West Penn 60975BSOR1000 Specsheet

Detailed Specification & Technical Data
60975BS
18/2 Stranded Shielded FPLP
Fire Alarm Signaling
Construction & Dimensions
CONSTRUCTION & DIMENSIONS CONDUCTOR PARAMETER
• Number of Conductors 2
• AWG Size 18
• Conductor Stranding Stranded
• Conductor Type Bare Copper
• Nominal DCR 6.5 Ohm/1000
• Twists/Foot 4 twist/
INSULATION PARAMETER
• Insulation Type Plenum PVC
• Insulation ickness 0.008 in
• Insulation Color Code 1. Black 2.Red
SHIELDING PARAMETER
• Shield Type Overall 100% Aluminum Foil
• Drain Wire Type Tinned Copper
• Drain Wire AWG 24 AWG
ELECTRICAL CHARACTERISTICS
• Nom. Cap. Between Conductors 66 pF/
• Nom. Cap. Conductor to Shield 119 pF/
-
-
-
-
-
Overall Construction
OVERALL CONSTRUCTION PARAMETERS
Jacket Type Flexible Plenum
Jacket ickness 0.015 in
Nominal Cable O.D. 0.148 in
Plenum Yes
NEC UL Rating FPLP
RoHS Compliant Yes
Pull Tension 53 lbs
Bend Radius 1.33 in
Cable Weight 22 lbs
-
Overall Electrical & Optical Characteristics
OVERALL ELECTRICAL/OPTICAL CHARACTERISTICS
UL Flammability NFPA 262 Plenum
Operating Range -0 to 60 Deg C
UL Voltage Rating 300
-
2833 West Chestnut Street | Washington, PA 15301 | Toll Free: 800-245-4964 | www.westpenn-wpw.com