Westgate DV62 Technical Manual

Page 1
SHERWOOD INDUSTRIES IS AN ENVIRONMENTALLY RESPONSIBLE COMPANY. THIS MANUAL IS PRINTED ON RECYCLED
PLEASE KEEP THESE INSTRUCTIONS FOR FUTURE REFERENCE
PAPER.
DV62
B Y : S H E R W O O D I N D U S T R I E S L T D
TECHNICAL
MANUAL
INSTALLER:
Leave this manual with the appliance.
CONSUMER:
Retain this manual for future reference.
WHAT TO DO IF YOU SMELL GAS
• Open windows/extinguish any open ame.
• Do not try to light any appliance.
• Do not touch any electrical switch; do not use any phone in your building.
• Immediately call your gas supplier from a neighbour’s phone. Follow the gas supplier’s instructions.
• If you cannot reach your gas supplier, call the re department.
FOR YOUR SAFETY: Do not store or use gasoline or
other ammable vapours and liquids in the vicinity of
this or any other appliance.
WARNING: If the information in this manual is
not followed exactly, a re or explosion may result
causing property damage, personal injury or loss of
life. Installation and service must be performed by a
qualied installer, service agency or the gas supplier.
This appliance may be installed in an
after-market permanently located,
This appliance is only for use with
the type of gas indicated on the
rating plate. This appliance is not
convertible for use with other gases,
unless a certied kit is used.
Massachusetts installations (Warning): This product must be installed by a licensed plumber or gas tter when installed within the Commonwealth of Massachusetts. Other Massachusetts code requirements: Flexible connector must not be longer than 36in., a shut off valve must be installed; only direct vent sealed combustion products are approved for bedrooms/bathrooms. A carbon monoxide detector is required in all rooms containing gas red direct vent appliances. The replace damper must be removed or welded in the open position prior to installation of a replace insert.
50-2163
Page 2
Safety PrecautionS
FOR SAFE INSTALLATION AND OPERATION OF YOUR “WESTGATE” HEATER, PLEASE CAREFULLY READ THE FOLLOWING INFORMATION:
• All Westgate gas-red appliances must be installed in accordance with their instructions. Carefully read all the instructions in this manual rst. Consult the building authority having jurisdiction to determine the need for a permit prior to commencing the installation.
• NOTE: Failure to follow these instructions could cause a malfunction of the replace, which could result in death, serious bodily injury, and/or property damage.
• Failure to follow these instructions may also void your re insurance and/or warranty.
GENERAL
• Installation and repair should be done by a qualied service person. The appliance should be inspected before the rst use and, at least, annually by a qualied service person. More frequent cleaning may be required due to excessive lint from carpeting, bedding material, etc. It is imperative the control compartments, burners and circulating air passageways of the appliance be kept clean.
• Due to high temperatures, the appliance should be located out of high trafc areas and away from furniture and draperies.
Children and adults should be alerted to the hazards of high surface temperatures and should stay away to avoid burn or clothing ignition.
• Young children should be carefully supervised when they are in the same room as the appliance, Toddlers, young children and others may be susceptible to accidental contact burns. A physical barrier is recommended if there are at risk individuals in the house. To restrict access to a replace or stove, install an adjustable safety gate to keep toddlers, young children and other at risk individuals out of the room and away from hot surfaces.
• Clothing or other ammable materials should not be placed on or near the appliance.
• To prevent injury, if the pilot or pilot and burners have gone out on their own, open the glass door and wait 5 minutes to air out before attempting to re-light the replace.
• Always keep the area around these appliances clear of combustible material, gasoline and other ammable liquids and vapours.
• These appliances should not be used as a drying rack for clothing or for hanging Christmas stockings/ decorations.
• Due to the paint curing on the replace, odor and slight smoking will likely be noticed when the replace is rst used. Open a window until the smoking stops.
Always connect this gas replace to a vent system and vent to the outside of the building envelope. Never vent to another room or inside the building. Make sure the specied vent pipe is used, properly sized and of adequate height to provide sufcient draft. Inspect the venting system annually for blockage and signs of deterioration.
WARNING: Failure to position the parts in accordance with the diagrams in this booklet, or failure to use only parts specically approved with this appliance, may result in property damage or personal injury.
WARNING: Do not operate with the glass front removed, cracked or broken. Replacement of the glass should be done by a licensed or qualied service person.
• Never use solid fuels such as wood, paper, cardboard, coal, or any ammable liquids, etc., in this appliance.
• Do not use this heater if any part has been under water. Immediately call a qualied service technician to inspect the heater and to replace any part of the control or gas control systems that have been under water.
• Do not abuse the glass by striking it or slamming the door shut.
FOR YOUR SAFETY
• Installation and service must be performed by a qualied installer, service agency or gas supplier.
• This installation must conform to local codes or, in the absence of local codes, to the current CAN/CSA-B149.1 Natural Gas and Propane Installation Code (Canada) or National Fuel Gas Code ANSI Z223.1.2 (USA)
• To prevent injury, do not allow anyone who is unfamiliar with the replace to operate it.
2
WARNING
HOT GLASS WILL
CAUSE BURNS
DO NOT TOUCH GLASS
UNTIL COOLED.
NEVER ALLOW
CHILDREN TO TOUCH
GLASS.
Page 3
table of contentS
Safety Precautions..........................................................................................2
Table of Contents............................................................................................3
Codes And Approvals......................................................................................4
Specications.................................................................................................5
Dimensions........................................................................................5
Rating Label Location..........................................................................5
Rating Label.......................................................................................6
Planning Your Installation................................................................................7
Introduction.......................................................................................7
Non-Combustible Material Zone............................................................7
Typical Framing - Internal Chase..........................................................8
Typical Framing - External Chase..........................................................9
Typical Framing - Corner:...................................................................10
Typical Framing - Sidewall and Mantel.................................................11
Typical Framing - Raised Hearth.........................................................12
Installation of Facing Trim..................................................................13
Installation of Fireplace Facing...........................................................14
Installation of Receiver.......................................................................16
Allowable Vent Congurations............................................................17
Vent Termination Restrictions.............................................................18
Approved Vent Parts..........................................................................19
Installation of Flue Restrictor..............................................................20
Planning Your Installation..................................................................21
Assembly of the Unit.........................................................................21
Securing unit into Position.................................................................21
Installation Set-Up........................................................................................22
Installation Of Non-combustible Wall ..................................................22
Installation Of Venting And Terminations.............................................23
Horizontal Installation........................................................................23
Vertical Termination Installation..........................................................26
Door Removal and Installation...........................................................28
Gas Hook-Up.....................................................................................29
Electrical Hook-Up.............................................................................30
Firebox Liner Installation...................................................................30
Log Burner / Ember Bed Installation...................................................32
Log Set Installation...........................................................................34
Glass Burner Installation...................................................................39
Porcelain Panel Kit Installation............................................................41
Optional Front Installation.................................................................44
Wiring Harness.............................................................................................45
Diagnostic Flash codes..................................................................................46
Troubleshooting............................................................................................47
Parts Diagram...............................................................................................49
Parts Diagram - Options................................................................................50
Parts List......................................................................................................51
Warranty......................................................................................................53
Installation Data Sheet..................................................................................54
3
Page 4
codeS and aPProvalS
DIRECT VENT ONLY: This type is identied by the prex DV. This appliance draws all of its air for combustion from outside the dwelling, through a specially designed vent pipe system.
In the USA: The appliance may be installed at higher altitudes. Please refer to your American Gas
Association guidelines which state: the sea level rated input of Gas Designed Appliances installed at elevations above 2000 (610 m) feet is to be reduced 4% for each 1000 feet (305 m) above sea level. Refer also to National Fuel Gas Code, ANSI Z223.1/ NFPA 54, local authorities, or codes which have jurisdiction in your area regarding the de-rate guidelines.
In Canada: When the appliance is installed at elevations above 4500 feet (1372 m), the certied high
altitude rating shall be reduced at the rate of 4% for each additional 1000 feet (305 m). Refer also to CSA-B149.1 Natural Gas and Propane Installation Code, local authorities, or codes which have jurisdiction in your area regarding the de-rate guidelines.
• This appliance has been tested by LabTest Certication Inc. and found to comply with the established VENTED GAS FIREPLACE HEATER standards in CANADA and the USA as follows:
VENTED GAS FIREPLACE HEATER (DV62)
TESTED TO: ANSI Z21.88-2009/CSA 2.33-2009 VENTED GAS FIREPLACE HEATERS
CAN/CGA 2.17-M91 GAS FIRED APPLIANCES FOR HIGH ALTITUDES
CSA P.4.1-R2009 TESTING METHOD FOR MEASURING ANNUAL FIREPLACE EFFICIENCY
This Westgate DV62 Fireplace:
• Has been certied for use only with natural gas.
• Is not for use with solid fuels.
• Is approved for bedroom or bed sitting room. (IN CANADA: must be installed with a listed wall thermostat. IN USA: see current ANSI Z223.1 for installation instructions.)
• Must be installed in accordance with local codes. If none exist, use current installation code CAN/CSA-B149.1 Natural Gas and Propane Installation Code in Canada or ANSI Z223.1/NFPA 54 in the USA.
• Must be properly connected to an approved venting system and not connected to a chimney ue serving a separate solid-fuel burning appliance.
• The ow of combustion and ventilation air not be obstructed.
IMPORTANT NOTICE (Regarding rst re up): When the unit is turned
on for the rst time, it should be turned onto high without the fan on for the rst 4 hours. This will cure the paint, logs, gasket material and other products used in the manufacturing process. It is advisable to open a window or door, as the unit will start to smoke and can irritate some people. After the unit has gone through the rst burn, turn the unit off including the pilot, let the unit get cold then remove the glass door and clean it with a good gas replace glass cleaner, available at your local WESTGATE dealer.
4
Page 5
Dimensions:
SPecificationS
Rating LabeL Location:
The Rating and Lighting instruction label is located below the door frame, underneath the rebox attached to a chain. To access the label, slide the plate forward out from under the rebox. Always return it when nished.
Figure 1. Dimensions of the Firebox.
Figure 2. Rating/Lighting Label Location.
5
Page 6
Rating LabeL:
SAMPLE
SPecificationS
6
Figure 3. Rating Label.
Page 7
Planning your inStallation
intRoDuction:
This section of the technical manual is for the use of qualied technicians only. Fireplace placement, hearths, facings, mantles, and venting terminations will be covered, as well as the gas and electric systems. There are several installation safety guidelines that must be adhered to. Please carefully read the safety precautions at the front of this manual.
Warning: Clearances must be sufcient to allow access for maintenance and service.
If installing a Power Vent Kit (50-1970) refer to the instructions included with the kits to aid in your planning.
non-combustibLe mateRiaL Zone:
This installation guide will show you many options for installing your new DV62. Some options include external chases, internal chases, rock facing and corner installations. No matter what direction your installation takes, this illustration shows an area where combustible building products may NOT go. This illustration applies to any and all installations for the DV62 and should be used as the rst reference before any others. Failure to comply with this requirement can lead to elevated operating temperatures, degradation of materials or even result in re. If you are un-clear about any details contained here, consult with your retailer prior to installation.
Figure 4. Non-Combustible Material Zone.
7
Page 8
Planning your inStallation
typicaL FRaming - inteRnaL chase:
Figure 5. Typical Framing for Internal Chase - General.
Figure 6. Typical Framing for Internal Chase - Detailed.
8
Page 9
Planning your inStallation
typicaL FRaming - exteRnaL chase:
Figure 7. Typical Framing for External Chase - General.
Figure 8. Typical Framing for External Chase - Detailed.
9
Page 10
Planning your inStallation
typicaL FRaming - coRneR:
Figure 9. Typical Framing for Corner - General.
Figure 10. Typical Framing for Corner - Detailed.
10
Page 11
Planning your inStallation
typicaL FRaming - siDewaLL anD manteL:
The mantel’s maximum overhang is 12” (300mm) at the minimum height of 62” (1575mm) measured from the base of the replace.
The mantel can extend 1” (25.4mm) further for every 1” (25.4mm) of height it is installed over the minimum height.
Non-combustible mantels and mantel legs are not limited to these dimensions.
Mantel temperatures are monitored during testing and can reach 117°F (47°C) above room temperatures. Make sure the nish on your mantel is suitable for temperatures of this range.
Figure 11. Typical Framing for Sidewalls & Mantel - General.
Figure 12. Typical Framing for Sidewalls & Mantel - Detailed.
11
Page 12
Planning your inStallation
typicaL FRaming - RaiseD heaRth:
Warning: Failure to follow these guidelines may result in elevated operating temperatures,
an inability to remove or install the door, or install the optional front that are available for this unit.
A non-combustible Hearth Insulation Board is not required for the DV62.
If a hearth is to be installed in front of the unit , it must not be thicker than ¾” . If the hearth is raised or the hearth materials is thicker than ¾”, the unit must be spaced up by the same distance that the hearth materials extended beyond the ¾” limit.
Example:
Hearth material is 2” limestone. The hearth thickness limit is ¾”, therefore the unit must be raised up 1¼” off the oor so that the hearth does not extend vertically beyond the bottom ange of the replace.
The DV62 can be installed directly on top of combustible ooring. If the unit needs to raise up off the oor, a wooden structure can be built to accommodate the raised. Placing a couple of thicknesses of plywood under the unit would be an acceptable method.
Figure 13. Typical Framing for a Raised Hearth - General.
12
Figure 14. Typical Framing for a Raised Hearth - Detailed.
Page 13
Planning your inStallation
instaLLation oF Facing tRim:
Figure 15. Facing Trim Installation - General.
13
Page 14
Planning your inStallation
instaLLation oF FiRepLace Facing:
Figure 16. Typical Facing for the Fireplace - General.
The DV62 may be installed with an optional front. The front lift on and off of the replace, providing access to the replace for regular maintenance and service, see Optional Front Installation.
You have 3 possible scenarios when installing facing to your replace. Care must be taken to ensure proper clearances are maintained. Clearances are required between optional front and any stone work applied to your replace installation. Failure to maintain this clearance will lead to elevated operating temperatures and possible discoloration of materials and or front.
Three (3) possible installations include:
1) For replace facing without an optional front installed.
2) For replace facing greater than 1” thick with an optional front installed.
3) For any replace less than 1” thick (total facing and non-combustible board combined) with an optional front installed.
Figures 17 to 19 highlight the relationships between the replace, optional front, and facing installed.
NOTE: Optional Door Front cannot be installed with the Porcelain Firebox Liner option.
Figure 17. Option 1 - Fireplace Facing Without Optional Front Installed
When installing the DV62 without the optional door sets, install the inner trim kit that is supplied with the unit. The inner trim is fastened to the non-combustible wall board that comes with the unit and the rock/tile facing covers over the trim ange as with any typical drywall ange. The rock or tile facing can be any thickness, but once this unit is installed, you can no longer install the optional door sets
14
Page 15
Planning your inStallation
instaLLation oF FiRepLace Facing continueD:
Figure 18. Option 2 - Fireplace Facing More Than 1” (25.4mm) Thick With
Optional Fronts Installed.
When installing the DV62 with the optional door and you plan to install rock or tile facing that is thicker than 1” (combined with the non-combustible board supplied), you must install the wall trim kit that is supplied with the unit. The optional wall trim is fastened to the non-combustible wall board that comes with the unit and the rock or tile facing covers over the trim ange as with any typical drywall ange. The minimum air gap shown on the drawing must be maintained between the optional door set and the wall as well as between the facing and the door set as shown.
Figure 19. Option 3 - Fireplace Facing Less than 1” (25.4mm) Thick
When installing the DV62 with the optional door and you plan to install rock or tile facing that is thinner than 1” (combined with the non-combustible board supplied), you do not need to install any optional trim. The minimum air gap between the optional door set and the wall must be maintained as shown. Failure to maintain this air gap will result in elevated operating conditions.
With Optional Fronts Installed.
15
Page 16
Planning your inStallation
instaLLation oF ReceiveR:
NOTE: Finish receiver install after all other construction to avoid damage
Figure 20. Receiver Installation.
The Receiver is the heart of the remote control system. You need to access this receiver after installation to change the batteries (for operation during a power failure), to program a new remote / receiver combination and to operate a manual override should you lose your remote control or the batteries in the remote control lose their power.
The Receiver is connected to the replace with a wire harness that has a maximum length of 8 ft (2.4m). The connection point on the replace is on the right side of the unit, where the gas valve and electronic ignition module is located. Because of the 8 ft (2.4m) limitation in the wiring harness, the receiver needs to be mounted to the right side of the replace. An electrical box is provided for the receiver. Mount this electrical box as you would any electrical outlet or switch box. Thread the cable and connector through the back of the electrical box and connect it to the rear of the receiver. Secure the receiver into the electrical box. Once the facing of the replace installation is complete, install the receiver cover, supplied with the unit as shown. The receiver cover also functions as a switch plate and allows for access to the program button, critical for remote control operation.
Review the section in this manual regarding the remote control operations for more information on the functions of the receiver.
aLLowabLe vent conFiguRations:
The vent chart, in Figure 21, illustrates the vent congurations that have been tested and approved for use with this appliance. 45˚ elbows are acceptable for this installation and may be used instead of 90˚ elbows. You may use two (2) 45˚ elbows for every 90˚ elbow shown in this chart.
This appliance can be used with 5” x 8” venting in vertical termination installation with the used of Simpson 5” x 8” reducer adapter.
The restrictor settings shown in Figure 21, are recommended. Installation factors such as altitude, prevailing weather conditions such as temperature or wind, or the number of elbows used may affect your nal restrictor settings. Insufcient restriction may cause pilot outages or reduced efciencies. Too much restriction may lead to elevated operating temperatures, poor ame appearances, sooting or carbon deposits building up on burner effects or window glass.
16
Page 17
Planning your inStallation
Figure 21. Allowable Vent Congurations Chart.
17
Page 18
Planning your inStallation
vent teRmination RestRictions:
QUALIFIED INSTALLERS ONLY
N
O
D
E
C
B
L
F
Fixed
Closed
Openable
B
B
Openable
Fixed
Closed
H
G
G
M
B
A
J
I
Termination Cap
Figure 22. Vent Termination Restrictions, refer to Table 1.
Table 1: Vent termination clearances, refer to Figure 22.
Letter Canadian Installation
A 12 in (30 cm) Clearance above grade, verandah, porch, deck, or
B 12 in (30 cm) 9 in (23 cm) Clearance from window or door that may be opened.
C 12 in (30 cm)* Clearance from permanently closed window (to prevent
D 30 in (77 cm) Vertical clearance to ventilated soft located above the
E 30 in (77 cm) Clearance to unventilated soft.
F 12 in (30 cm)* Clearance to outside corner.
G 12 in (30 cm) Clearance to inside corner.
H 3 ft (91 cm) within a height
of 15 ft (4.5 m) above the
meter/regulator assembly
I 3 ft (91 cm) 3 ft (91 cm)* Radial clearance around service regulator vent outlet.
J 12 in (30 cm) 9 in (23 cm) Clearance to non-mechanical air supply inlet to building,
K 6 ft (1.83 m) 3 ft (91 cm) above if within 10
L 7 ft (2.13 m
M 12 in (30 cm)
N 12 in (30 cm)* Clearance horizontally to any surface (such as an exte-
O 12 in (30 cm) Clearance above roof line for vertical terminations.
1
)t
Air Supply Inlet
US Installation
3 ft (91 cm) within a height
of 15 ft (4.5 m) above the
meter/regulator assembly*
ft (3 m) horizontally
7 ft (2.13 m)
+
2
*t
Gas MeterG
balcony.
condensation).
terminal, within a horizontal distance of 2 ft (60 cm) from center line of terminal.
Clearance to each side of center line extended above meter/regulator assembly.
or the combustion air inlet to any other appliance.
Clearance to mechanical air supply inlet.
Clearance above paved sidewalk or paved driveway located on public property.
Clearance under verandah, porch, deck, or balcony.
rior wall) for vertical terminations.
Restriction Zone
(Termination not allowed)
Description
K
A
1
In accordance with the current CSA B149, Natural Gas and Propane Installation Code.
2
In accordance with the current ANSI Z223.1 NFPA 54, National Fuel Gas Code.
* These numbers are only estimates. Clearance in accordance with installation codes and the requirements of the gas supplier. t
A vent shall not terminate directly above a side walk or paved driveway that is located between two single family dwellings and it serves both dwellings.
+
Permitted only if verandah, porch, deck, or balcony is fully open on a minimum of two sides beneath the oor.
NOTE: Venting terminals shall not be recessed into walls or siding.
18
Page 19
Planning your inStallation
appRoveD vent paRts:
Table 2: Vent part numbers (Must state if galvanized or black wanted, PART NUMBERS).
Part Description Simpson Duravent
6” Pipe Length
12” Pipe Length
24” Pipe Length
36” Pipe Length
48” Pipe Length
12`Adjustable Length
45° Elbow
90° Elbow
90° Elbow (swivel)
Adjustable Roof Flashing
0/12 - 6/12
Steep Roof Flashing 7/12
- 12/12
Elbow Strap
Wall Strap
Storm Collar
Ceiling Firestop
Wall Thimble
Horiz. Termination, High
Wind
Vert. Termination, High
Wind
Vinyl Siding Standoff
5” x 8” Reducer Adapter
662492666098
662492877241
662492779163
662492486399
662492429266
662492606360
662492654897
662492646984
662492863695
662492760871
662492384497
662492864975 662492794630 662492323151
662492471715
662492144596
662492641439
662492723951
662492314067
TBA
IMPORTANT: This chart covers the major components only. Refer to the manufacturers’ catalogue for further details on roof ashings and other installation items The DV62 replace has been tested and certied for use with SIMPSON DURAVENT TYPE GS PIPE FOR GAS STOVES. When planning an installation, it will be necessary to select the proper length of vent pipe for the particular requirements. WARNING: Do not mix parts from different vent manufacturers’ systems.
19
Page 20
Planning your inStallation
instaLLation oF FLue RestRictoR:
Flue Restrictor is necessary to keep the replace running at its intended efciency. They are also required to counteract the effect that taller vertical vent runs may have on the appliance. The additional venting action that tall vertical vent systems may have can result in poor pilot and/or burner operations and possibly nuisance shut downs. Generally, the vent restriction may be less than what is shown in the vent chart, but not greater.
The DV62 has a built in adjustable ue restrictor. Set the ue restrictor before you install the rebox liners. The ue restrictor pivots in the middle and is secured with a T20 screw. Refer to the Venting Chart (Figure 21) to determine the correct setting. The vent chart shows the range of vent setups that you can use when installing the DV62. The vent chart shows an appropriate restrictor setting for the vent run that you are using.
The vent chart is a starting point for the restrictor setting. Environment factors can affect the restrictor setting such as altitude, prevailing weather and wind conditions. Keep in mind that running a restrictor setting that is more restrictive than the recommended setting may result in the replace running at elevated temperatures which can result in hazardous conditions. Do not leave an installation without securing the vent restrictor.
Figure 23: Installation of Flue Restrictor - Close-Up.
20
Page 21
inStallation Set-uP
QUALIFIED INSTALLERS ONLY
pLanning youR instaLLation:
Prior to starting your venting installation, refer to the section on Allowable Vent Congurations to make sure your plans fall into the allowable limits of horizontal and vertical installations.
When planning your installation, it will be necessary to select the proper length of vent pipe for your particular requirements. For horizontal installations, refer to the section on Clearances to Combustibles to determine the minimum clearance from the rear of the appliance to the wall. It is also important to note the wall thickness. Select the amount of vertical rise desired for “vertical-to-horizontal” type installations. To determine the length of vent pipe required for vertical installations, measure the distance from the appliance ue outlet to the ceiling, the ceiling thickness, the vertical rise in an attic or second story, and allow for sufcient vent height above the roof line. For two-story applications, restops are required at each oor level. If an offset is needed in the attic, additional pipe and elbows will be required.
assembLy oF the unit:
1.Using eight (8) T-20 screws provided, install the drywall supports right and left as well as the heat shield in the middle, as shown in Figure 28.
2.Using eight (8) T20 screws provided, attach back stand-offs, as shown in Figure
24.
secuRing unit into position:
Figure 25: Securing the Unit.
Figure 24: Installation of Supports, Heat
shield & Stand-off.
Once the unit is in its nal position, conrm that you have access to power, gas supply, that your non­combustible zone requirements are met, that you meet all the minimum vent requirements, and that your planned vent terminal location will meet all of the vent termination clearances. Secure the unit to the oor, with at least four (4) wood screws, two (2) on either side of the unit’s bottom nailing ange. Secure the side stand-offs to the framing members using four (4) wood screws, one (1) for each stand-off and to the header, one (1) wood screw for each drywall support.
21
Page 22
inStallation Set-uP
instaLLation oF non-combustibLe waLL boaRD:
Install the non-combustible wall board provided with the unit. The side boards are interchangeable and are secured with drywall screws, three (3) to each side of the unit and three (3) to each side frame member. The top board is secured with four (4) drywall screws along the top frame (header), four (4) along the top nailing ange of the unit and two (2) on each vertical frame member. Also secure the top wall board to the heat shield behind it with two (2) screws and each drywall support upright with two (2) screws. See the section on hearth installation for installing the hearth protector, required with the installation of this unit. All the screws required to attach the wall board sides and top to the unit have corresponding holes already located on the units nailing anges, drywall supports and heat shield.
Figure 26: Installation of Wall Board
22
Page 23
inStallation Set-uP
instaLLation oF venting anD teRminations:
Read all instructions carefully before starting the installation. Failure to follow these instructions may create a re or other safety hazard, and will void the warranty.
INSTALLATION PRECAUTIONS:
• Do not install any damaged venting or vent components.
• Do not modify any vent or termination component.
• Do not install any vent component that is not an approved vent component for this appliance.
• Do not use any instructions other that those included in this manual or those included by the vent component manufacturer with the venting. When there are discrepancies between the two, this manual will be considered the nal authority.
Consult your local building codes before beginning the installation.
WARNING
• Always maintain required clearances (air spaces) to nearby combustibles to prevent a re hazard.
Do not ll air spaces with insulation. Unless stated otherwise, clearances on horizontal vent sections are 2” (51mm) to combustible materials. Clearances to vertical vent sections are 1” (25mm) to combustible clearances.
• The replace and vent system must be vented directly to the outside of the building. Each direct
vent replace must use its own separate vent system. Common vent systems are prohibited.
• The ow of combustion and ventilation air not be obstructed.
hoRiZontaL instaLLation:
Step 1. Set the replace in its desired location. Check to determine if wall studs or roof rafters are in the way when
the venting system is attached. If this is the case, you may want to adjust the location of the appliance.
Step 2. Direct Vent pipe and ttings are designed with special twist-lock connections. Assemble the desired
combination of pipe and elbows to the appliance. See the sections on Typical Framing - inTernal chase, exTernal chase or corner insTallaTion for some of the possible vent pathway options. All installations must fall within the Allowable Vent Congurations shown in Figure 21.
Notes:
(1) Twist-lock procedure: Four (4) indentations, located on the female
ends of pipes and ttings, are designed to slide straight onto the male ends of adjacent pipes and ttings, by orienting the four pipe indentations so they match and slide into the four (4) entry slots on the male ends. Push the pipe sections completely together, then twist-lock one section clockwise approximately one-quarter turn, until the two (2) sections are fully locked.
(2) Horizontal runs of vent must be supported every 3 feet (915mm).
Wall Straps are available for this purpose.
(3) Sealant is only necessary on the outer tube of the GS Pipe. Run a
⅛ inch (3mm) wide bead of sealant around the male end of the outer sleeve, as shown in Figure 27, and twist-lock the pipes or ttings together.
Figure 27: Twist-Lock Connection.
Step 3. With the adaptor and pipe attached to the replace, slide the replace into its correct location, and mark
the wall for a rectangular hole of the appropriate size. Use 12.5”x14.75” (318x375mm) hole for 6” x 8-5/8” pipe, Figure 28. The center of the hole should line up with the center line of the horizontal pipe, as shown in Figure 30. Cut and frame the hole in the exterior wall where the vent will be terminated. If the wall being penetrated is constructed of non-combustible material, i.e. masonry block or concrete, a hole with zero clearance to the pipe is acceptable.
23
Page 24
inStallation Set-uP
Notes:
(1) Any horizontal run of vent
must have a ¼ inch (6mm) rise for every 1 foot (305mm) of run towards the termination. Never allow the vent to run downward. This could cause high temperatures and may present the possibility of a re.
(2) The location of the horizontal
vent termination on an exterior wall must meet all local and national building codes, and must not be easily blocked or obstructed. Termination clearances must comply with the VenT TerminaTion resTricTions section.
Step 4. Attach the termination to the termination stand-off
with four screws (refer to Figure 31a). Before attaching the Vent Termination to the termination stand-off, run a bead of non-hardening sealant around its outside edges, so as to make a seal between it and the termination stand-off.
Figure 28:Thimble Framing
Figure 29:Thimble
Step 5. Place the termination assembly against the wall board with
the vent termination center with the cut out hole. Secure the termination assembly to the exterior wall with eight (8) wood screws provided (refer to Figure 31b). The arrow on the vent cap should be pointing up. Ensure that proper clearances to combustible materials are maintained. Attach intake heat shield to the termination stand-off with the pre-drill holes (refer to Figure 32).
Notes:
The eight (8) wood screws provided should be replaced with
appropriate fasteners for stucco, brick, concrete, or other types of sidings.
Figure 30: Horizontal Venting and Cut Away.
Figure 31a: Attach Termination Stand-off
24
Figure 31b: Fastening Horizontal
Termination Cap in Place.
Page 25
inStallation Set-uP
Step 6. Before connecting the horizontal run of vent pipe to the vent termination, slide the Wall Firestop over
the vent pipe on the interior side of the wall.
Step 7. Slide the appliance and vent assembly towards the wall, carefully inserting the vent pipe into the vent
cap assembly. It is important that the vent pipe extend into the vent cap sufcient distance so as to result in a minimum pipe overlap of 1¼ inches (32mm).
Step 8. Slide the Wall Firestop up to the wall surface and attach with screws provided (see Figure 33).
Figure 32: Install Intake Heat Shield
Figure 33: Installation of Wall Firestop.
Figure 34: Typical Minimum Vent Congurations
- Horizontally Terminated.
25
Page 26
inStallation Set-uP
veRticaL teRmination instaLLation:
Step 1. M a i n t a i n
c l e a r a n c e s between venting and combustible building materials as stated earlier in this section. Do not pack air spaces with insulation. Check with the Allowable Vent C o n f i g u r a t i o n s page when planning your installation to ensure the vertical and horizontal elements of your installation are within these limits.
Figure 35: Installation of Ceiling Firestop.
Step 2. Set the replace in its desired location. Drop a plum bob down
from the ceiling to the position of the appliance ue exit, and mark the location where the vent will penetrate the ceiling. Drill a small hole at this point. Next, drop a plumb bob from the roof to the hole previously drilled in the ceiling, and mark the spot where the vent will penetrate the roof. Determine if ceiling joists, roof rafters, or other framing will obstruct the venting system. You may wish to relocate the appliance, or to offset, to avoid cutting load bearing members.
Step 3. To install the Ceiling Firestop in a at ceiling, cut a square hole in the ceiling 11”x11” (280x280mm)
square for 8” x 5” pipe, centered on the hole drilled in Step 2. Frame the hole as shown in Figure 35.
Step 4. Assemble the desired lengths
of galvanized Pipe and Elbows necessary to reach from the Appliance Adaptor up through the Ceiling Firestop. Ensure that all Pipe and Elbow connections are in their fully twist-locked position.
Step 5. Cut a hole in the roof centered on
the small drill hole placed in the roof in Step 2. The hole should be of sufcient size to meet the minimum requirements for clearance to combustibles, as specied earlier. Continue to assemble lengths of Pipe and Elbows necessary to reach from the Ceiling Firestop up through the roof line.
Figure 36: Vertical Installation using
Wall Straps.
26
Figure 37: Installation of Flashing & Vertical Termination.
Page 27
inStallation Set-uP
Notes:
(1) If an offset is necessary in the attic to avoid obstructions, it
is important to support the vent pipe every 3 feet, to avoid excessive stress on the Elbows, and possible separation. Wall Straps are available for this purpose (see Figure 36).
(2) Whenever possible, use 45° Elbows, instead of 90° Elbows.
The 45° Elbow offers less restriction to the ow of ue gases and intake air.
Step 6. Slip the ashing over the Pipe Section(s) protruding
through the roof. Use a non-hardening sealant between the Flashing and the roof to prevent water leakage. Secure the base of the Flashing to the roof with roong nails. Ensure the roong material overlaps the top edge of the Flashing as shown in Figure 37. Verify that you have at least the minimum clearance to combustibles at the rooine.
Step 7. Continue to add Pipe Sections until the height of
the Vent Cap meets the minimum building code requirements described by your local codes. In the absence of local codes, make sure the terminal is 2 feet (610mm) above anything within 10 feet (3046mm) of the vent (refer to Figure 40 & Table 3 for clearances for different pitches). Note that for steep roof pitches, the vent height must be increased. In high wind conditions, nearby trees, adjoining rooines, steep pitched roofs, and other similar factors can result in poor draft, or down-drafting. In these cases, increasing the vent height may solve this problem.
Figure 38: Installation of Ceiling Fire Stops.
Step 8. Slip the Storm Collar over the Pipe, and push it down to the top
of the Flashing, as shown in Figure 38. Use the non-hardening sealant above and below the joint between the Storm Collar and the Pipe.
Step 9. Twist lock the Vent Cap.
Notes:
(1) For multi-story vertical installations, a Ceiling Firestop is required at
any subsequent oors (as shown in Figure 38). The opening should be cut and framed in the same manner as the opening in Step 3 (see Figure 35).
(2) Any occupied areas above the rst oor, including closets and storage
spaces, which the vertical vent passes through, must be enclosed. The enclosure may be framed and sheet rocked with standard construction materials, however minimum allowable clearances between the outside of the vent pipe must be maintained. Do not ll any of the required air spaces with insulation.
Figure 39: Typical Vent Congurations
- Vertically Terminated.
27
Page 28
inStallation Set-uP
H
Dimension ‘H’ obtained from table to the left.
Table 3: Minimum ‘H’ for Figure 40.
Roof Pitch Minimum Height (H)
Feet Meters
Flat to 7/12 1 0.3
Over 7/12 to 8/12 1.5 0.46
Over 8/12 to 9/12 2 0.61
Over 9/12 to 10/12 2.5 0.76
Over 10/12 to 11/12 3.25 0.99
Over 11/12 to 12/12 4 1.22
Over 12/12 to 14/12 5 1.52
Over 14/12 to 16/12 6 1.83
Over 16/12 to 18/12 7 2.13
Over 18/12 to 20/12 7.5 2.29
Over 20/12 to 21/12 8 2.44
DooR RemovaL anD instaLLation:
Figure 40: Height of Vertical Termination;
Reference Table 3.
1) The replace door is hung on two (2) hooks on the top of the rebox. The two (2) door latches at the bottom of the rebox hook over the tabs on the bottom of the door frame.
2) Lower the door latch tool underneath the door frame. Catch the lower door latch with the door latch tool (see Figure 41) and pull it out slightly, then down. Once the lower door latch clears the tab on the bottom of the door frame, release it inwards and then remove the door latch tool. Refer to Figures 43 & 44.
3) Pull the Door Frame at the bottom forward about 2” (5cm), then lift the Door Frame upwards to clear the
Figure 41: Door Latch /Air Adjustment Tool.
28
Figure 43: Door Latch Tool in Place. Figure 42: Door Latch Locations.
Page 29
inStallation Set-uP
4) Lift the Door Frame away, being careful that the glass panel is secure within the Door Frame.
gas hook-up:
The DV62 is equipped from factory with a ½” SAE 45° male gas tting. This tting will t commonly used exible gas supply lines.
Figure 44: Door Latch Locations.
If the local code requires to use rigid pipe for gas supply, nish the gas line inside the control box, (through the access hole illustrated) fasten the pipe to the control box and complete the connection using a short length ex line.
NOTES:
This appliance and its main gas valve must be disconnected from the gas supply piping system during any pressure testing of that system at test pressures in excess of ½ psi (35 kPa).
Isolate this appliance from the gas supply piping system by closing its equipment shutoff valve during any pressure testing of the gas supply piping system at test pressures equal to or less than ½ psi (3.5 kPa).
Figure 45: Location of Gas Hook-Up.
29
Page 30
inStallation Set-uP
eLectRicaL hook-up:
An electrical junction box is provided and fastened to the back of the control box. Power needs to be brought to the electrical junction box. The power for the various control components are all provided from the fan control module. Remove the control box cover, install the provided electric outlet and cover and plug the fan control module into it. See the Rating Label for the listed electrical requirements.
When installed, the DV62, must be electrically grounded in accordance with local codes or, in the absence of local codes, with the National Electrical Code, ANSI/NFPA 70, or the Canadian Electrical Code, CSA
C22.1.
WARNING
Electrical Grounding Instructions
This appliance is equipped with a three-prong (grounding) plug for your protection against shock hazard and should be plugged directly into a properly grounded three-prong receptacle. Do not cut or remove the grounding prong from this plug.
FiRebox LineR instaLLation:
Figure 46: Location of Electrical Hook-Up.
IMPORTANT: Complete the installation of ue restrictor before proceed the rebox liner installation. The paint on the panels may fade for the rst 8-10 hours of burn time, but will come back to its color after the paint has cured. The paint is very delicate and handling them with care is necessary not to mark or smudge the paint.
1) Install the Rear Firebox Liner Panel. This panel rest on top of the rear brick panel support. Hold it with one hand or have someone else hold it while place in the Left Panel.
2) Install the Left Firebox Liner Panel; it sits on the bottom front edge of the rebox (see Figure 48), a support bracket at the lower rear of the rebox, and is held in by a retainer at the top of the rebox. Adjust the panel retainers as required.
3) Install the Top Firebox Liner Panel by placing it on top of the Rear Panel and behind the Left Panel (see Figure 50 and 51). Hold it with one hand or have someone else hold it for you while you place the last panel. WARNING: If this panel falls from this location it will possibly break or the paint work will become chipped.
4) Install the Right Firebox Liner Panel in the same manner used for the Left Panel (see Figure 52). The vertical edges of the left and right panels should line up with the front edges of the rebox sides.
Figure 47: Rear Firebox Liner Panel In Place
30
Figure 48: Left Firebox Liner Panel on Front Edge
Page 31
inStallation Set-uP
Figure 49: Left Firebox Liner Panel in Place Figure 50: Top Firebox Liner Panel Installed.
Figure 51: Top Firebox Liner Panel in Place.
Figure 52: Rigjt Firebox Liner Panel in Place.
31
Page 32
inStallation Set-uP
Log buRneR / embeR beD instaLLation:
1. In the bottom rear of the rebox there are two (2) gas orices in a housing that facilitate the air shutter mechanisms and the Burner Mounting Brackets are above them (See Figure 53). There are two (2) mixing tubes underneath the back of the burner (see Figure
54). Lift the burner into the rebox with the back of the burner tilted downward. Keep the burner high enough at the front to clear the pilot assembly. Line up the mixing tubes with the holes in the burner mounting brackets and slowly lower the front of the burner over the pilot assembly (see Figure 55).
2. Pull the burner forward up to the angular brackets near the front of the rebox (see Figure 56).
IMPORTANT: If the burner is not far enough back
to lower the burner behind these brackets, then the mixing tubes are not engaged in the air shutter. Failing to ensure the mixing tubes are located in the mixing tube support brackets may cause serious performance and or safety issues.
Figure 53: Burner Mounting Brackets.
3. Install the burner accent pieces as shown in Figure
57. There are a left, a right and a front ceramic trim. On each side of the burner and on the inside of each burner side accent pieces there is a slot, which should be aligned in order to position the log grate correctly (see Figure 58).
4. The rebox grate has two (2) tabs that run below the feet of the grate (see Figure 59), place the grate over the burner top and carefully inserting the grate tabs into the slots on the burner (see Figure 60). Once the grate is installed correctly, the burner, grate, and side burner accents will be all locked together.
Figure 54: Burner Mixing Tubes
Figure 55: Log Burner Over Pilot Assembly.
32
Figure 56: Log Burner in Place.
Page 33
inStallation Set-uP
Figure 57: Burner Accents Pieces in Place.
Figure 59: Tab on Firebox Grate.
Figure 58: Slot for Firebox Grate.
Figure 60: Firebox Grate in Place.
33
Page 34
inStallation Set-uP
Log set instaLLation:
IMPORTANT: The paint on the logs may fade for the rst 8-10 hours of burn time, but will come back to
its color after the paint has cured. The paint is very delicate and handling them with care is necessary not to mark or smudge the paint.
1. Install Log 8. Insert the pin hole on the front end of log 8 into the pin tab locates at the center of the grate The rear end sits on the grate with the groove on the bottom of the log tting onto the top of the grate rear left leg.
Figure 61a: Log 8 Rear End in Place
2. Install Log 7. Place the rear end of the log on the grate using the groove on the bottom of the log to index itself to the grate. The front end of log 7 rest against a guide on log 8.
Figure 62a: Log 7 Rear End in Place
Figure 61b: Log 8 in Place
Figure 62b: Log 7 Front End
34
Figure 62c: Log 7 in Place
Page 35
inStallation Set-uP
3. Install Log 9. Insert the hole on the left side into the pin tab at the back of the grate. The right side self locates on log 7. Leave a 1/8” gap between the rear brick panel and the log.
Figure 63b: Log 9 in PlaceFigure 63a: Log 9 Right Side in Place
4. Install Log 5. Place the log on top of the grate with the log locators on the left side of the grate inserted into the grooves on log 5.
Figure 64a: Log Locators and grooves
5. Install Log 6. Place the log on top of the grate with the log locators on the right side of the grate inserted into the grooves on log 6.
Figure 65a: Position Log 6
Figure 64b: Log 5 in Place
Figure 65: Log 6 in Place
35
Page 36
inStallation Set-uP
6. Install Log 10. Place the end with number 10 against the notch on log 8 and rest the other end on the groove of log 7. The edge along the bottom of this log will index into the groove of Log 7.
Figure 66a: Log 10 Rear End in Place. Figure 66b: Log 10 Front End in Place.
Figure 66b: Log 10 in Place.
7. Install Log 2. Position log 2 to sit on the left grate nger and lean the log back to rest on the at depression on log 9.
Figure 67b: Log 2 in Place.Figure 67a: Position Log 2 on Grate Finger.
36
Page 37
inStallation Set-uP
8. Install Log 1. Position log 1 to sit on the right grate nger and lean the log back to rest on the at depression on log 9.
Figure 68a: Rest Log 1 in Place.
9. Install Log 4. Log 4 sits in between Log 2 and the grate nger and its body rests across the body of Log 10. There is a groove cut out on log 10 for log 4 to rest on.
Figure 69a: Place Log on Grate Finger.
10. Install Log 3. Log 3 sits on the right grate nger. There is a notch across Log 6, which this log will locate into. The edge along the back of this log will index into the notch of Log 6.
Figure 68b: Log 1 in Place.
Figure 69b: Log 9 in Place.
Figure 70a: Index Log 3 in Place
Figure 70b: Log 3 in Place
37
Page 38
inStallation Set-uP
NOTE: Variances in gas quality or log placement may cause some discoloration of the log set, or sooting
to occur.
38
Page 39
inStallation Set-uP
gLass buRneR instaLLation:
1. In the bottom rear of the rebox there are two (2)
gas orices in a housing that facilitate the air shutter mechanisms and the Burner Mounting Brackets are above them (See Figure 71). There are two (2) mixing tubes underneath the back of the burner (see Figure 72). Lift the burner into the rebox with the back of the burner tilted downward. Keep the burner high enough at the front to clear the pilot assembly. Line up the mixing tubes with the holes in the burner mounting brackets and slowly lower the front of the burner over the pilot assembly (see Figure 73).
2. Pull the burner forward up to the angular brackets near the
front of the rebox (see Figure 75). The burner rests on the oor of the rebox and is properly aligned against the two (2) front burner rests.
IMPORTANT: If the burner is not far enough back to lower
the burner behind these brackets, then the mixing tubes are not engaged in the air shutter. Failing to ensure the mixing tubes are located in the mixing tube support brackets may cause serious performance and or safety issues.
Figure 71: Burner Mounting Brackets
3. Place the glass tray over top of the burner top as shown in
Figure 74. It simply rests over the top section of the burner.
4. In front of the pilot assembly, on the front edge of the
burner is one burner port which helps in the lighting of the main burner (see Figure 75). The glass tray has one hole in the same position that allows the gas to ow to this location. Ensure the glass tray hole is properly positioned over the port in the burner.
5. The DV62 glass burner option is supplied with two (2)
quantities of glass, black and white. There is enough of either to ll the burner, so you can decide whether to install all white, all black, or some type of mixture. Place crushd glass evenly in the burner tray and ll glass to the top untuil they are level with the 4 sides of the tray (example in Figure 76). Try to keep glass from falling in around the pilot assembly.
Figure 72: Mixing Tubes in Glass Burner.
Figure 73: Placing Glass Burner.
Figure 75: Glass Burner in Place Figure 74: Glass Tray over Burner
39
Page 40
inStallation Set-uP
Pilot Assembly
Keep this
area clear.
6. Gently place the burner trim piece around the burner (see Figure 77). It sits on various support brackets and ts around the burner tray and up against the rebox liner. Figure 78 shows the burner trim in the correct position. Ensure a minimum ⅜” (8mm) gap is maintained around the burner glass tray (see Figure 79).
7. If the optional rock accent kit was purchased for the DV62, you can place the rocks in a random pattern around the glass tray. A few can straddle the 1/2” (13mm) gap around the glass tray. Try to keep them looking randomly placed. Keep from placing them in large piles as they need to be evenly distributed. Examples are shown in Figure 80.
It is important that rock accents are not placed
in front or over the pilot assembly. This may prevent the burner from lighting in a timely fashion or overheat the pilot assembly. Keep an area of about 3” (75mm) in front of the pilot light free from obstruction and rock accents (see Figure 81).
Figure 76: Glass Tray with Mixed Glass.
Figure 78: Burner Trim in Correct Position.
Figure 77: Burner Trim Being Placed.
Figure 79: Proper Gap Between The Glass Tray and
The Burner Trim
Figure 80: Rock Accents
Figure 81: Keep Area in Front of Pilot
Assembly Clear.
40
Page 41
inStallation Set-uP
poRceLain kit instaLLation:
1. Install the Rear Firebox Liner. This panel rests on the Rear Brick Panel Support.
2. Install the Left Firebox Liner Panel; it sits on the bottom front edge of the rebox (see Figure 82), a support bracket at the lower rear of the rebox, and is held in by a retainer at the top of the rebox. Adjust the panel retainers as required.
5. Install the Top Panel by placing it on top of the Rear Panel and behind the Left Panel (see Figure 83). Hold it with one hand or have someone else hold it for you while you place the last panel. WARNING: If this panel falls from this location it will possibly break or the paint work will become chipped.
6. Place the Right Firebox Liner Panel in the same manner used for the Left Panel. The vertical edges of the left and right panels should line up with the front edges of the rebox sides. The side panels rest up against the back panel and hold the top panel in position.
7. Installation of Porcelain Kit for Glass Burner continue on with next step. Installation of Porcelain Kit for Log Burner go to step 14.
8. Install the Burner Assembly; refer to Step 1 & 2 of glass Burner
insTallaTion.
Figure 82: Rear & Left Porcelain
Panels in Place.
9. Attach the Glass Burner Skirt to the Right Burner Cover Support using two (2) T-20 Torx screws supplied (see Figure
84) and do the same to the Left Burner Cover Support as you’ve done on the right side.
Figure 84: Porcelain Light Covers Close-up.
Figure 83: Top Porcelain Panel in Place.
41
Page 42
inStallation Set-uP
10. Install the Glass Burner Cover Support Kit to the Right Burner Support using three (3) T-20 Torx screws supplied. Install the Support Kit to the Left Burner Cover Support as you’ve done on the right side.
11. Place one of the Permanent Magnets provided on the front edge of the Burner Cover Supports as shown in Figure 86.
12. The Burner Cover has two (2) slots, one the either side of the rear ange (refer to Figure 87). These
slots t over the two (2) studs in the burner cover support (refer to Figure 86) to keep it in place.
The arrows in Figure 88 point at the studs that hold the Burner Cover in position. Place the Burner
Cover over the pins and then once aligned with the holes, push the Burner Cover back towards the rear of the rebox. The front of the Burner Cover is held in place by the permanent magnets installed in step 11.
13. Install the Glass Tray and the Glass to complete the installation
Figure 85: Installing Burner Cover Support Kit
Figure 87: Slots in Back of Burner Cover.
Figure 86: Permanent Magnet on
Right Burner Cover Support.
Figure 88 Installing Burner Cover.
42
Page 43
inStallation Set-uP
14. Install the Burner Assembly; refer to Step 1 & 2 of log Burner /
emBer Bed insTallaTion.
15. Install the Left and Right Burner Cover Support as shown in Figure
89. Each burner cover is installed using three (3) T-20 Torx screws supplied.
16. Install the Log burner accent to
the burner cover supports with four (4) T-20 Torx as shown in Figure 90.
Figure 89: Installing Burner Cover Supports
Figure 90: Installing The Log Burner Accent
17. Install the Grate and the Logs
Set to complete the installation.
43
Page 44
inStallation Set-uP
optionaL FRont instaLLation:
Optional front is available for your replace. The replace front hang onto the front of your replace using four (4) hooks, one on each corner (refer to Figure 91). These hooks secure the front to the replace, providing for easy removal for service access to the replace and also to position the front the proper distance away from the glass door and the replace facing.
Figure 91: Optional Front Parts.
Install the front by lifting it parallel to the replace with the mounting bracket hooks pointing towards the replace. Slide the hooks all the way into the slots between the Glass Door Frame and the drywall anges of the replace. Pull down on each corner to make sure the hook is engaged with the hanger. Refer to Figures 92.
IMPORTANT: Ensure that the minimum gap required between the Optional Front and wall of the unit is maintained (refer to Figure 93). Not maintaining the proper gap will cause the unit to run at elevated temperatures and result in an unsafe condition
The face should be cleaned before the replace is turned on for the rst time.
Figure 92: Optional Front Being Installed.
44
Figure 93: Optional Front Installed.
Page 45
Wiring HarneSS
Figure 94: Wiring Harness.
Caution: Label all wires
prior to disconnection when servicing controls, Wiring errors can cause improper and dangerous operation. Verify proper operation after servicing.
45
Page 46
diagnoStic flaSH codeS
1. Fail to ignite: If there is no positive ignition, the board will go into lock out and the LED will blink 3 times in intervals until the system is reset. See Figure 96 for LED location in the unit.
2. Low battery condition (<4V): the LED indicator will blink one (1) time in intervals.
3. Parasitic Pilot Flame: the LED indicator will blink two (2) times in intervals.
4. System Lock out: the LED indicator will blink three (3) times in intervals.
Additional Ignition Information
1. The Proame DFC Board will try two (2) times for ignition.
2. Each try for ignition will last approximately 60 seconds.
3. The wait time between the two tries is approximately 35 seconds.
Figure 95: Proame DFC Board with LED Indicator attached.
46
Figure 96: LED Indicator Location.
Page 47
troubleSHooting
Problem Possible Cause Solution
Thermostat does not work
No spark generation
No pilot ame ignition
The pilot ame has gone out The On/Off switch is turn to OFF The thermostat is set too high
Spark developes near the pilot assembly or could occur onboard
No spark from the igniter
Air in the gas line
Pilot gas pressure dropout upon main burner gas valve opening
No gas ow out of the pilot burner
· Turn it ON
· Set the thermostat to a lower temperature
· Check pilot assembly wiring
· Check for broken or poor connection from the sparker to the electrode
· Check for the spark shorting or arcing at other locations
· Check for defective sparker and spark electrode
· See “no spark generation”
· It takes a while for all the air to purge out of the pilot before gas can reach the pilot and ignite
· Check gas mains supply and pressure
· Check gas valve wirings and connections to the board
· Check the pilot burner for obstruction
· Check the wirings and connections between the pilot assembly and the board
· Check the correct gas type settings on the valve and pilot burner assembly orice
Pilot will not remain lit
Remote control does not work
No reaction to command
Problem with Flame Sensor circuit
Restrictor setting
The pilot light has gone out The remote is too far away from
the heater The remote control receiver is
turned “OFF” One of the two remote control or
receiver batteries are dead Receiver or transmitter batteries
are low
A maximum number of failed ignitions or ame restorations have been reached.
· Check for proper connection of the Flame Sensor to the DFC board
· Check pilot for full ame impingement around Flame Sensor
· If ame is too small, check gas pressure, adjust pilot rate screw, check pilot head for damage
· Ensure the ground wire is properly attached to the pilot mounting bracket and that it is makes a good electrical connection.
· Use the correct restrictor setting for the venting conguration
· See “Pilot will not remain lit”
· Use the remote closer to the heater
· Check the remote control instructions
· Replace the batteries
· Replace the batteries
· Remove any possible blocking conditions. See “locking conditions”
· See how to reset the board from Lockout
No communication between the remote control and the receiver
· Reprogram the transmitter to the receiver.
· Follow the initializing system for the rst time
47
Page 48
troubleSHooting
Problem Possible Cause Solution
· Turn the system off by pressing the ON/OFF button on the transmitter
· After approximately 2 seconds press the ON/OFF button on the transmitter again.
· In the manual ame control mode, use the down arrow button to reduce the ame to off, indicated by the word
Locking conditions
Main burners will not start
Reset the Proame DFC board
The pilot ame has gone out · See “Pilot will not remain lit” The remote control is not working
correctly The thermostat is disconnected or
set too high
Problem with thermopile circuit
OFF displayed on the transmitter LCD screen.
· Wait approximately 2 seconds and press the up arrow button, the ignition sequence will start.
· With the transmitter off, move the slider switch on the receiver to the OFF position.
· Wait approximately 2 seconds and move the receiver slider switch to the ON position.
· Replace the batteries
· Set the thermostat to a lower temperature
· Check gas line pressure
· Check wiring to thermostat for breaks
· Check for ame impingement on thermopile
Flame lifting
Blue Flames
Glass fogs up
Flames are burning “dirty” or sooting
Leak in vent pipe · Check for leaks in vent connections Improper vent conguration
Terminal may be re-circulating ue gases
The heater has just been started
Improper air shutter adjustment · Adjust air shutter – contact your dealer
Normal condition: after the appliance warms up the glass will be clear.
The logs or glasses are placed incorrectly
Improper air shutter adjustment
Incorrect rating input
· Check vent conguration with manual
· Check to see if terminal is on correctly
· May need to install high wind termination cap.
· Contact dealer
· Normal during start up: ame will yellow as the replace heats up
**Due to additives in gas, glass may get hazy during operation** Clean as needed.
· Check log positioning
· Check level of glasses layout
· Increase primary air by opening the air shutter and/or
by opening the vent restrictor
· Check for proper venting and blockage of the vent
termination
· See also “Burners will not remain lit”
· Check manifold pressure and clock input rating for over­ring
48
Page 49
PartS diagram
49
Page 50
PartS diagram - oPtionS
50
Page 51
PartS liSt
Item Number Items
1 50-1980 2 50-1984 3 50-2234 4 50-2233 5 50-2235 6 50-2238 7 50-2232 8 50-2231
9 50-2236 10 50-2237 11 50-2239 12 50-2240 13 50-2241 14 50-2242 15 50-2243 16 50-2315 17 50-2006 18 50-2008 19 50-2009 20 50-2001 21 50-2311 22 23 50-2314 24 50-1939 25 26 50-2010 27 50-2319 28 50-2316 29 50-2309 30 50-2007 31 50-2031 32 50-2005
Crushed Glas - White Crushed Glas - Black Log Set Log Grate Log Burner Accent - Mortar Grey Glass Burner Accent - Castle Stone Burner Log / Ember Bed Burner Glass Media Log Burner Accent - Black Porcelain Glass Burner Accent - Black Porcelain Panel Set - Black Porcelain Panel Set - Rustic Brick Brown Panel Set - Rustic Brick Red Panel Set - Fractured Slate Panel Set - Castle Stone Fireplace Facing Kit Remote Control Transmitter Wire Harness - Receiver Wire Harness - IPI Door Tool Door Assembly Glass Door Valve Assembly (50-2004) Rock Accents Wire Loom Gasket Pilot Assembly Light Bulb Cover
Halogen Socket Light & Wire Light Bulbs (Set 2) Remote Receiver Fan Control Module (50-1572) Digital Fireplace Controller
Item Number Items
50-2245 50-2246 50-1970 50-2305 50-2308 50-2312 50-2313
EC-019 EC-011
30-043 50-1983 50-1984 50-5317 50-2320
20-034 50-2310
Fireplace Door Front - AC Fireplace Door Front - Black Power Vent Kit Vent Reducer 6” x 8 5/8” to 5” x 8” Log Burner Kit Owners Manual Technical Manual Pilot Orice (Injector) NG Threaded Spark Electrode with Ignitor Cable SIT Pilot 1/8” Tube w/End Frerules Pilot Flame Sensor (Long Ceramic) Pilot Bypass Swith Assembly Light Circuit Wire Harness Dual Bulb Door Gasket (20 ft) Halogen Cycle (Pin Socket) Valve Access Panel Gasket
51
Page 52
Warranty
Sherwood Industries Ltd. is the manufacturer of the Westgate line of heating products. At Sherwood Industries, our commitment to the highest level of quality and customer service is the most important thing we do. Each Westgate stove is built on a tradition of using only the nest materials and is backed by our Exclusive Lifetime Limited Warranty to the original purchaser. With Westgate, you’re not just buying a replace or stove, you’re buying a company with years of unequalled performance and quality.
Limited Lifetime Warranty:
Under this warranty, Sherwood Industries Ltd. covers the replace or stove body and accessories against defects in materials and workmanship, for part repair or replacement for the rst seven (7) years and limited labour for the rst two (2) years to the original purchaser. This Warranty covers: Firebox, Heat Exchanger, Steel Firebox Panels, Ceramic Logs & Panels, Burner, Ceramic Glass, Pedestals, Panels and Legs. Please see the exclusions and limitation section below as certain restrictions and exclusions apply to this warranty.
Limited Two (2) Year Warranty:
Under this warranty, Sherwood Industries Ltd. covers: Gas Assembly, Blower, Blower control, Temperature Sensors and Wire Harness against defects in materials and workmanship, for part repair or replacement for the rst two (2) years and limited labour for the rst two (2) years to the original purchaser. Please see the exclusions and limitation section below as certain restrictions and exclusions apply to this warranty.
Limited One (1) Year Warranty:
Under this warranty, Sherwood Industries Ltd. covers all exterior surface nishes against defects in materials and workmanship, for part repair or replacement and limited labour for the rst (1) year to the original purchaser. Please see the exclusions and limitations section below as certain restrictions and exclusions apply to this warranty. Here is how our Warranty works If you have any concerns with your Westgate product, please contact the dealer where you purchased the replace or stove. Your dealer shall make all claims under this warranty in writing.
To the Dealer
When lling out a warranty claim, please complete the following information on an ofcial warranty claim form: Customer information: Name, address and telephone number of purchaser and date of purchase. Dealer information: Date of installation, name of installer and dealer, serial number of the appliance, nature of complaint, defects or malfunction, description and part numbers of any parts replaced.
To the Distributor
Sign and verify that work and information are correct.
Exclusions and Limitations:
1. This Warranty does not cover tarnish, discoloration or wear on the plating or paint.
2. This Warranty excludes wear and tear or breakage caused by cleaning, moving or service on log set and panels.
3. A qualied installer must install this stove or replace. This Limited Warranty covers defects in materials and workmanship only if the product has been installed in accordance with local building and re codes; in their absence, refer to the owner’s manual. If the product is damaged or broken as a result of any alteration, willful abuse, mishandling, accident, neglect, or misuse of the product, the Limited Warranty does not apply.
4. The stove must be operated and maintained at all times in accordance with the instructions in the Owner’s Manual. If the unit shows signs of neglect or misuse, it is not covered under the terms of this Warranty policy. Performance problems due to operator error will not be covered by the Limited Warranty policy.
5. As this is a heating appliance, some changes in colour of surface nishes may occur. This is not a aw and as such is not covered under this warranty.
6. Some minor expansion, contraction, or movement of certain parts and resulting noise, is normal and not a defect and, therefore, is not covered under this Limited Warranty.
7. Misuse includes over-ring. Over-ring this appliance can cause serious damage and will nullify the Limited Warranty.
8. The Limited Warranty will cover glass thermal breakage only and will not cover misuse of the stove glass, including but not limited to glass that is struck, has surface contaminates or has had harsh or abrasive cleaners used on it.
9. This warranty does not cover products made or provided by other manufacturers and used in conjunction with the operation of this stove without prior authorization from Sherwood Industries Ltd. The use of such products may nullify the Limited Warranty on this stove. If unsure as to the extent of this Limited Warranty, contact your authorized Westgate dealer before installation.
10. Sherwood Industries Ltd. will not be responsible for inadequate performance caused by environmental conditions.
11. The Limited Warranty does not cover installation and operational related problems caused by downdrafts or spillage
caused by environmental conditions. Environmental conditions include but are not limited to nearby trees, buildings, roof tops, wind, hills, mountains, inadequate venting or ventilation, excessive offsets, negative air pressures or other inuences caused by mechanical systems such as furnaces, fans, clothes dryers etc.
52
Page 53
Warranty
12. The Limited Warranty is void if: a) The stove has been operated in atmospheres contaminated by chlorine, uorine or other damaging chemicals. b) The stove is subject to submersion in water or prolonged periods of dampness or condensation. c) Any damage to the unit, combustion chamber or other components due to water, or weather damage which is the
result of, but not limited to, improper chimney/venting installation.
c) Salt air in coastal areas or high humidity can be corrosive to the nish; these environments can cause rusting.
Damage caused by salt air or high humidity is not covered by the Limited Warranty.
13. Exclusions to the Limited Warranty include: injury, loss of use, damage, failure to function due to accident, negligence, misuse, improper installation, alteration or adjustment of the manufacturer’s settings of components, lack of proper and regular maintenance, alteration, or act of God.
14. The Limited Warranty does not cover damage caused to the replace or stove while in transit. If this occurs, do not operate the stove and contact your courier and/or dealer.
15. Limited Warranty does not extend to or include rebox paint, door or glass gaskets with damage caused by normal wear and tear, or exterior paint discoloration or chipping, worn gaskets, etc.
16. The Limited Warranty does not include damage to the unit caused by abuse, improper installation, or modication of the unit.
17. Damage to plated surfaces caused by ngerprints, scratches, melted items, or other external scores and residues left on the plated surfaces from the use of abrasive cleaners or polishes is not covered in this warranty.
18. The Limited Warranty does not cover tarnish, discoloration or wear on the plated surfaces.
19. The paint on the Metal Brick Liner may peel. This is due to the extreme conditions applied to the paint during normal usage. It is not a aw and is not covered under warranty.
20. Sherwood Industries Ltd. is free of liability for any damages caused by the replace or stove, as well as inconvenience expenses and materials. The Limited Warranty does not cover incidental or consequential damages.
21. The Limited Warranty does not cover any loss or damage incurred by the use or removal of any component or apparatus to or from the Westgate replace or stove without the express written permission of Sherwood Industries Ltd. and bearing a Sherwood Industries Ltd. label of approval.
22. Any statement or representation of Westgate products and their performance contained in Westgate advertising, packaging literature, or printed material is not part of the Limited Warranty.
23. The Limited Warranty is automatically voided if the replace or stove’s serial number has been removed or altered in any way. If the stove is used for commercial purposes, it is excluded from the Limited Warranty.
24. No dealer, distributor, or similar person has the authority to represent or warrant Westgate products beyond the terms contained within the Limited Warranty. Sherwood Industries Ltd. assumes no liability for such warranties or representations.
25. Sherwood Industries Ltd. will not cover the cost of the removal or re-installation of the stove, hearth, facing, mantels, venting or other components.
26. Labour to replace or repair items under this Limited Warranty will be covered per our warranty service fee reimbursement schedule. Labour rates are set per component and as such total labour costs may not be covered.
27. Sherwood Industries Ltd. is not liable for freight or labour on any stove replaced in-eld and is not liable for travel costs for service work. In the event of in-home repair work, the customer will pay any in-home travel fees or service charges required by the Authorized Dealer.
28. At no time will Sherwood Industries Ltd. be liable for any consequential damages which exceed the purchase price of the unit. Sherwood Industries Ltd. has no obligation to enhance or modify any stove once manufactured (example: as a stove evolves, eld modications or upgrades will not be performed).
29. This Limited Warranty is applicable only to the original purchaser and it is non-transferable.
30. This warranty only covers Westgate products that are purchased through an authorized Westgate dealer.
31. If for any reason any section of the Limited Warranty is declared invalid, the balance of the warranty remains in effect and all other clauses shall remain in effect.
32. The Limited Warranty is the only warranty supplied by Sherwood Industries Ltd., the manufacturer of the stove. All other warranties, whether expressed or implied, are hereby expressly disclaimed and purchaser’s recourse is expressly limited to the Limited Warranty.
33. Sherwood Industries Ltd. and its employees or representatives will not assume any damages, either directly or indirectly, caused by improper usage, operation, installation, servicing or maintenance of this stove.
34. Sherwood Industries Ltd. reserves the right to make changes without notice. Please complete and mail the warranty registration card and have the installer ll in the installation data sheet in the back of the manual for warranty and future reference.
35. Sherwood Industries Ltd. is responsible for stocking parts for a maximum of seven (7) years after discontinuing the manufacture or incorporation of the item into its products. An exception to this would be if an OEM supplier is not
to supply a part.
able
53
Page 54
inStallation data SHeet
The following information must be recorded by the installer for warranty purposes and future reference.
NAME OF OWNER:
_________________________________________
ADDRESS:
_________________________________________
_________________________________________
_________________________________________
PHONE:___________________________________
MODEL:___________________________________
SERIAL NUMBER:___________________________
DATE OF PURCHASE: _____________ (dd/mm/yyyy)
NAME OF DEALER:
_________________________________________
ADDRESS:
_________________________________________
_________________________________________
_________________________________________
PHONE:___________________________________
NAME OF INSTALLER:
_________________________________________
DATE OF INSTALLATION:___________(dd/mm/yyyy)
� NATURAL GAS (NAT) � PROPANE(LPG)
INLET GAS PRESSURE:_________in wc
MAIN BURNER ORIFICE:__________# DMS
PILOT ORIFICE #_________OR________in diam.
INSTALLER’S SIGNATURE:
_________________________________________
MANUFACTURED BY:
SHERWOOD INDUSTRIES LTD.
6782 OLDFIELD RD. SAANICHTON, BC, CANADA V8M 2A3
July 01 2010
www.westgatereplaces.com
ADDRESS:
_________________________________________
_________________________________________
_________________________________________
PHONE:___________________________________
C-12283
54