Detailed Specification & Technical Data
D60975
18/2 - Shielded Low Capacitance FPLP Rated
Addressable Fire Alam SLC Circuits
Construction & Dimensions
CONSTRUCTION & DIMENSIONS
CONDUCTOR PARAMETER
• Number of Conductors 2
• AWG Size 18
• Conductor Stranding Solid
• Conductor Type Bare Copper
• Nominal DCR 6.5 Ohm/1000
INSULATION PARAMETER
• Insulation Type FEP
• Insulation ickness 0.012 in
• Insulation Color Code 1. Black 2.Red
SHIELDING PARAMETER
• Shield Type Overall 100% Aluminum Foil
• Drain Wire Type Tinned Copper
• Drain Wire AWG 24 AWG
ELECTRICAL CHARACTERISTICS
• Nom. Cap. Between Conductors 25 pF/
• Nom. Cap. Conductor to Shield 45 pF/
-
-
-
-
-
Overall Construction
OVERALL CONSTRUCTION PARAMETERS
Jacket Type Flexible Plenum
Jacket ickness 0.015 in
Nominal Cable O.D. 0.165 in
Plenum Yes
NEC UL Rating FPLP
RoHS Compliant Yes
Pull Tension 53 lbs
Bend Radius 1.485 in
Cable Weight 27 lbs
-
Overall Electrical & Optical Characteristics
OVERALL ELECTRICAL/OPTICAL CHARACTERISTICS
UL Flammability NFPA 262 Plenum
Operating Range -0 to 60 Deg C
UL Voltage Rating 300
-