wheelock AHWP INSTALLATION INSTRUCTIONS

273 Branchport Avenue Long Branch, NJ 07740 Thank you for using our products. (800) 631-2148 www.cooperwheelock.com INSTALLATION INSTRUCTIONS
SERIES AH-WP INDOOR/OUTDOOR AUDIBLE HORN APPLIANCES
Use this product according to this instruction manual. Please keep this instruction manual for future reference.
Cooper Wheelock’s AH-WP Audible Horn Appliances are designed to provide a selectable continuous horn or code 3 tone when connected directly to the Fire Alarm Control Panel (FACP), or provide a synchronized code 3 horn when used in conjunction with a Sync Module (SM), Dual Sync Module (DSM) or Wheelock’s Power Supplies. The AH-WP Appliances are UL Listed under UL Standard 464 for Audible Signal Appliances. The AH-24WP is ULC Listed under Standard CAN/ULC-S525-99 for Audible Signaling Appliances. They are listed for indoor and outdoor use and can be mounted to a 4” backbox (See Mounting Options).
AH-WP Appliances can be field set to provide either High (HI) dBA, Medium (MED ) dBA or Low (LO) dBA sound output.
All AH-WP models are designed for use with either filtered DC (VDC) or unfiltered Full-Wave-Rectified (FWR) input voltage. All inputs are polarized for compatibility with standard reverse polarity supervision of circuit wiring by a FACP.
NOTE: The code 3 horn incorporates the temporal pattern (1/2 second on, 1/2 second off, 1/2 second on, 1/2 second off, 1/2 second on, 1-1/2 off and repeat) specified by ANSI/NFPA for standard emergency evacuation signaling.
The code 3 horn shall be used only for fire evacuation signaling and not for any other
purpose.
NOTE: All CAUTIONS and WARNINGS are identified by the symbol
. All warnings are printed in bold capital letters.
WARNING: THE AH-WP APPLIANCE IS A "FIRE ALARM DEVICE - DO NOT PAINT."
WARNING: PLEASE READ THESE INSTRUCTIONS CAREFULLY BEFORE USING THIS PRODUCT. FAILURE TO COMPLY WITH ANY OF THE FOLLOWING INSTRUCTIONS, CAUTIONS AND WARNINGS COULD RESULT IN IMPROPER APPLICATION, INSTALLATION AND/OR OPERATION OF THESE PRODUCTS IN AN EMERGENCY SITUATION, WHICH COULD RESULT IN PROPERTY DAMAGE AND SERIOUS INJURY OR DEATH TO YOU AND/OR OTHERS.
SPECIFICATIONS:
Table 1: UL/ULC Listed Models and Ratings
Maximum RMS Current (AMPS)
DC FWR
Model
Regulated
Voltage
(VDC/VRMS)
UL Voltage
Range
(VDC/VRMS)
ULC Voltage
Range
(VDC/VRMS)
Lo Med Hi Lo Med Hi
AH-24WP 24 16-33 20-31 0.021 0.043 0.080 0.041 0.051 0.090 AH-12WP 12 8-17.5 ----- 0.058 0.108 0.192 0.059 0.109 0.209
Model AH-12WP is not ULC listed.
Table 1A: ULC Current Ratings 24VDC Models
Average Current (AMPS) Model ULC Voltage
AH-24
(VDC/VRMS)
20.0 .014 .020 .035
Lo Med Hi
24.0 .017 .025 .050
31.0 .021 .030 .065
Table 2: dBA Sound Output for 24VDC Models
Reverberant dBA Per UL 464 Anechoic Per CAN/ULC-S525-99 Description Volume
16.0VDC 24VDC 33.0VDC 16.0VDC 24VDC 33.0VDC
Low 80 83 86 88 90 92
Continuous Horn Medium 85 88 91 90 95 97
High 88 91 93 92 97 99 Low 75 79 82 88 90 92
Code 3 Horn Medium 80 84 86 90 95 97
High 84 87 90 92 97 99
Copyright 2006 Cooper Wheelock, Inc. All rights reserved.
P83641 L
Sheet 1 of 4
Table 2A: dBA Sound Output for 12VDC Models
Description Volume Reverberant Per UL 464
8.0VDC 12VDC 17.5VDC Low 80 83 86
Continuous Horn Medium 85 88 91
High 88 91 93 Low 75 79 82
Code 3 Horn Medium 80 84 86
High 84 87 89
NOTES:
1. All models are UL/ULC Listed for indoor and outdoor use with a temperature range of -31
o
F to +151oF (-35oC to 66oC) and maximum humidity of
98% RH.
Table 2B: ULC Directional Characteristics
-3 dBA: 48 degrees left, 41 degrees right
-6 dBA: 50 degrees left, 58 degrees right
WARNING: CHECK THE MINIMUM AND MAXIMUM OUTPUT OF THE POWER SUPPLY AND STANDBY BATTERY AND SUBTRACT THE VOLTAGE DROP FROM THE CIRCUIT WIRING RESISTANCE TO DETERMINE THE APPLIED VOLTAGE TO THE SIGNALING APPLIANCE.
WARNING: FOR UL APPLICATIONS THESE APPLIANCES WERE TESTED TO THE OPERATING VOLTAGE LIMITS OF 16-33 VOLTS FOR 24V MODELS AND 8-17.5 VOLTS FOR 12V MODELS USING FILTERED (DC) OR UNFILTERED FULL-WAVE-RECTIFIED (FWR). DO NOT APPLY 80% AND 110% OF THESE VOLTAGE VALUES FOR SYSTEM OPERATION.
WARNING: FOR ULC APPLICATIONS THESE APPLIANCES WERE TESTED TO THE OPERATING VOLTAGE LIMITS OF 20-31 VOLTS FOR 24V MODELS AND 10.5-15.6 VOLTS FOR 12V MODELS USING FILTERED (DC) OR UNFILTERED FULL-WAVE-RECTIFIED (FWR). APPLY 80% AND 110% OF THESE VOLTAGE VALUES FOR SYSTEM OPERATION.
WARNING: MAKE SURE THAT THE TOTAL RMS CURRENT, TOTAL AVERAGE CURRENT AND TOTAL PEAK CURRENT REQUIRED BY ALL APPLIANCES THAT ARE CONNECTED TO THE SYSTEM’S PRIMARY AND SECONDARY POWER SOURCES, NAC CIRCUITS, SM, DSM SYNC MODULES OR WHEELOCK’S POWER SUPPLIES DO NOT EXCEED THE POWER SOURCES’ RATED CAPACITY OR THE CURRENT RATINGS OF ANY FUSES ON THE CIRCUITS TO WHICH THESE APPLIANCES ARE WIRED. OVERLOADING POWER SOURCES OR EXCEEDING FUSE RATINGS COULD RESULT IN LOSS OF POWER AND FAILURE TO ALERT OCCUPANTS DURING AN EMERGENCY, WHICH COULD RESULT IN PROPERTY DAMAGE AND SERIOUS INJURY OR DEATH TO YOU AND/OR OTHERS.
When calculating the total currents: Use Table 1 to determine the highest value of “RMS Current” for an individual AH Appliance (across the expected operating voltage range of the AH Appliance) or use Table 1A to determine the highest value of “Rated Average Current” of an individual AH Appliance (across the expected voltage range of the AH Appliance), then multiply these values by the total number of AH Appliances; be sure to add the currents for any other appliances, powered by the same source and include any required safety factors.
If the peak current exceeds the power supplies’ peak capacity, the output voltage provided by the power supplies may drop below the listed voltage range of the appliances connected to the supply and the voltage may not recover in some types of power supplies. For example, an auxiliary power supply that lacks filtering at its output stage (either via lack of capacitance and/or lack of battery backup across the output) may exhibit this characteristic.
CAUTION: Audible Horn appliances are not designed to be used on coded systems in which the applied voltage is cycled on and off.
WARNING: THE AUDIBLE HORN APPLIANCES MUST BE FIELD SET TO THE DESIRED TONE AND dBA SOUND OUTPUT LEVEL BEFORE THEY ARE INSTALLED. THIS IS DONE BY PROPERLY INSERTING A JUMPER PLUG IN ACCORDANCE WITH THESE INSTRUCTIONS. INCORRECT SETTINGS WILL RESULT IN IMPROPER PERFORMANCE, WHICH COULD RESULT IN PROPERTY DAMAGE AND SERIOUS INJURY OR DEATH TO YOU AND/OR OTHERS.
SOUND OUTPUT (SPL) SETTINGS:
Figure 1: Showing Location of Jumper Plug J1 and J1.
P83511
J2 J1
J2
J1
C
H
O
M
D E
L
+ -
AUD
3
Factory setting is on Medium dB and Code 3.
C O
H
D E
M
3
L
Figure 2: Jumper Plug Settings for High, Medium, Low dB, Code 3 Horn and Continuous Horn Setting
P83641 L
Sheet 2 of 4