West Penn 357GY0500, 357GY1000 Specsheet

2833 West Chestnut Street
Washington, PA 15301
Toll Free: (800) 245-4964
Fax: (724) 222-6420
www.westpenn-wpw.com
This document is the property of West Penn Wire. The information contained herein is considered Proprietary and not to be reproduced by any means
Without written consent of West Penn Wire
Standard Lengths are 1000ft. The Jacket is sequentially footmarked. The information presented here is, to the best of our knowledge, is true and accurate. However, since conditions of use are beyond our control, all recommendations or suggestions are presented without guarantee or responsibility on our part. We disclaim all liability in connection with the use of
information contained herein or otherwise.
Technical Data Sheet Communication Cables
PART NUMBER: 357
DESCRIPTION: 22/4 Stranded Bare copper conductors, shielded/unshielded with an overall jacket.
NEC RATING: CMR, NEC Article 800
APPLICATION: Indoor for: Intercom, Security, Sound, Audio, Background Music, and Power Limited Control
Construction Parameters:
Conductor 22 AWG Bare Copper Stranding 7x30 Insulation Material Polypropylene Insulation Thickness 0.007'' Nom. Number of Conductors 4 (2 Shielded)(2 Unshielded) Shield 100% Aluminum Polyester Foil Drain Stranded Tinned Copper Jacket Material PVC Jacket Thickness 0.017'' Nom. Overall Cable Diameter 0.162'' Nom. Approximate Cable Weight 18.2 Lbs/1M' Nom. Flame Rating UL 1666 Riser Flame Test
Electrical & Environmental Properties:
Temperature Rating -20°C To +60°C Operating Voltage 300 V RMS Max.Capacitance Between Conductors @ 1 KHz 34 pf/ft Nom. Capacitance Between Conductors to Shield @ 1 KHz 67 pf/ft Nom. DC Resistance per Conductor @ 20deg C 16.4 Ohms/1M' Nom. Insulation Colors Shielded: Black, Red Unshielded: White, Green Jacket Color Gray RoHS Compliant Yes
Mechanical Properties:
Max. Recommended Pull Tension 42 lbs. Min. Bend Radius (Install) 1.8”
Specification Issue Date: 7/14
.
Circuits.