West Penn D980RD1000 Specsheet

Technical Data Sheet Fire Alarm Cables-
PART NUMBER:
DESCRIPTION: 18/2 Solid bare copper conductors, unshielded with an overall jacket.
APPROVALS: (UL) Listed
APPLICATION: Indoor data fire alarm cable for (Data Circuits, Initiating Circuits, Notification Circuits, Addressable
Addressable
D980
Systems)
2833 West Chestnut Street
Washington, PA 15301
Toll Free: (800) 245-4964
Fax: (724) 222-6420
www.westpenn-wpw.com
Construction Parameters:
Conductor 18 AWG Bare Copper Stranding Solid Insulation Material Polyolefin Insulation Thickness 0.015'' Nom. Number of Conductors 2 Shield None Drain None Jacket Material PVC Jacket Thickness 0.030'' Nom. Overall Cable Diameter 0.182'' Nom. Approximate Cable Weight 21 Lbs/1M' Nom. Flame Rating UL 1666 Riser Flame Test
Electrical & Environmental Properties:
Temperature Rating -20deg C to 60deg C Operating Voltage 300 V RMS Max.Capacitance Between Conductors @ 1 KHz 16 pf/ft Nom. DC Resistance per Conductor @ 20deg C 6.5 Ohms/1M' Nom. Velocity of Propagation 71% Nom. Insulation Colors Black, Red Jacket Color Red RoHS Compliant --
Mechanical Properties:
Max. Recommended Pull Tension 39.2 lbs. Min. Bend Radius (Install) 2”
Specification Issue Date: 7/06
This document is the property of West Penn Wire.
.
The information contained herein is considered Proprietary and not to be reproduced by any means Without written consent of West Penn Wire
Standard Lengths are 1000ft. The Jacket is sequentially footmarked. The information presented here is, to the best of our knowledge, is true and accurate. However, since conditions of use are beyond our control, all recommendations or suggestions are presented without guarantee or responsibility on our part. We disclaim all liability in connection with the use of information contained herein or otherwise.