Detailed Specification & Technical Data
994S
14/2 Stranded Unshielded FPLR
Fire Alarm Signaling
Construction & Dimensions
CONSTRUCTION & DIMENSIONS
CONDUCTOR PARAMETER
• Number of Conductors 2
• AWG Size 14
• Conductor Stranding Stranded
• Conductor Type Bare Copper
• Nominal DCR 2.6 Ohm/1000
• Cabling Lay Length 3.5 in
• Twists/Foot 3.4 twist/
INSULATION PARAMETER
• Insulation Type Polypropylene - PP
• Insulation ickness 0.01 in
• Insulation Color Code 1. Black 2.Red
SHIELDING PARAMETER
• Shield Type None
ELECTRICAL CHARACTERISTICS
• Nom. Cap. Between Conductors 23 pF/
-
-
-
-
-
Overall Construction
OVERALL CONSTRUCTION PARAMETERS
Jacket Type PVC
Jacket ickness 0.022 in
Nominal Cable O.D. 0.222 in
Plenum No
NEC UL Rating FPLR
RoHS Compliant Yes
Pull Tension 99 lbs
Bend Radius 1.998 in
Cable Weight 41 lbs
-
Overall Electrical & Optical Characteristics
OVERALL ELECTRICAL/OPTICAL CHARACTERISTICS
UL Flammability UL1666 Vertical Sha
Operating Range -20 to 60 Deg C
UL Voltage Rating 300
-
2833 West Chestnut Street | Washington, PA 15301 | Toll Free: 800-245-4964 | www.westpenn-wpw.com