Technical Data Sheet
Fire Alarm Cables
PART NUMBER:
DESCRIPTION: 18/2 Solid bare copper conductors, unshielded with an overall jacket.
NEC RATING: FPLP, NEC Article 760
APPROVALS: (UL) Listed
APPLICATION: Indoor within ducts, plenums, and other spaces used for environmental air for (Audio Circuits,
Construct ion Parameters:
Conductor 18 AWG Bare Copper
Stranding Solid
Insulation Material Teflon
Insulation Thickness 0.012'' Nom.
Number of Conductors 2
Shield None
Drain None
Jacket Material Flex Plenum PVC
Jacket Thickness 0.015'' Nom.
Overall Cable Diameter 0.165'' Nom.
Approximate Cable Weigh t 18 Lbs/1M' Nom.
Flame Rating NFPA- 262 Flame Test
Electrical & Environm e n tal Properties:
Temperature Rating -10deg C to 60deg C
Operating Voltage 300 V RMS
Max.Capacitance Between C onductors @ 1 KHz 16 pf/ft Nom.
DC Resistance per Conductor @ 20deg C 6.5 Ohms/1M' Nom.
Nom. Impedance 107 Ohms
Insulation Colors Black, Red
Jacket Color Red
RoHS Compliant Yes
Mechanical Properties:
Max. Recommended Pu ll Tension 55 lbs.
Min. Bend Radius (Install) 1.5”
Specification Issu e Date: 1/14
.
The inform at i o n contained her ein is considered
Proprietary and not to be reproduced by any means
Without written consent of West Penn Wire
Washington, PA 15301
Toll Free: (800) 245-4964
Fax: (724) 222-6420
www.westpenn-wpw.com
D60980
Control Circuits, Initiating Circuits, Notification Circuits)
The Jacket is sequentia lly footmarked.
The information presented here is, to the best of our
knowledge, is true and accurate. However , since
conditions of use are beyond our control, all
recommendations or sugg estions are pr esented
without guarantee or resp onsibility on our part. We
disclaim all liability in connection with the use of
information contained herein or otherwise.