Detailed Specification & Technical Data
60993B
14/2 Solid Unshielded FPLP
Fire Alarm Signaling
Construction & Dimensions
CONSTRUCTION & DIMENSIONS
CONDUCTOR PARAMETER
• Number of Conductors 2
• AWG Size 14
• Conductor Stranding Solid
• Conductor Type Bare Copper
• Nominal DCR 2.6 Ohm/1000
• Cabling Lay Length 3.25 in
• Twists/Foot 3.7 twist/
INSULATION PARAMETER
• Insulation Type Plenum PVC
• Insulation ickness 0.09 in
• Insulation Color Code 1. Black 2.Red
SHIELDING PARAMETER
• Shield Type None
ELECTRICAL CHARACTERISTICS
• Nom. Cap. Between Conductors 34 pF/
-
-
-
-
-
Overall Construction
OVERALL CONSTRUCTION PARAMETERS
Jacket Type Flexible Plenum
Jacket ickness 0.015 in
Nominal Cable O.D. 0.198 in
Plenum Yes
NEC UL Rating FPLP
RoHS Compliant Yes
Pull Tension 99 lbs
Bend Radius 1.782 in
Cable Weight 36 lbs
-
Overall Electrical & Optical Characteristics
OVERALL ELECTRICAL/OPTICAL CHARACTERISTICS
UL Flammability NFPA 262 Plenum
Operating Range -0 to 60 Deg C
UL Voltage Rating 300
-
2833 West Chestnut Street | Washington, PA 15301 | Toll Free: 800-245-4964 | www.westpenn-wpw.com
Detailed Specification & Technical Data
60993B
14/2 Solid Unshielded FPLP
Fire Alarm Signaling
Related Products
RELATED PRODUCTS
Non Plenum Number 994
Aquaseal Number AQC226
Aquaseal Direct Burial Number AQ226
-
2833 West Chestnut Street | Washington, PA 15301 | Toll Free: 800-245-4964 | www.westpenn-wpw.com