Application Note
TAN 1005
Surge Suppression
for Zone 0 Locations
991.115
03/99
Synopsis
This note discusses the surge
protection requirements of
intrinsically safe circuits entering a
Zone 0 hazardous area. It
analyses the potential gradients
generated by lightning strikes and
their possible routes of invasion.
The alleviation of the problem at
the zone 0 interface transfers the
problem elsewhere and an
adequately safe pragmatic
solution is proposed.
A member of The MTL
Instruments Group plc
CONTENTS
PAGE
1 INTRODUCTION ........................................................................................................................... 1
2 INTRINSIC SAFETY REQUIREMENTS FOR EARTHING AND BONDING............................................... 2
3 CERTIFICATION OF SURGE SUPPRESSORS ...................................................................................... 2
4 PROTECTION OF THE SENSOR AND TRANSMITTER ........................................................................ 3
5 PROTECTION OF THE GALVANIC ISOLATOR AND SAFE-AREA EQUIPMENT....................................... 3
6 PROTECTION OF SUPPLIES AND SIGNALS FROM EXTERNAL SOURCES ............................................ 4
7 CONCLUSION ............................................................................................................................. 5
APPENDIX A .......................................................................................................................................... 5
APPENDIX B........................................................................................................................................... 5
Application Notes from Telematic
Telematic publish an increasing number of Application Notes providing easily understood information on various aspects of surge and
lightning protection. At the date of publication of this Application Note, the list included:–
TAN1001
TAN1002
TAN1003
TAN1004
TAN1005
TAN1006
TAN1007
Lightning surge protection for electronic equipment – a practical guide
A relatively brief and easy to understand introduction to the subject – an excellent starting point
Lightning and surge protection – basic principles
A more detailed account of the mechanism of lightning strikes and the measures needed to achieve an adequate level
of protection
Earthing guide for surge protection
A detailed analysis of the subject of earthing for surge suppression purposes, this is both an easily understood
exposition and a valuable reference document
Surge protection for intrinsically safe systems
A description of the best methods of combining surge suppression and intrinsically safe systems
Surge suppression for Zone 0 locations
A detailed analysis of this particular aspect of surge suppression in hazardous areas; complements TAN1004
Surge protection for weighing systems
Discusses, in some detail, the specific application of surge suppression to load-cell weighing systems
Surge protection for Local Area Networks
Discusses ways in which Local Area Networks can be damaged by lightning induced transients and how they can be
protected economically
About Telematic
Telematic Limited is a company with a well-established reputation for the design and manufacture of surge protection devices and with
considerable experience of successful installation practices. A consultancy service is available to advise customers on the selection and
location of devices for particular applications. If you have any specific enquiries, please contact Telematic directly at the address on the
back cover or contact your local MTL group company – whichever is most convenient.
Telematic is a member of the MTL Instruments group and is therefore in a unique position to make good use of Measurement Technology’s
leading position as a supplier of intrinsically safe interfaces to provide the best possible choices of equipment for hazardous-area applications.
The principal author of this publication is LC Towle, BSc, Chairman at Telematic Ltd, who acknowledges with thanks the comments of
colleagues and customers. If you have any comments (preferably constructive) on this document, please make them to the author so that the
document can be amended and made even more useful.
SURGE SUPPRESSION FOR
ZONE 0 LOCATIONS
1 INTRODUCTION
For many years there has been general recognition that there is a
significant problem from lightning strikes on installations such as storage tanks. The codes of practice for instrumentation in hazardous areas for Germany and Holland both contain recommendations for specific installation practice. In the United Kingdom the code of practice
contains no detailed requirements and the problem has always been
approached on an individual installation basis. Perhaps the clearest
references are in the draft revision of the IEC code which contains two
specific references to lightning problems. These, together with the relevant clause on potential equalisation, are quoted in full as an appendix (clauses 6.3, 6.5 and 12.3).
Although this code of practice has not yet been finally voted on and
published it is likely to form the basis of accepted practice in significant parts of the world and forms a convenient reference document.
When a plant is struck by lightning then the point of impact would
inevitably ignite a gas and air mixture that was present. Ignition at
points other than the point of impact are dependent on the efficiency of
bonding which must be adequate to prevent side flashes and hence
bonding should have a low impedance as well as a low resistance.
The majority of petrochemical installations are adequately bonded and
sufficiently robust to prevent excessive lightning damage although some
side flashes usually occur following a significant adjacent strike. Corona discharge from structures does occur in some atmospheric conditions and multiple streamers rising from structures to meet the usual
lightning downward leader (which selects one of them) are a well established phenomenon. It is possible that if either a lightning flash, an
upward corona streamer, or a side flash pass through a flammable
mixture of gas then ignition will occur. In general, conventional bonding of a plant is considered adequate and the implications of possible
lightning impact points are not considered a significant problem except in the case of vents which frequently discharge. Where lightning
can damage the electrical insulation of power circuits there is a transient potential hazard caused by the follow through of the power circuit. This should however be rapidly removed by the electrical protection ie. fuses, out of balance circuit breakers etc. which is a fundamen-
tal requirement of all the methods of protection used for power equipment. It is not usual for lightning induced current to directly cause enough
heating to create a hazard by temperature ignition, since the current
pulses are too short to create a sustained high temperature. However,
vapourisation of flimsy conductors such as printed circuit tracks is not
unusual. Overheating may occur if there is a power follow through of
a fault initiated by the lightning induced voltage. It can be argued that
if intrinsically safe apparatus is likely to be subjected to lightning damage then it is necessary to protect it since, following the lightning damage, its intrinsic safety may be impaired. There is no requirement in the
apparatus standard to consider the effect of excessive surges, which
are difficult to predict and could lead to damage. The problem should
not be exaggerated, since lightning damage usually results in failure
to a safe condition and also to operational failure and hence should
be noticed and corrected. Possibly the need to repair or remove nonfunctional electrical equipment needs to be given further emphasis in
the code of practice.
It is accepted that transient hazards during infrequent electrical faults
can occur in Zones 1 and 2 providing that they are removed as quickly
as is practical. The argument being that the coincidence of the potentially hazardous electrical fault and a flammable mixture of gas is sufficiently improbable to be acceptable. In the particular case of lightning a similar analysis suggests that transient hazards caused by points
of lightning impact and the occasional failure to bond adequately are
possibly acceptable in Zone 1 and 2 but not acceptable in Zone 0.
Fortunately the majority of Zone 0 locations are contained within process vessels which form an adequate Faraday cage which effectively
prevents significant potential differences within the Zone 0 and hence
the problem is generally controllable. Where problems are known to
exist then special precautions are taken, for example the bond between the floating roof of a storage tank and the tank itself is designed
with considerable care, and subjected to frequent inspections. A problem is introduced when the Faraday cage of the Zone 0 is broken by
the introduction of equipment for measurement purposes.
Figure 1 shows an average contents temperature gauge being used in
a storage tank and this illustrates the problem. The potential equalising
network is shown diagramatically as a substantial structure interconnected electrically, in practice it is the plant structure bonded together.
The transmitter protruding from the tank top is intended to illustrate the
concept. In practice in a high lightning activity area it would be unwise
to have the equipment protruding from the tank in this way since it
would possibly invite a direct strike and could be the natural source of
corona discharge. It should be provided with some mechanical protec-
100kA
10µS
10m
0.1µH/m
(10kV)
30KV
L
1
L
2
Potential equalising
network
30kV
Computer 0V
Power 0V
0.1µH/m
10kA
500m
(50kV)
Figure 1 Installation without surge protection
1