Westinghouse IL 33-DAH-1 User Manual

IL 33-DAH-1
Digitrip Retrofit System for
Westinghouse DA-75 Breakers
Table of Contents
SAFETY PRECAUTIONS................................................................................................................1
Kit Components List.........................................................................................................................2
Step 1: General Breaker Preparation............................................................................................3
Step 2: Removing the Original Electromechanical Trip Units........................................................3
Step 3: Preparing the Sensors......................................................................................................4
Step 4: Installing the Sensors........................................................................................................4
Step 5: Installing the Trip Unit Mounting Platform..........................................................................5
Step 6: Preparing the Trip Unit Assembly......................................................................................6
Step 7: Installing the Trip Unit........................................................................................................6
Step 8: Installing the Trip Finger....................................................................................................7
Step 9: Installing the Reset Arm Assembly...................................................................................7
Step 10: Installing the DTA Assembly.............................................................................................8
Step 12: Installing the Breaker Mounted CPT.................................................................................9
Step 13: Final Connection of the Harnesses and Wiring...............................................................11
Step 14: Installing the Auxiliary Switch..........................................................................................14
Step 15: Testing the Breaker.........................................................................................................15
Step 16: Mounting the Cell Harness.............................................................................................15
Step 17: Installing the Retrofitted Breaker in the Cell....................................................................16
Kit Parts List...................................................................................................................................17
Torque Values for General Mounting..............................................................................................21
Torque Values for Copper BUS Connectors...................................................................................21
INDEX............................................................................................................................................25
Digitrip Retrofit System for Westinghouse DA-75 Breakers

SAFETY PRECAUTIONS

WARNING
POWER CIRCUIT BREAKERS ARE EQUIPPED WITH HIGH SPEED, HIGH ENERGY OPERATING MECHANISMS. THE BREAKERS AND THEIR ENCLOSURES ARE DESIGNED WITH SEVERAL BUILT-IN INTERLOCKS AND SAFETY FEATURES INTENDED TO PROVIDE SAFE AND PROPER OPERATING SEQUENCES. TO PRO­VIDE MAXIMUM PROTECTION FOR PERSON­NEL ASSOCIATED WITH THE INSTALLATION, OPERATION, AND MAINTENANCE OF THESE BREAKERS, THE FOLLOWING PRACTICES MUST BE FOLLOWED. FAILURE TO FOLLOW THESE PRACTICES MAY RESULT IN DEATH, PERSONAL INJURY, OR PROPERTY DAMAGE.
• Only qualified persons, as defined in the National Electric Code, who are familiar with the installa­tion and maintenance of power circuit breakers and their associated switchgear assemblies should perform any work associated with these breakers.
IL 33-DAH-1
• Completely read and understand all instructions before attempting any installation, operation, maintenance, or modification of these breakers.
Always turn off and lock out the power source
feeding the breaker prior to attempting any installation, maintenance, or modification of the breaker. Do not use the circuit breaker as the sole means for isolating a high voltage circuit. Follow all lockout and tagging rules of the National Electric Code and all other applicable codes, regulations, and work rules.
• Do not work on a closed breaker or a breaker with the closing springs charged. Trip (open) the breaker and be sure the stored energy springs are discharged before performing any work. The breaker may trip open or the charging springs may discharge, causing crushing or cutting injuries.
• For drawout breakers, trip (open), and then remove the breaker to a well-lit work area before beginning work.
• Do not perform any maintenance: including breaker charging, closing, tripping, or any other function which could cause significant movement of the breaker while it is on the extension rails. Doing so may cause the breaker to slip from the rails and fall, potentially causing severe personal injury to those in the vicinity.
• Do not leave the breaker in an intermediate position in the switchgear cell. Always leave it in the connected, disconnected, or (optional) test position. Failure to do so could lead to improper positioning of the breaker and flashover, causing death, serious personal injury, and / or property damage.
Do not defeat any safety interlock. Such interlocks are intended to protect personnel and equipment from damage due to flashover and exposed contacts. Defeating an interlock could lead to death, severe personal injury, and / or property damage.
Effective December, 1998
Page 2
IL 33-DAH-1
Cutler-Hammer Digitrip Retrofit Kits are available in a number of configurations that provide a wide
which level of Retrofit Kit is to be installed and
which components are included with the Kit. range of features. The Digitrip System starts with the 510 Basic Kit which offers true RMS sensing, overcurrent protection, and self-testing features. Advanced Digitrip Retrofit Kits feature zone interlocking, digital alphanumeric displays, remote alarm signals, IMPACC communications, energy
The instructions contained in this manual cover the
installation of all levels of Retrofit Kit. If the Kit you
are installing does not contain a certain component,
skip the instructions for that component and
proceed to the next. monitoring capabilities, power factors, and harmonic content measurements.
Throughout the Retrofit process, refer to the Torque
Tables at the back of this manual for specific The following table provides a quick reference of
torque values. the components supplied with each level of Retrofit Kit. Before beginning the Retrofit process, take a minute to review the information contained in the table. It is important that the Retrofitter understand
If you have any questions concerning the Retrofit
Kit and / or the Retrofit process, contact
Cutler-Hammer at 1-800-937-5487.
510 with
Components 510 Basic Zone 610 810 910
Interlock
Trip Unit Rating Plug Auxiliary Current
Transformer (CT) Module
Auxiliary CT Harness
Sensors Sensor Harness Direct Trip
Actuator (DTA) Mounting Brackets
and Hardware External Plug 1 Connector 2 Connector 4 Connector 4 Connector
Harness Harness Harness Harness Harness Cell Harness Breaker Mounted
Control Power Transformer (CPT)
Potential Transf ormer (PT) Module
Auxiliary Switch
Effective December, 1998
IL 33-DAH-1
Page 3

Step 1: General Breaker Preparation

Before attempting to remove the Breaker from the cell or perform any Retrofit Operation, be sure to read and understand the Safety Precautions section of this manual. In addition, be sure to read and understand the
Instructions for the Application of Digitrip RMS Retrofit Kits on Power Circuit Breakers
(Retrofit Application Data - Publication
AD 33-855-1), supplied with the Digitrip Retrofit Kit.
WARNING
DO NOT ATTEMPT TO INSTALL OR PERFORM MAINTENANCE ON EQUIPMENT WHILE IT IS ENERGIZED. SEVERE PERSONAL INJURY OR DEATH CAN RESULT FROM CONTACT WITH ENERGIZED EQUIPMENT. VERIFY THAT NO VOLTAGE IS PRESENT BEFORE PROCEEDING.
A. Trip the Breaker and remove it from the Cell.
Move the Breaker to a clean, well-lit work bench.
To begin the Retrofit Process, refer to the components list at the end of this manual. Lay out the components and hardware according to the steps outlined. The components and hardware will be used to complete each step in the Retrofit Process.
Step 2: Removing the Original
Electromechanical T rip Units
Follow the Westinghouse DA-75 Instruction Manual, originally supplied with the Breaker, to perform the following procedure.
A. Remove and scrap the original
Electromechanical Trip units and all associated hardware.
NOTE: It is the responsibility of the Retrofitter to insure that the Breaker and all original components are in good condition. Visually inspect all Breaker components for signs of damage or wear. If any signs of damage or wear are detected for components not included in the Retrofit Kit, secure the necessary replacement parts before beginning the Retrofit Process.
The force necessary to trip the Breaker should not exceed seven (7) lbs.
Effective December, 1998
Page 4
IL 33-DAH-1

Step 3: Preparing the Sensors

A. Place each Sensor between two Glass Poly
Insulation Plates. The connector stabs should be positioned towards the cutouts in the Insulation Plates as shown.
B. Secure the Glass Poly Plates on either side of
the Sensors using the (12) .250-20 × 2.00" bolts, (24) flat washers, and (12) elastic stop nuts supplied. Note that the bolts must be installed so that the bolt heads will be against the back of the Breaker and the stop nuts away from the Breaker (same side as the screw heads of the Sensor terminals). Do not over tighten the bolts.

Step 4: Installing the Sensors

A. Remove and save the center bolts securing the
bottom Finger Clusters to the Breaker Stabs. Remove the Finger Clusters.
B. Install a Sensor Assembly over each Breaker
Stab, with the Sensor terminals pointing downward and the bolt heads outward as shown.
C. Reinstall the Finger Clusters and secure them
using the original hardware.
Effective December, 1998
IL 33-DAH-1
(4)
Page 5
Step 5: Installing the Trip Unit Mounting
Platform
A. Using Drilling Plan “A”, drill and counter sink
two .375" holes in both the left and right Breaker side plates.
B.
Mount the right and left Trip Unit Support Brackets to the Breaker side plates as shown, using the (4) .312-18 × .750" flat head screws, (4) flat washers, (4) lock washers, and (4) nuts
supplied.
Do not tighten them completely at this time.
NOTE: The holes for mounting the DTA (see Step 10) should also be drilled and countersunk in the right Breaker Frame at this time.

Drilling Plan “A”

6.50" 2.00"
1.81"
Drill 0.375" Dia. and
0.75"
0.75"
Countersink to 0.578" Head Size (2) Right Side Only
Drill 0.375" Dia. and Countersink to 0.578" Head Size
2.38"
NOTE: For ease of assembly, the 2-Point Terminal Block (Step 11-A) can be mounted to the inside of the right Trip Unit Support Bracket at this time.
C. Mount the Trip Unit Mounting Platform to the
Support Brackets using the (4) .312-18 × .750" bolts, (8) flat washers, (4) lock washers, and (4) nuts supplied. Tighten the hardware connecting the Mounting Platform to the Support Brackets, and then the Support Brackets to the Breaker side plates. Assure that the Mounting Platform and Support Brackets are square with the Breaker.
Effective December, 1998
Page 6
IL 33-DAH-1

Step 6: Preparing the Trip Unit Assembly

A.
For Kits Supplied with a PT Module Only.
the PT Module to the Glass Poly Insulation Barrier as shown, using the (2) .138-32 × .500" screws, (4) flat washers, (2) lock washers, and (2) nuts supplied.
D. Mount the Trip Unit Mounting Brackets to the
sides of the Aux. CT Module, using the (4) .190-32 × .375" screws, (4) lock washers, and (4) flat washers supplied, so they “pinch” the Trip Unit in place.
Mount
E. Remove the Trip Unit cover and install the
Rating Plug. Replace the cover.
F. Install the Digitrip Nameplate on the top of the
Trip Unit.
B. Secure the Glass Poly Insulation Barrier to
the back of the Aux. CT Module using the (2) .190-32 × .375" screws, (2) lock washers, and (2) flat washers supplied.
C. Install the Trip Unit on the top of the Aux. CT
Module using the (2) brass spacers, (2) .190-32 × 4.00" screws, (2) lock washers, and (2) flat washers supplied as shown. Note that the brass spacers are placed between the bottom of the Trip Unit and the top of the Aux. CT Module.
G. Connect the Aux. CT Harness to the Trip Unit
and Aux. CT Module.

Step 7: Installing the Trip Unit

A. Mount the Trip Unit / Aux. CT Module Assembly
to the Trip Unit Mounting Platform as shown, using the (4) .250-20 × .750" bolts, (8) flat washers, (4) lock washers, and (4) nuts supplied.
Effective December, 1998
IL 33-DAH-1
Page 7

Step 8: Installing the Trip Finger

A. Note the position of the original Trip Finger and
associated “gap” between the Trip Finger and manual Trip Shaft. Remove the original Trip Finger and scrap the mounting hardware.

Step 9: Installing the Reset Arm Assembly

B. Mount the new Trip Finger on the top of the
Cross Bar (with the curve upward and the notch to the right) as shown, and the original Trip Finger back on the bottom of the Cross Bar. Secure using the (2) .190-32 × 1.75" bolts, (4) flat washers, (2) lock washers, and (2) nuts supplied.
C. Verify that the original Trip Finger has been
reinstalled in its initial position by checking the gap (noted in Step 8-A) between the original Trip Finger and manual Trip Shaft.
GAP
A. Remove the original Interlock Arm. Scrap the
original bolts, washers, and nuts.
B. Mount the Reset Arm Assembly to the bottom
of the Cross Bar and the original Interlock Arm to the top of the Cross Bar in its original position, using the (2) .190-32 × 1.75" bolts, (4) flat washers, (2) lock washers, and (2) nuts supplied. The Reset Arm Assembly should be positioned so that the Reset Arm is hanging downward as shown.
Effective December, 1998
Loading...
+ 18 hidden pages