West Penn LL5162RD1000 Specsheet

Technical Data Sheet LL5 NYC Fire Alarm Pl
PART NUMBER:
DESCRIPTION: 16/2 Solid bare copper conductors, unshielded with an overall jacket.
APPROVALS: (UL) Listed
APPLICATION: Plenum Rated for Local Law 5 New York City Fire Alarm Cables
enum Cables
LL5162
2833 West Chestnut Street
Washington, PA 15301
Toll Free: (800) 245-4964
Fax: (724) 222-6420
www.westpenn-wpw.com
Construction Parameters:
Conductor 16 AWG Bare Copper Stranding Solid Insulation Material Insulation Thickness 0.016'' Nom. Number of Conductors 2 Shield None Drain None Jacket Material Jacket Thickness .026” Nom. Overall Cable Diameter .212” Nom. Approximate Cable Weight 32 Lbs/1M' Nom. Flame Rating NFPA- 262
Fluoropolymer
Fluoropolymer
Electrical & Environmental Properties:
Temperature Rating -20deg C to 150deg C Operating Voltage 300 V RMS Max.Capacitance Between Conductors @ 1 KHz 20 pf/ft Nom. DC Resistance per Conductor @ 20deg C 4.1 Ohms/1M' Nom. Insulation Colors Black, Red Jacket Color Red RoHS Compliant Yes
Mechanical Properties:
Max. Recommended Pull Tension 65 lbs. Min. Bend Radius (Install) 2.1”
Specification Issue Date: 10/09
This document is the property of West Penn Wire.
.
The information contained herein is considered Proprietary and not to be reproduced by any means Without written consent of West Penn Wire
Standard Lengths are 1000ft. The Jacket is sequentially footmarked. The information presented here is, to the best of our knowledge, is true and accurate. However, since conditions of use are beyond our control, all recommendations or suggestions are presented without guarantee or responsibility on our part. We disclaim all liability in connection with the use of information contained herein or otherwise.
Loading...