1.0 UL LISTED GROUND FAULT SENSING AND RELAYING EQUIPMENT
Type GFR ground fault relays, current sensors, test panels and accessory devices are UL listed by Underwriters' Lab-oratories, Inc. in accordance with their standard for
Ground Fault Sensing and Relaying Equipment, UL 1053,
under File E48381.
Fig.
-
lB
Ground Fault Relay-Mechanical Reset Interlocking
(Cat.
No.
GFR60Ml)
Removable
Link
---
Turn Lock
Ground Indicator-Depress
to
Reset
With
Adjusting Switches
Screw
to
Settings
Fault
Trip
Zone
2.0 GENERAL PURPOSE
A type erly installed
phase to ground fault currents. When the level
current
GFR
ground fault protection system, when prop-
on
a grounded electrical system, will sense
is
in excess
of
the pre-selected current pick-up
of
fault
and time delay settings, the GFR relay will initiate a trip action
of
a disconnect device, which will open the faulted
circuit and clear the fault.
The GFR devices are UL
Class
I devices designed to
protect electrical equipment against extensive damage
from arcing ground faults.
CAUTION: GROUND FAULT PROTECTION SYSTEMS DESIGNED TO PROTECT EQUIPMENT CANNOT SIMULTANEOUSLY PROVIDE PROTECTION
FOR PERSONNEL AGAINST ELECTRIC SHOCK HAZARDS, SINCE THIS TYPE PROTECTION REQUIRES A SENSI-
LOW
TIVITY IN THE
MILLI-AMPERE RANGE.
Removable
Link
Type
,____
___
Fig. 2 Typical Ground Fault Sensors
Solid
Core
Type
3.0
Courtesy of NationalSwitchgear.com
DESCRIPTION
3
A basic type
of
a ground fault relay (GFR)
fault current sensor (GFS)
GFR
ground fault protection system consists
as
shown in Fig. 1, a ground
as
illustrated in Fig. 2 and a disconnect device equipped with a shunt trip device. This disconnect device can be a molded case circuit breaker,
a power circuit breaker, a bolted pressure switch or fusible disconnect device, suitable for application
other
with UL Class I Ground Fault Sensing and Relaying equipment. A typical molded case circuit breaker with a shunt trip
complete style number, add group suffix from below,
@For
complete catalog number, add suffix from below,
@All types require 120 volt,
C!>
After March, 1983, an with the
SPB
and Digitrip interlocks.
"A"
12M
50/60
Hz. control for test winding.
suffix will be included after the
60M
as
1200M 12MD
as
G11, GOl, G03.
12EI, 60EI, 1200£1.
GFR
style number to signify
De
120 Volt
Style l 293C83
Cat. No. GFR
Control
<D
<al
Pick-up In Amperes
1-12 5-60 Gl
l
Gl2
GOl G03
G02 G04
GOS
12MID
60MID 1200MID
G06 G08
60MD
that
the
GFR
interlock
@
is
comparable
100-1200
G07
1200MD
4.3.1.3 Multiple Zones
of
Protection
With
Zone
Selective Interlocking
Establish time/current coordination multiple zones without zone interlocking. This on the basis
that
most faults occur downstream and that
as
in 4.3.1.2 for
is
done
the most downstream device should be set to clear the fault first leaving upstream devices for back-up fault protection.
Add zone interlocking to provide fast tripping
stream devices regardless
of
pre-set time delay for faults in
of
up-
the upstream zones.
Where
desired, nearly instantaneous operation
of
down-stream devices can be defeated were time delayed op-erations are adequate. See 4.2.2.2.
5.0 RELAY TYPE SELECTION (See Fig. 1)
5
.1
Available Relay Types
The GFR ground fault relays are available in two basic types, ie, with and without zone selective interlocking. Each type relay must be reset following a trip operation.
of
Each
the basic type relays
is
available with either an
electrically held or mechanically latched
output
relay. The electrically held type must be electrically reset remotely -usually
the control power circuit. In this type, a red lamp
via
a normally closed, momentary pushbutton in
is
pro-vided for visual ground fault trip indication. The mechani-cally latched type must be manually reset by depressing the pushbutton on the face reset
bottom
also serves cator. A complete list Table
1.
of
the GFR relay. This manual
as
a mechanical pop-up trip indi-
of
available styles
is
provided
in
5.2 Setting Adjustments
Each type relay
is
provided with two switches that are adjustable over the range selected. The top adjusting knob,
as
shown in Fig. 1, adjusts the pick-up level
of
the ground fault current. The bottom adjusting knob adjusts the time delay range. The calibration marks provided for both
adjustments
are
shown in Table 2. After the desired values have been pre-set, the adjusting knobs can be locked in position by the pointer lock screw shown in
Fig.
1.
5.3 Ground Fault Signal Memory
Arcing ground fault currents are, by definition, erratic nature being caused by the intermittent striking and
in
re-
-++++--r+---
Courtesy of NationalSwitchgear.com
3~-·+
....
~---+---+--+++-»---r+----
2---.-+f-<
~~-+,1+---J_
1----.-~-+H
s~~~~
.._
5 r-t-·+
~+--
J:---------+-
01~
...-
--,,
005--
003----+-+--
DOI--·-
~
-+--4--+
._..
1---
-t-h-f---
~
t-t-
----------+--t+
-=---=1-
,_,_.---
-.
~
~--
-
--+!-<-
~
__:__:___-_-=_+--
-t-+--+
+
--
+---+I-+
i --
----r---+
------+-----+---t -+-+-+--
--+--
---+-
--+----+-
----+---1 ---+----t-+
t +
---+---
44
-
-+--
;.:-:H=-.-~:_:____
-:J-+-=--:--:-:---
-+-~·1
~+---;-----r-
'"
I;
t+
~-
+ • •
r-+-+
.,.
•---------+---+-
+ +
-+----+--f-+
+~
+----+---+-•
--+--+--
I
~
--+
+.
___
. -
+.
-+----.-
----~-~--+-!++~
_..,. •
------,-·
~
--r-~-
.,.
-----r_____._
-~-
-+--__,____,____+-....-
+--
•
•-+-
Cl
0 0 0 G
M
~
MINIMUM
PICK
~--...-----r----+-----+-
--+----1-t
-
·+~~---1-
I •
~
+ •
..
.....
~t-
· ·
+-
+
r-~~-~~
J--..-
~~==
....
-;--+--+-----
T--+---t
+•
--+--·
..
+-+----
t-
-
-+--
-;
----+---------~--+
r
--
1:
• j
1---
+-
-
.----+-+
. :-::-::t
0
UP
SEITINGS.
AMPERES
+-
+-
• --.-+---i-
...-+,-
.
so.
+.
--.-
-++---
...
+~-+--+-1-
....
--
+-----r-+-+r
-+
+---r--+---+-+
...
-+-+---+T-
+ t t +
·-
+
-
~
+--
i.
-
t+----
+-+-
a a a
•
·---~10
L .
.
~--113
--
~.
·----.. -005
+
••. -002
++-~3
·-~-2
--1
·---02
••••
003
Fig.
8 GFR Relay Time-Current Curve
8
Courtesy of NationalSwitchgear.com
striking neous resetting time the fault current drops fault relays are equipped with a memory response, which integrates these intermittent faults with time using a seven second time constant.
*All Adjustments
5.4 Time-Current Curves
The time/current performance curve lay has a flat response, ie., the operating time fault current above its pick-up setting stant. There as delay tolerances,
of
an arcing ground fault. To avoid the instanta-
of
the solid state timing circuitry every
to
zero, Type GFR ground
Table 2
Pick-up
Amperes
1-12 1
5-60 5 10
100-1200
Time Delay Cycles
indicated in Fig. 8, but very little. The pick-up and time
100 200
I
are
is
some small variation in the lower ranges
are±
Dial Marking*
3 5 7
2
15
25 35
300 500
10
15
25
in discrete steps.
10%.
9 12
45
700
900
45
35
of
a Type GFR
of
is
essentially con-
60
1200
60
re-
any given
for multi-level system applications where only the mini-mum amount ing an arcing ground fault.
5.5.3
TYPEOFOPERATION
Electrically held relays will satisfy most applications where reliable control power interruption. Where control power load side tion
is selected. Also, in applications where the control power less than reliable and where an automatic reset could fect interlocking circuitry, the mechanically held relay should be selected.