Detailed Specification & Technical Data
998
12/2 Solid Unshielded FPLR
Fire Alarm Signaling
Construction & Dimensions
CONSTRUCTION & DIMENSIONS
CONDUCTOR PARAMETER
• Number of Conductors 2
• AWG Size 12
• Conductor Stranding Solid
• Conductor Type Bare Copper
• Nominal DCR 1.8 Ohm/1000
• Cabling Lay Length 4.25 in
• Twists/Foot 2.8 twist/
INSULATION PARAMETER
• Insulation Type Polypropylene - PP
• Insulation ickness 0.01 in
• Insulation Color Code 1. Black 2.Red
SHIELDING PARAMETER
• Shield Type None
ELECTRICAL CHARACTERISTICS
• Nom. Cap. Between Conductors 23 pF/
-
-
-
-
-
Overall Construction
OVERALL CONSTRUCTION PARAMETERS
Jacket Type PVC
Jacket ickness 0.022 in
Nominal Cable O.D. 0.244 in
Plenum No
NEC UL Rating FPLR
RoHS Compliant Yes
Pull Tension 158 lbs
Bend Radius 2.195 in
Cable Weight 57 lbs
-
Overall Electrical & Optical Characteristics
OVERALL ELECTRICAL/OPTICAL CHARACTERISTICS
UL Flammability UL1666 Vertical Sha
Operating Range -20 to 60 Deg C
UL Voltage Rating 300
-
2833 West Chestnut Street | Washington, PA 15301 | Toll Free: 800-245-4964 | www.westpenn-wpw.com
Detailed Specification & Technical Data
998
12/2 Solid Unshielded FPLR
Fire Alarm Signaling
Related Products
RELATED PRODUCTS
Plenum Number 60995B
Aquaseal Direct Burial Number AQ227
-
2833 West Chestnut Street | Washington, PA 15301 | Toll Free: 800-245-4964 | www.westpenn-wpw.com