West Penn 998RD1000 Specsheet

2833 West Chestnut Street
Washington, PA 15301
Toll Free: (800) 245-4964
Fax: (724) 222-6420
www.westpenn-wpw.com
This document is the property of West Penn Wire. The information contained herein is considered Proprietary and not to be reproduced by any means
Without written consent of West Penn Wire
Standard Lengths are 1000ft. The Jacket is sequentially footmarked. The information presented here is, to the best of our knowledge, is true and accurate. However, since conditions of use are beyond our control, all recommendations or suggestions are presented without guarantee or responsibility on our part. We disclaim all liability in connection with the use of
information contained herein or otherwise.
Technical Data Sheet Fire Alarm Cables
PART NUMBER: 998
DESCRIPTION: 12/2 Solid bare copper conductors, unshielded with an overall jacket.
NEC RATING: FPLR, NEC Article 760
APPLICATION: Indoor for (Audio Circuits, Control Circuits, Initiating Circuits, Notification Circuits)
Construction Parameters:
Conductor 12 AWG Bare Copper Stranding Solid Insulation Material Polypropylene Insulation Thickness 0.010'' Nom. Number of Conductors 2 Shield None Drain None Jacket Material PVC Jacket Thickness 0.017'' Nom. Overall Cable Diameter 0.244'' Nom. Approximate Cable Weight 57 Lbs/1M' Nom. Flame Rating UL 1666 Riser Flame Test
Electrical & Environmental Properties:
Temperature Rating -20deg C to 60deg C Operating Voltage 300 V RMS Max.Capacitance Between Conductors @ 1 KHz 23 pf/ft Nom. DC Resistance per Conductor @ 20deg C 1.53 Ohms/1M' Nom. Insulation Colors Black, Red Jacket Color Red – optional: Black RoHS Compliant Yes
Mechanical Properties:
Max. Recommended Pull Tension 158 lbs. Min. Bend Radius (Install) 2.5”
Specification Issue Date: 8/13
.