West Penn 25225BBK1000, 25225BGN1000, 25225BGY0500, 25225BGY1000, 25225BSGN1000 Specsheet

...
Technical Data Sheet Plenum Communication Cables
PART NUMBER:
DESCRIPTION: 16/2 Stranded bare copper conductors, unshielded with an overall jacket.
NEC RATING: CMP, NEC Article 800
APPLICATION: Indoor within ducts, plenums and other spaces used for environmental air for: (Intercom, Security, Sound, Audio, Background music)
25225B
2833 West Chestnut Street
Washington, PA 15301
Toll Free: (800) 245-4964
Fax: (724) 222-6420
www.westpenn-wpw.com
Construction Parameters:
Conductor 16 AWG Bare Copper Stranding 19x29 Insulation Material Flex Plenum PVC Insulation Thickness 0.008'' Nom. Number of Conductors 2 Shield None Drain None Jacket Material Flex Plenum PVC Jacket Thickness 0.015'' Nom. Overall Cable Diameter 0.176'' Nom. Approximate Cable Weight 25 Lbs/1M' Nom. Flame Rating NFPA 262 Flame Test
Electrical & Environmental Properties:
Temperature Rating -10°C To +60°C Operating Voltage 300 V RMS Max.Capacitance Between Conductors @ 1 KHz 33 pf/ft Nom. DC Resistance per Conductor @ 20deg C 4.2 Ohms/1M' Nom. Insulation Colors Black, Red Jacket Color Gray, Black, Green RoHS Compliant Yes
Mechanical Properties:
Max. Recommended Pull Tension 54 lbs Min. Bend Radius (Install) 1.8”
Specification Issue Date: 7/06
This document is the property of West Penn Wire.
.
The information contained herein is considered Proprietary and not to be reproduced by any means Without written consent of West Penn Wire
Standard Lengths are 1000ft. The Jacket is sequentially footmarked. The information presented here is, to the best of our knowledge, is true and accurate. However, since conditions of use are beyond our control, all recommendations or suggestions are presented without guarantee or responsibility on our part. We disclaim all liability in connection with the use of information contained herein or otherwise.
Loading...