations should be in accordance with the Canadian Standard for the Installation of Fire Alarm Systems -
CAN/ULC-S524-01 and Canadian Electrical Code, Part 1. Final acceptance is subject to Authorities Having Jurisdiction.
WARNING: PLEASE READ THESE INSTRUCTIONS CAREFULLY BEFORE USING THIS PRODUCT. FAILURE TO COMPLY WITH ANY OF THE FOLLOWING INSTRUCTIONS, CAUTIONS AND WARNINGS COULD RESULT IN IMPROPER APPLICATION, INSTALLATION AND/OR OPERATION OF THESE PRODUCTS IN AN EMERGENCY SITUATION, WHICH COULD RESULT IN PROPERTY DAMAGE AND SERIOUS INJURY OR DEATH TO YOU AND/OR OTHERS.
SPECIFICATIONS:
Models
AS-2415C 24 16.0-33.0 20.0-31.0 15 AS-2430C 24 16.0-33.0 20.0-31.0 30 AS-2475C 24 16.0-33.0 20.0-31.0 75 AS-24100C 24 16.0-33.0 20.0-31.0 100
NOTE: THE MAXIMUM WIRE IMPEDANCE BETWEEN STROBES SHALL NOT EXCEED 35 OHMS. THE MAXIMUM NUMBER OF STROBES ON A SINGLE NAC CIRCUIT SHALL NOT EXCEED 47.
Copyright 2001 Wheelock, Inc. All rights reserved.
and equipped with a Universal Mounting Plate (UMP) that can be mounted to single-gang, double-
. All warnings are printed in bold capital letters.
Table 1: UL/ULC Ratings and Models
Regulated
Voltage
(VDC/VRMS)
Voltage Range Limit
Per UL 1971/464
(VDC/VRMS)
Voltage Range Per
CAN/ULC-S526-M87/S525-99
(VDC/VRMS)
Strobe
Candela
(cd)
P84024 E
Sheet 1 of 8
Table 2: dBA Sound Output
Description Volume Reverberant Per UL 464 Anechoic dBA Per CAN/ULC-S525-99
16.0VDC 24.0VDC 33.0VDC 20.0VDC 24.0VDC 31.0VDC Low 80 83 86 86 90 92
Continuous Horn Medium 85 88 91 91 95 98
High 88 91 93 95 99 101 Low 75 79 82 86 90 92
Code 3 Horn Medium 80 84 86 91 95 98
High 84 87 90 95 99 101
NOTES:
1. Strobe will produce 1 flash per second over the "Regulated Voltage" range.
2. Anechoic dBA is measured on-axis in a non-reflective (free field) test room using fast meter response. For peak dBA (measured
with peak meter response), add 5dBA to anechoic values shown in Table 2. Reverberant dBA is a minimum UL rating based on sound pressure measurements in a reverberant test room.
3. All models are UL Listed for indoor use with a temperature range of +32oF to +120oF (0oC to +49oC) and maximum humidity
of 93% RH, ± 2%.
4. Ratings - tested range -20% below and 10% above.
WARNING: FOR UL APPLIACATIONS THESE APPLIANCES WERE TESTED TO THE OPERATING VOLTAGE LIMITS OF 16-33 VOLTS USING FILTERED (DC) OR UNFILTERED FULL-WAVE RECTIFIED (FWR). DO NOT APPLY 80% AND 110% OF THESE VOLTAGE VALUES FOR SYSTEM OPERATION.
WARNING: FOR ULC APPLIACATIONS THESE APPLIANCES WERE TESTED TO THE OPERATING VOLTAGE LIMITS OF 20-31 VOLTS USING FILTERED (DC) OR UNFILTERED FULL-WAVE RECTIFIED (FWR). APPLY 80% AND 110% OF THESE VOLTAGE VALUES FOR SYSTEM OPERATION.
WARNING: CHECK THE MINIMUM AND MAXIMUM OUTPUT OF THE POWER SUPPLY AND STANDBY BATTERY AND SUBTRACT THE VOLTAGE DROP FROM THE CIRCUIT WIRING RESISTANCE TO DETERMINE THE APPLIED VOLTAGE TO THE STROBES.
Table 3: UL/ULC Current Ratings (AMPS) for 24VDC Models with Hi dBA Setting
Rated Average Current *
UL ULC AS-2415C AS-2430C AS-2475C AS-100C
Voltage Voltage MEAN RMS MEAN RMS MEAN RMS MEAN RMS
16.0VDC 20.0VDC 0.137 0.137 0.187 0.195 0.376 0.376 0.425 0.458
24.0VDC 24.0VDC 0.112 0.115 0.142 0.176 0.261 0.304 0.292 0.375
33.0VDC 31.0VDC 0.107 0.128 0.138 0.155 0.211 0.290 0.258 0.362
16.0VRMS 20.0VRMS ----- 0.182 ----- 0.244 ----- 0.483 ----- 0.544
24.0VRMS 24.0VRMS ----- 0.152 ----- 0.196 ----- 0.381 ----- 0.426
33.0VRMS 31.0VRMS ----- 0.159 ----- 0.183 ----- 0.339 ----- 0.398 Rated Peak Current **
UL Voltage ULC Voltage AS-2415C AS-2430C AS-2475C AS-24100C
16.0VDC 20.0VDC 0.160 0.255 0.510 0.670
24.0VDC 24.0VDC 0.180 0.280 0.610 0.710
33.0VDC 31.0VDC 0.195 0.300 0.640 0.750
16.0VRMS 20.0VRMS 0.210 0.320 0.560 0.690
24.0VRMS 24.0VRMS 0.245 0.360 0.640 0.770
33.0VRMS 31.0VRMS 0.500 0.550 0.660 0.825
Rated Inrush Current ***
UL Voltage ULC Voltage AS-2415C AS-2430C AS-2475C AS-24100C
16.0VDC 20.0VDC 0.110 0.110 0.110 0.110
24.0VDC 24.0VDC 0.165 0.165 0.165 0.165
33.0VDC 31.0VDC 0.230 0.230 0.230 0.230
16.0VRMS 20.0VRMS 0.155 0.155 0.155 0.155
24.0VRMS 24.0VRMS 0.235 0.235 0.235 0.235
33.0VRMS 31.0VRMS 0.325 0.325 0.325 0.325
* Rated average current is measured using mean value.
** The time duration for the peak current is 100 microseconds.
*** The time duration for the inrush current is 4 milliseconds.
P84024 E
Sheet 2 of 8
Table 3A: Rated Average Current (AMPS) for 24VDC Models with Medium and Low dBA Setting
Rated Average Current (Medium) *
UL ULC AS-2415C AS-2430C AS-2475C AS-24100C
Voltage Voltage MEAN RMS MEAN RMS MEAN RMS MEAN RMS
16.0VDC 20.0VDC 0.122 0.124 0.173 0.175 0.357 0.362 0.409 0.435
24.0VDC 24.0VDC 0.096 0.097 0.126 0.141 0.238 0.295 0.272 0.363
33.0VDC 31.0VDC 0.083 0.084 0.108 0.133 0.188 0.272 0.228 0.307
16.0VRMS 20.0VRMS ----- 0.155 ----- 0.225 ----- 0.461 ----- 0.529
24.0VRMS 24.0VRMS ----- 0.126 ----- 0.171 ----- 0.352 ----- 0.406
33.0VRMS 31.0VRMS ----- 0.120 ----- 0.153 ----- 0.304 ----- 0.372 Rated Average Current (Low) *
UL ULC AS-2415C AS-2430C AS-2475C AS-24100C
Voltage Voltage MEAN RMS MEAN RMS MEAN RMS MEAN RMS
16.0VDC 20.0VDC 0.118 0.118 0.168 0.168 0.349 0.355 0.402 0.455
24.0VDC 24.0VDC 0.086 0.086 0.119 0.136 0.230 0.277 0.265 0.355
33.0VDC 31.0VDC 0.073 0.073 0.100 0.106 0.173 0.253 0.218 0.301
16.0VRMS 20.0VRMS ----- 0.149 ----- 0.220 ----- 0.464 ----- 0.528
24.0VRMS 24.0VRMS ----- 0.118 ----- 0.166 ----- 0.342 ----- 0.402
33.0VRMS 31.0VRMS ----- 0.109 ----- 0.144 ----- 0.294 ----- 0.366
* Rated average current is measured using mean value.
WARNING: MAKE SURE THAT BOTH THE TOTAL AVERAGE CURRENT, TOTAL PEAK CURRENT AND TOTAL INRUSH CURRENT REQUIRED BY ALL APPLIANCES THAT ARE CONNECTED TO THE SYSTEM’S PRIMARY AND SECONDARY POWER SOURCES, NAC CIRCUITS, SM, DSM SYNC MODULES OR PS-12/24-8 POWER SUPPLY DO NOT EXCEED THE POWER SOURCES’ RATED CAPACITY OR THE CURRENT RATINGS OF ANY FUSES ON THE CIRCUITS TO WHICH THESE APPLIANCES ARE WIRED. OVERLOADING POWER SOURCES OR EXCEEDING FUSE RATINGS COULD RESULT IN LOSS OF POWER AND FAILURE TO ALERT OCCUPANTS DURING AN EMERGENCY, WHICH COULD RESULT IN PROPERTY DAMAGE AND SERIOUS INJURY OR DEATH TO YOU AND/OR OTHERS.
When calculating total average, peak or inrush currents: Use Table 3 and 3A to determine the highest value of “Rated Average Current” for an individual strobe (across the expected operating voltage range of the strobe) or the highest value of “Rated Inrush current” or “Rated Peak current” (whichever is higher) of an individual strobe (across the expected operating voltage range of the strobe) then multiply the value by the total number of strobes; be sure to add the currents for any other appliances, including audible signaling appliances, powered by the same source and include any required safety factor.
If the inrush current or peak current exceeds the power supplies’ inrush capacity, the output voltage provided by the power supplies may drop below the listed voltage range of the appliances connected to the supply and the voltage may not recover in some types of power supplies. For example, an auxiliary power supply that lacks filtering at its output stage (either via lack of capacitance and/or lack of battery backup across the output) may exhibit this characteristic.
CAUTION: Strobes are not designed to be used on coded systems in which the applied voltage is cycled on and off.
P84024 E
Sheet 3 of 8
Loading...
+ 5 hidden pages