wheelock AMT-12-LS, AMT-24-IS, AMT-24-LS, AMT-24-LSM INSTALLATION INSTRUCTIONS

273 Branchport Avenue Long Branch, NJ 07740 Thank you for using our products. (800) 631-2148 www.wheelockinc.com INSTALLATION INSTRUCTIONS
GENERAL:
The AMT Multitone Strobe Appliance are UL Listed under Standard 1971 for Emergency Appliances for the Hearing Impaired and UL Standard 464 for Audible Appliances. They are listed for indoor use only
with the backboxes specified in these instructions (See Mounting Options). Models with LS and IS strobes are Listed for wall or ceiling mounting; models with LSM strobes are Listed for wall mounting. The LSM strobes are listed at 15 candela under UL Standard 1971 and meet 75 candela intensity on axis with low current draw. The AMT Multitone Strobe Appliance use a xenon flashtube with solid state circuitry enclosed in a rugged Lexan lens to provide maximum visibility and reliability for effective visible signaling.
Wheelock's AMT Appliance are unique multitone alarm signals with separate input terminals for each sound. They are the ideal choice for suppression systems and emergency signaling systems where distinctive multiple alarm conditions are required. Eight groups of three self-prioritized sound outputs are provided with separate electrically isolated input terminals for each sound (see Table 2 and Table 8 for sound selections). Sound output can be field set to provide either HIGH (HI) dBA or STANDARD (STD) dBA sound output level.
All AMT Multitone Strobe models are designed for use with either filtered or unfiltered Full-Wave-Rectified (FWR) input voltage. The AMT Multitone Strobe Appliance have separate input terminals for alarm tone activation and strobe activation. The strobes can be easily field programmed to operate independently or in unison with all of the audible alarms. All inputs are polarized for compatibility with standard reverse polarity supervision of circuit wiring by a Fire Alarm Control Panel (FACP).
NOTE: All CAUTIONS and WARNINGS are identified by the symbol
WARNING: PLEASE READ THESE INSTRUCTIONS CAREFULLY BEFORE USING THIS PRODUCT. FAILURE TO COMPLY WITH ANY OF THE FOLLOWING INSTRUCTIONS, CAUTIONS AND WARNINGS COULD RESULT IN IMPROPER APPLICATION, INSTALLATION AND/OR OPERATION OF THESE PRODUCTS IN AN EMERGENCY SITUATION, WHICH COULD RESULT IN PROPERTY DAMAGE AND SERIOUS INJURY OR DEATH TO YOU AND/OR OTHERS.
WARNING: THE AMT MULTITONE STROBE APPLIANCE MUST BE FIELD SET TO THE DESIRED dBA SOUND OUTPUT LEVEL AND ALARM TONE BEFORE THEY ARE INSTALLED. THIS IS DONE BY PROPERLY INSERTING A JUMPER PLUG AND ADJUSTING A FOUR POSITION SWITCH IN ACCORDANCE WITH THESE INSTRUCTIONS. INCORRECT SETTINGS WILL RESULT IN IMPROPER PERFORMANCE AND MAY DAMAGE THE PRODUCT, WHICH COULD RESULT IN PROPERTY DAMAGE AND SERIOUS INJURY OR DEATH TO YOU AND/OR OTHERS.
SPECIFICATIONS
:
Table 1: UL Listed Models
Model
Nominal
Voltage
(VDC)
Rated
Voltage
(VDC)
Strobe
Candela
(CD)
Mounting
Options
AMT-12-LS 12 10.5-15.6 15 AMT-24-LS 24 20.0-31.0 15 A,B,C,D AMT-24-LSM 24 20.0-31.0 15* E,F,G AMT-24-IS 24 20.0-31.0 75
*15cd models are Listed at 15cd and meet 75cd on axis.
. All warnings are printed in bold capital letters.
WARNING: THESE APPLIANCES WERE TESTED TO THE OPERATING VOLTAGE LIMITS OF 20-31 VOLTS FOR 24V MODELS AND 10.5-15.6 VOLTS FOR 12V MODELS USING FILTERED (DC) OR UNFILTERED FULL-WAVE RECTIFIED (FWR). DO NOT APPLY 80% AND 110% OF THESE VOLTAGE VALUES FOR SYSTEM OPERATION.
Check the minimum and maximum output of the power supply and standby battery and subtract the voltage drop from the circuit wiring resistance to determine the applied voltage to the signaling appliance.
WARNING: WHEELOCK STRONGLY RECOMMENDS THAT THE VOLTAGE APPLIED TO THESE PRODUCTS BE WITHIN THEIR RATED VOLTAGE RANGE. THE APPLICATION OF IMPROPER VOLTAGE MAY RESULT IN DEGRADED OPERATION OR DAMAGE TO THESE PRODUCTS, WHICH COULD RESULT IN PROPERTY DAMAGE AND SERIOUS INJURY OR DEATH TO YOU AND/OR OTHERS.
Copyright 1995, 1996, 2000 Wheelock, Inc. All rights reserved.
P82478 C
Sheet 1 of 10
Table 2: Current Ratings for AMT Multitone Audible Signals
Rated Average Rated Average
Tone Tone Description Current (Amps) Current (Amps)
24VDC 12VDC HI dBA STD
dBA
HI dBA STD
dBA Horn Broadband Horn (Continuous) 0.040 0.023 0.100 0.020 Bell 1560 Hz Modulated (0.07 Sec. ON/Repeat) 0.016 0.012 0.031 0.010 March Time Horn Horn (0.25 Sec. ON/0.25 Sec. OFF/Repeat) 0.040 0.023 0.100 0.020 Code 3 Horn Horn (ANSI S3.41 Temporal Pattern) 0.040 0.023 0.100 0.020 Code 3 Tone 500 Hz (ANSI S3.41 Temporal Pattern) 0.028 0.017 0.060 0.015 Slow Whoop 500-1200Hz Sweep (4.0 Sec. ON/0.5 Sec.
0.048 0.026 0.100 0.025
OFF/Repeat) Siren 600-1200Hz Sweep (1.0 Sec. ON/Repeat) 0.036 0.023 0.082 0.020 HI/LO 1000/800 Hz (0.25 Sec. ON/Alternate) 0.020 0.015 0.044 0.013 Vibrating Chime 700Hz (1.0 Sec. Decay/Repeat) 0.017 0.012 0.027 0.010
Add 25% more input current than shown in Table 2 when operating the unit at maximum input voltage.
Add strobe current from Table 4 to audible signal current from Table 2 to obtain total current for each unit, if the strobe and audible are wired to operate in unison on a single circuit.
Table 3: dBA for AMT Multitone with Strobe
Tone
Anechoic
dBA @ 10'
Nominal
Voltage
Reverberant
DBA @ 10' Per UL 464
Minimum
Voltage
Nominal
Voltage
HI STD HI STD HI STD Horn 98 92 82 79 85 82 Bell 91 86 79 75 82 75 March Time Horn 98 92 82 75 85 79 Code 3 Horn 98 92 82 75 82 79 Code 3 Tone 94 89 82 79 85 79 Slow Whoop 98 93 79 75 82 75 Siren 97 92 79 73* 79 75 HI/LO 92 87 79 75 82 75 Vibrating Chimes 88 82 75 70* 79 73*
Anechoic dBA is measured on-axis in a non-reflective (free field) test room using fast meter response. For peak dBA (measured with peak meter response), add 5 dBA to anechoic values shown in Table 3. Reverberant dBA is a minimum UL rating based on sound power measurements in a reverberant test room.
WARNING: AMT MULTITONE STROBE MODELS SET ON "SIREN AND VIBRATING CHIME TONES" WITH STANDARD dBA DO NOT MEET THE 75 dBA MINIMUM UL REVERBERANT SOUND LEVEL REQUIRED FOR PUBLIC MODE FIRE PROTECTION SERVICE (NOTED BY * IN TABLE
3). MODELS WITH SETTINGS WHICH PRODUCE LESS THAN 75 dBA MAY NOT BE HEARD. THIS SETTING IS ACCEPTABLE ONLY FOR GENERAL SIGNALING (NON­FIRE ALARM) USE. USE THE "HIGH" dBA SETTING WITH THIS TONE OR USE A DIFFERENT TONE FOR PUBLIC MODE SERVICE.
Table 4: Strobe Current Requirement (AMPS)
Rated Average
Rated Peak Current Rated Inrush Current
Current
Voltage LS LSM IS LS LSM IS LS LSM IS
20.0VDC .090 .130 .275 .160 .250 .500 .210 .225 .650
24.0VDC .090 .130 .250 .190 .260 .450 .250 .270 .660
31.0VDC .090 .130 .205 .210 .260 .370 .320 .360 .880
20.0VFWR .095 .140 .300 .210 .350 .700 .320 .315 .920
24.0VFWR .095 .140 .275 .216 .365 .640 .380 .380 .930
31.0VFWR .095 .140 .230 .240 .365 .520 .450 .500 1.25
10.5VDC .170 --- --- .340 --- --- .300 --- ---
12.0VDC .170 --- --- .340 --- --- .300 --- ---
15.6VDC .170 --- --- .340 --- --- .390 --- ---
10.5VFWR .170 --- --- .475 --- --- .420 --- ---
12.0VFWR .170 --- --- .475 --- --- .420 --- ---
15.6VFWR .170 --- --- .475 --- --- .545 --- ---
P82478 C
Sheet 2 of 10
WARNING: MAKE SURE THAT THE TOTAL AVERAGE CURRENT, TOTAL PEAK CURRENT AND TOTAL INRUSH CURRENT REQUIRED BY ALL APPLIANCES THAT ARE CONNECTED TO THE SYSTEM'S PRIMARY AND SECONDARY POWER SOURCES, SIGNALING CIRCUITS, SM, DSM SYNC MODULES AND PS-12/24-8 DO NOT EXCEED THE POWER SOURCES' RATED CAPACITY OR THE CURRENT RATINGS OF ANY FUSES ON THE CIRCUITS TO WHICH THESE APPPLIANCES ARE WIRED. OVERLOADING POWER SOURCES OR EXCEEDING FUSE RATINGS COULD RESULT IN LOSS OF POWER AND FAILURE TO ALERT OCCUPANTS DURING AN EMERGENCY, WHICH COULD RESULT IN PROPERTY DAMAGE AND SERIOUS INJURY OR DEATH TO YOU AND/OR OTHERS.
When calculating the total average, peak and inrush currents: Use Table 4 to determine the highest value of "Rated Average Current" for an individual strobe (across the expected operating voltage range of the strobe), determine the highest value of "Rated Inrush Current" or "Tated Peak Current" (whichever is higher) of an individual strobe (across the expected voltage range of the strobe), then multiply these values by the total number of strobes; be sure to add the currents for any other appliances, including audible signaling appliances, powered by the same source and include any required safety factors.
If the inrush current or peak current exceeds the power supplies' inrush capacity, the output voltage provided by the power supplies may drop below the listed voltage range of the appliances connected to the supply and the voltage may not recove in some types of power supplies. For example, an auxiliary opower supply that lacks filtering at its output stage (either via lack of capacitance and/or lack of battery backup across the output) may exhibit this characteristic.
CAUTION
WARNING: THE STROBES ARE DESIGNED TO FLASH AS SPECIFIED WITH CONTINUOUS (NON-CODED) APPLIED VOLTAGE. THE STROBES MAY NOT FLASH IF USED IN CODED SYSTEMS.
: Strobes are not designed to be used on coded systems in which the applied voltage is cycled on and off.
All models are UL Listed for indoor use only with a temperature range of 32oF to 120oF (0oC to 49oC) and maximum humidity of 85% RH.
CAUTION
: If Multitone Strobe Appliances are operated within 15 inches of a person’s ear, they can produce a sound pressure level that exceeds the maximum 120 dBA permitted by ADA and OSHA rules. Exposure to such sound levels can result in damage to a person’s hearing.
NOTE: This equipment has been tested and found to comply with the limits for a Class B digital appliance, pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in residential installation. This equipment generates, uses and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures:
1) Reorient or relocate the receiving antenna, 2) Increase the separation between the equipment and receiver, 3) Connect the equipment into an outlet on a circuit different from that to which the receiver is connected, and 4) Consult the dealer or an experienced radio/TV technician for help.
P82478 C
Sheet 3 of 10
Loading...
+ 7 hidden pages