INSTALLATION INSTRUCTIONS
HORNS
Use this product according to this instruction manual. Please keep this instruction manual for future reference.
GENERAL:
Wheelock offers a complete line of high performance AC horns. Wheelock's Horns are ideal for General Signaling Applications
where high output, low current draw and dependability are of critical concern.
All models provide rugged, vandal resistant construction with die cast housing to protect the horn mechanism. A full range of
mounting options are provided for indoor and outdoor installations.
NOTE: All CAUTIONS and WARNINGS are identified by the symbol
WARNING: PLEASE READ THESE INSTRUCTIONS CAREFULLY. FAILURE TO COMPLY WITH ANY OF THE
FOLLOWING INSTRUCTIONS, CAUTIONS AND WARNINGS COULD RESULT IN IMPROPER APPLICATION,
INSTALLATION AND/OR OPERATION OF THESE PRODUCTS IN AN EMERGENCY SITUATION, WHICH COULD RESULT
IN PROPERTY DAMAGE, SERIOUS INJURY OR DEATH TO YOU AND/OR OTHERS.
WARNING: THE 31T HORN APPLIANCE IS A “FIRE ALARM DEVICE – DO NOT PAINT.”
SPECIFICATIONS:
. All warnings are printed in bold capital letters.
Table 1: Ratings Per UL
Model
Number
Regulated
Voltage
(VRMS)
Voltage
Range
(VRMS)
Maximum
RMS Current
(AMPS)
Reverberant
dBA
Per UL 464
Mounting
Options
31T-115 120 96-132 0.160 87 A,B,C,D,E
WARNING: FOR UL APPLICATIONS THESE APPLIANCES WERE TESTED TO THE OPERATING VOLTAGE LIMITS
OF 96-132 VOLTS. DO NOT APPLY 80% AND 110% OF THESE VOLTAGE VALUES FOR SYSTEM OPERATION.
WARNING: MAKE SURE THAT THE TOTAL RMS CURRENT REQUIRED BY ALL APPLIANCES THAT ARE
CONNECTED TO THE SYSTEM’S PRIMARY AND SECONDARY POWER SOURCES DO NOT EXCEED THE POWER
SOURCES’ RATED CAPACITY OR THE CURRENT RATINGS OF ANY FUSES ON THE CIRCUITS TO WHICH THESE
APPLIANCES ARE WIRED. OVERLOADING POWER SOURCES OR EXCEEDING FUSE RATINGS COULD RESULT IN
LOSS OF POWER AND FAILURE TO ALERT OCCUPANTS DURING AN EMERGENCY, WHICH COULD RESULT IN
PROPERTY DAMAGE AND SERIOUS INJURY OR DEATH TO YOU AND/OR OTHERS.
When calculating the total currents: Use Table 1 to determine the highest value of “RMS Current” for an individual horn (across
the expected operating voltage range of the horn), then multiply these values by the total number of horns; be sure to add the
currents for any other appliances, including audible signaling appliances, powered by the same source and include any required
safety factors.
.
WIRING DIAGRAM:
Figure 1: Figure 2: Typical Wiring
FROM PRECEDING APPLIANCE,
FIRE ALARM CONTROL PANEL (FACP)
+
-
+
TO NEXT APPLIANCE OR
END OF LINE
-
RESISTOR (EOLR)
Copyright 2004 Wheelock, Inc. All rights reserved.
(+) (-)
P10010 AC
Sheet 1 of 4
MOUNTING OPTIONS:
CAUTION: The following figures show the maximum number of field wires (conductors) that can enter the backbox used
with each mounting option. If these limits are exceeded, there may be insufficient space in the backbox to accommodate the
field wires and stresses from the wires could damage the product.
Although the limits shown for each mounting option comply with the National Electrical Code (NEC), Wheelock recommends
use of the largest backbox option shown and the use of approved stranded field wires, whenever possible, to provide additional
wiring room for easy installation and minimum stress on the product from wiring.
BASIC HORN
A
FLUSH BACKBOX
TO BE MOUNTED
IN WALL
FLUSH MOUNTING
THE BASIC HORN IS SUPPLIED
WITH SCREW TERMINALS FOR
CONNECTION TO THE POWER
SOURCE, (2) #10-32 SCREWS
FOR ACCESSORIES *
MOUNTED TO THE UNIT
GRILLE IF REQUIRED, AND
(2) #8-32 SCREWS FOR
INSTALLATION.
* IF NO ACCESSORIES ARE
USED REQUIRING THESE
SCREWS, INSERT THEM INTO
THE UNUSED HOLES.
B
WEATHER RESISTANT MOUNTING
1/2" CONDUIT
WEATHER RESISTANT
BACKBOX TO BE
MOUNTED IN WALL
MAXIMUM NUMBER OF CONDUCTORS
AWG #18 AWG #16 AWG #14 AWG #12
4 4 44
D
CONCEALED CONDUIT MOUNTING
ADAPTOR PLATE WITH
(4) #8-32 & #6-32
SCREWS & BUSHING
STANDARD 4"
SQUARE BACKBOX
ENTRANCE
ON TOP
BASIC HORN
(4) #8-32 SCREWS
EXISTING BOX
IN WALL
BASIC HORN
FLUSH PLATE WITH
(2) #10-32 AND
(2) #8-32 SCREWS
MAXIMUM NUMBER OF CONDUCTORS
AWG #1 8 AWG #16 AWG #1 4 AWG #12
4
C
SEMI-FLUSH PLATE
WITH (2) #8-32
SCREWS
BASIC HORN
(2) #10-32
SCREWS
MAXIMUM NUMBER OF CONDUCTORS
AWG #18 AWG #16 AWG #14 AWG #12
E
BASIC HORN
4 4 4
SEMI-FLUSH MOUNTI NG
STANDARD 4" SQUARE
BACKBOX TO BE
MOUNTED IN WALL
(2) #8-32 SCREWS
4 4 44
SURFACE MOUNTING
STANDARD 4" SQUARE
BACKBOX TO BE
MOUNTED ON WALL
SURFACE
(2) #10-32
SCREWS
MAXIMUM NUMBER OF CONDUCTORS
AWG #18 AWG #16 AWG #14 AWG #12
BASIC HORN
(2) #8-32 SCREWS
4 4 44
(2) #10-32
SCREWS
MAXIMUM NUMBER OF CONDUCTORS
AWG #18 AWG #16 AWG #14 AWG #12
4 4 44
(2) #8-32 SCREWS
P10010 AC
Sheet 2 of 4