Technical Data Sheet
Fire Alarm Cables
PART NUMBER:
DESCRIPTION: 14/2 Solid bare copper conductors, unshielded with an overall jacket.
NEC RATING: FPLP, NEC Article 760
APPROVALS: (UL) Listed
APPLICATION: Indoor within ducts, plenums, and other spaces used for environmental air for (Audio Circuits,
2833 West Chestnut Street
Washington, PA 15301
Toll Free: (800) 245-4964
Fax: (724) 222-6420
www.westpenn-wpw.com
60993B
Control Circuits, Initiating Circuits, Notification Circuits)
Construction Parameters:
Conductor 14 AWG Bare Copper
Stranding Solid
Insulation Material PVC
Insulation Thickness 0.010'' Nom.
Number of Conductors 2 (1 Pair)
Shield None
Drain None
Jacket Material PVC
Jacket Thickness 0.015'' Nom.
Overall Cable Diameter 0.198'' Nom.
Approximate Cable Weight 36 Lbs/1M' Nom.
Flame Rating NFPA- 262 Flame Test
Electrical & Environmental Properties:
Temperature Rating -10deg C to 60deg C
Operating Voltage 300 V RMS
Max.Capacitance Between Conductors @ 1 KHz 34 pf/ft Nom.
DC Resistance per Conductor @ 20deg C 2.6 Ohms/1M' Nom.
Insulation Colors Black, Red
Jacket Color Red, Blue, Yellow
RoHS Compliant Yes
Mechanical Properties:
Max. Recommended Pull Tension 99.4 lbs.
Min. Bend Radius (Install) 1.9”
Specification Issue Date: 7/06
This document is the property of West Penn Wire.
.
The information contained herein is considered
Proprietary and not to be reproduced by any means
Without written consent of West Penn Wire
Standard Lengths are 1000ft.
The Jacket is sequentially footmarked.
The information presented here is, to the best of our
knowledge, is true and accurate. However, since
conditions of use are beyond our control, all
recommendations or suggestions are presented
without guarantee or responsibility on our part. We
disclaim all liability in connection with the use of
information contained herein or otherwise.