Western Telematic RPC-4840N User Manual

WTI Part No.: 13224
Rev. A
RPC-4840N
Network Ready Remote Power Controller
User's Guide
Warnings and Cautions:
No Serviceable Parts Inside; Authorized Service Personnel Only
Shock Hazard - Do Not Enter
Nameplate Power Warning
This device should only be operated with the type of power source indicated on the instrument nameplate. If you are not sure of the type of power service available, consult your local power company.
Connect unit only to a properly measured supply. Use
only three wire cord which is provided with the unit.
Reliable earthing of this equipment must be maintained.
Particular attention should be given to supply connections when connecting to power strips, rather than direct connections to the branch circuit.
Rack Mount Installation
When installing this device in an instrument rack, the following factors must be accounted for:
1. Enclosed Racks: Enclosed racks must provide adequate ventilation. Make certain that the rack is not overly crowded and note that each unit in the rack generates its own heat. An enclosed rack should have louvered sides and a fan to circulate cooling air.
When mounting the unit in an enclosed rack with a ventilation fan at the top of the rack, note that excessive heat generated by devices at the bottom of the rack can be drawn upward and into the ventilation slots of units located at the top. Make certain to provide adequate ventilation for equipment installed at the bottom of the rack.
(Continued)
i
RPC-4840N Remote Power Controller; User's Guide
Rack Mount Installation (Continued)
1. Enclosed Racks (Continued):
The ambient within the rack may be greater than room ambient. Installation should be such that the amount of air flow required for safe operation is not compromised. The maximum temperature for the equipment in this environment is 45°C. Consideration should be given to the maximum rated ambient.
Installation should be such that a hazardous stability condition is not achieved due to uneven loading.
2. Open Racks: Make certain that the rack frame does not block the ventilation slots on the instrument cover. If the device is installed on sliders, check the unit when seated all the way into the rack to make certain that ventilation slots are not blocked.
Ventilation
Slots in the instrument cover are provided to allow ventilation for heat dissipation. To ensure safe, reliable operation, these openings must not be covered or blocked.
Disconnect Power
If any of the following events are noted, immediately disconnect the unit from the power source and contact qualified service personnel:
1. If the power cord becomes frayed or damaged.
2. If liquid has been spilled into the device or if the device has been exposed to rain or water.
ii
Table of Contents
1. Introduction
2. Unit Description
2.1. Front Panel
2.2. Back Panel
3. Quick Start Guide
4. Installation
4.1. Power Connection
4.2. Option Switches
4.3. Reset Unit to Defaults
4.4. Console Port Connection
4.5. Connecting an External Modem
4.6. Connecting the Network Cable ..................4-4
5. Configuration ...............................5-1
5.1. System Mode and User Mode ..................5-1
5.2. Communicating with the RPC-4840N ..............5-2
5.3. Command/Menu Conventions ..................5-4
5.4. Defining General Parameters ...................5-4
5.5. Circuit Parameters .........................5-7
5.6. Network Parameters ........................5-9
5.7. Save Configuration Parameters .................5-12
6. Operation
6.1. Access the Command Mode
6.2. Displaying circuit Status
6.3. Boot/On/Off Commands
6.4. The Default Command
6.5. The Automated Mode
6.6. Other Commands
6.7. Operating Tips
7. Saving and Restoring Configuration Parameters
7.1. Sending Parameters to a File
7.2. Restoring Saved Parameters
................................
.............................
.............................
.............................
............................
................................
.........................
..........................
.......................
4.3.1. Default Button / Reset Button (Local)
4.3.2. Default Parameters Option
.....................
5.6.1. Implementing IP Security ...............5-10
.................................
.....................
......................
......................
.......................
..........................
6.6.1. Login as Different User
6.6.2. Reset Network Port
6.6.3. Exit / Disconnect
...........................
....................
.....................
...............
.................
...................
.................
...................
...................
.........
.........
1-1 2-1
2-1 2-1
3-1 4-1
4-1 4-2 4-3 4-3 4-3 4-4 4-4
6-1
6-1 6-2 6-3 6-5 6-5 6-7 6-7 6-7 6-7 6-8
7-1
7-1 7-2
iii
RPC-4840N Remote Power Controller; User's Guide
Appendices: A. Interface Descriptions
A.1. Console Port Interface A.2. Modem Port Interface
B. Specifications C. Customer Service
.............................
........................
.....................
.....................
...........................
Apx-1
Apx-1 Apx-1
Apx-2 Apx-3
List of Figures
2.1. Front Panel
2.2. Back Panel
3.1. The System Help Screen
4.1. RPC-4840N Block Diagram
5.1. System Help Screen
5.2. User Help Screen
5.3. General Parameters Menu (System Mode Only)
5.4. Circuit Parameters Menu (Circuit 1 Shown)
5.5. Network Parameters Menu (System Mode Only)
5.6. IP Security Menu
6.1. System Status Screen (Passwords Hidden) A.1. Console Port Interface A.2. Modem Port Interface
iv
................................
................................
........................
......................
...........................
............................
.............
...........................
..............
........................
........................
...........
..........
Apx-1 Apx-1
2-1 2-2 3-2 4-1 5-3 5-3 5-5 5-8 5-9
5-10
6-2
1. Introduction
Network equipment sometimes "locks-up", requiring a service call just to flip the power switch to perform a simple reboot. The RPC-4840N Heavy Duty Remote Power Controller gives you the ability to reboot DC powered equipment from anywhere on the LAN/WAN, or if the network is down, to simply dial-in from a modem for out-of-band power control.
Intelligent Power Control
The RPC-4840N can communicate over any TCP/IP network using standard Telnet, or out-of-band using an external modem and terminal emulation. Each DC circuit can be assigned an individual password, device name, reboot delay time and unique power-up default status.
Security
Address specific IP security masks prevent unauthorized users from accessing the RPC command menu via network. The RPC provides two separate password security levels; System level and User level. The System password allows access to all configuration and command functions. The User password allows limited access to command functions.
Easy to Use, Easy to Configure
The RPC-4840N can be configured over the network, via modem, or locally via the RPC Console Port. Easy-to-use commands let you assign a location name, set system parameters and view circuit status. Circuits can be switched On, Off, or Booted using circuit numbers or user-defined names.
Heavy Duty DC Power Control
The RPC-4840N can control up to 40 amps of DC power per circuit. Since larger routers require as much as 30 amps, the RPC has power control to spare. The optional second Circuit Module allows the RPC to control power for two 40 amp, DC powered instruments.
1-1
RPC-4840N Remote Power Controller; User's Guide
Features:
Dual 40 Amp Circuits
·
On/Off/Reboot Switching
·
Integral 10Base-T Interface
·
RS232 Modem and Console Ports
·
Circuit-Specific Password Security
·
Network Security Features
·
Manual On/Off Buttons
·
Typographic Conventions
Throughout this manual, typefaces and characters have been used to denote the following:
COURIER FONT Indicates characters typed on the keyboard.
For example, /ON 1 or /OFF 2.
[Bold Font] Text set in bold face and enclosed in
square brackets indicates a specific key. For example, [Enter] or [Esc].
1-2
2. Unit Description
2.1. Front Panel
As shown in Figure 2.1, the RPC-4840N front panel includes a series of LED indicators which function as follows:
Figure 2.1: Front Panel
ON: Lights when Power is applied to the Control Section.
À
RDY: Flashes when the RPC-4840N is ready to receive
Á
commands. Indicates that the Console Port has received the "Ready" signal from the control device.
RXD: Lights when the RPC-4840N receives commands.
Â
Circuit 1 Indicator: Lights when the Circuit 1 Switch is
Ã
closed (Power ON to connected device.)
Circuit 2 Indicator: Lights when the optional Circuit 2
Ä
Switch is closed (Power ON to connected device.)
2.2. Back Panel
Network Port and Activity Indicator: A 10BaseT, RJ45
À
Ethernet port for connection to your TCP/IP network. To communicate via network, you must first specify network parameters as described in Section 5.6.
Note: The RPC-4840N features a 10BaseT interface. When connecting the RPC to a 100BaseT interface, note that most 100BaseT router switches will autosense to determine if the device is 100BaseT or 10BaseT and then configure the network interface accordingly. If your router switch does not autosense, then the network interface port must be manually set to 10BaseT.
2-1
RPC-4840N Remote Power Controller; User's Guide
Figure 2.2: Back Panel
Options Switch: Four DIP Switches which set the default
Á
baud rate, boot delay, echo mode, and timeout.
Default Button: Used in conjunction with the Reset
Â
Button to reset the unit to defaults (see Section 4.3.)
Console Port: A Male RS-232, DB9 Connector, DTE
Ã
configuration. For connection to a local PC.
Modem Port: A Male RS-232, DB9 Connector, DTE
Ä
configuration. For connection to an external modem.
Reset Button: Used in conjunction with the Default
Å
Button to reset the unit to defaults (see Section 4.3.)
2-2
Circuit Module 1: For connection to your DC power
Æ
supply and DC powered device. Each circuit is capable of switching up to 40 Amps. Note that power for control functions is also derived from the Circuit 1 input terminal.
A. ON Indicator: Lights when the corresponding Circuit
Module is switched On (switch closed).
B. Emergency Override Breaker: If the circuit is
overloaded, the breaker pops out and opens the circuit. If necessary the Override Breaker can also be manually pulled out to open the circuit. To reset the circuit, press the Override Breaker in.
Circuit Module 2 (Optional): For connection to a second
Ç
DC power supply and DC powered device. Same as Circuit Module 1.
3. Quick Start Guide
This section provides a brief overview of basic RPC-4840N capabilities, and describes a simple test that can be performed to determine if the unit is operating properly and demonstrate basic communication capabilities.
Note that this Quick Start procedure is included only to provide a quick demonstration of basic RPC-4840N capabilities. In order to take full advantage of the complete range of features provided by this unit, it is strongly recommended that you should complete the entire Installation and Configuration sections after completing the Quick Start procedure.
1. Apply Power to the RPC-4840N: Connect an appropriate power source to the input terminals on the Circuit 1 terminal block, located on the RPC back panel. Prior to connecting the unit to your power supply, make certain to review the safety precautions listed at the beginning of this User's Guide.
2. Connect a PC to the RPC-4840N: Attach a standard null modem cable from your PC COM port to the Console Port connector on the RPC back panel. For a description of the port interface, please refer to Appendix A.
Note: When the RPC is shipped from the factory, Console Port communication parameters are set as follows: 9600 bps, 8 Data Bits, One Stop Bit, No Parity. Although the RPC allows these parameters to be easily redefined, for this Quick Start procedure, it is recommended that you configure your communications program to accept the default parameters.
3. Access the Command Mode: Start your communications program and then press [Enter]; the System Help Screen should be displayed (Figure 3.1) and the "RPC>" command prompt should appear. For more information on command mode access, please refer to Section 5.2.
3-1
RPC-4840N Remote Power Controller; User's Guide
Remote Power Controller v2.0 Site: WESTERN TELEMATIC, INC.
Commands:
Display /H Display this help screen /S[P] Display Ckt. Status, [P] with passwords
Configuration /G View/Set General Parameters /P [n] View/Set Ckt. Parameters /N View/Set Network Parameters /DL Download configuration to file
Control +------------------------------------+ /D Set Ckts. to default setting | [n] = optional Ckt. name or number | /Boot <n> Boot Ckt. n | <n> = required Ckt. name or number | /On <n> Turn On Ckt. n | n+n = Ckt. n and Ckt. n | /Off <n> Turn Off Ckt. n | n:n = Ckt. n through Ckt. n | /T Reset Network Interface | * = all Ckts. with access | /R Relogin as different user +------------------------------------+ /X Exit/Disconnect
RPC>
Figure 3.1: The System Help Screen
4. Configure Network Port: In order to communicate with the RPC-4840N via the Network Port, you must first define the IP Address, Subnet Mask, and Gateway Address. At the RPC> command prompt, type /N and press [Enter] to display the Network Parameters menu.
3-2
a) Settings for network parameters will depend on the
configuration of your individual network. Please contact your network administrator to determine appropriate settings for the IP Address, Subnet Mask, and Gateway Address.
b) To assign network parameters, key in the number for
the desired parameter, press [Enter], and then follow the instructions in the resulting submenu. For example, to define the IP Address, type 1 and press [Enter].
Quick Start Guide
5. Exit Command Mode: When you have finished setting
Network Parameters, type /X and press [Enter] to exit the command mode at the Console Port.
Note: Only one port may access the command mode at a given time. In order to allow access to the RPC unit via other ports, always exit from the command mode when finished communicating with the unit.
6. Connect Network Cable: Connect your network interface to the RPC-4840N Network Port. The Network Port is an RJ45, 10BaseT Ethernet jack, for connection to a TCP/IP network.
Note: The RPC features a 10BaseT Interface. When connecting to a 100BaseT interface, note that most router switches will autosense to determine if the device is 100BaseT or 10BaseT, and then configure the network interface accordingly. If your router switch does not autosense, then the network interface port must be manually set to 10BaseT.
7. Network Access: Telnet to the RPC's IP address. For example, if the IP address is "119.1.1.1", on a UNIX system the Telnet command would be invoked as follows:
$ telnet 119.1.1.1 [Enter]
After the Telnet connection is established, the RPC should display the System Help Screen and the RPC> command prompt should appear, indicating that you have successfully accessed the RPC Command Mode via the Network Port.
3-3
RPC-4840N Remote Power Controller; User's Guide
8. Test Boot Commands: When the RPC-4840N is powered up, both switched circuits will be set in the ON (closed) position. In order to test for proper operation, you may wish to perform the following test. Note that it is not necessary to connect a device to either switched circuit in order to perform this test.
a) Reboot Circuits: To initiate a boot cycle at both
circuits, go to the RPC> command prompt, type /BOOT * and press [Enter]. Power to both circuits will be switched OFF. After the Boot Delay Period (Default = 5 Seconds), the power to both circuits will then be automatically switched back ON. Note that the Circuit Status Indicators on the RPC front panel will also switch Off and On.
b) Switch Circuits OFF: To switch both circuits OFF, go
to the RPC> command prompt, type /OFF * and then press [Enter]. Power to both circuits will be switched OFF. Note that the Circuit Status Indicators will also be switched Off.
c) Switch Circuits ON: To switch both circuits ON, go
to the RPC> command prompt, type /ON * and then press [Enter]. Power to both circuits will be switched ON. Note that the Circuit Status Indicators will also be switched On.
9. Exit Command Mode: Type /X and press [Enter] to exit from the RPC Command Mode, or disconnect using your Telnet program.
This completes the introductory overview of the RPC-4840N. Prior to installing and operating the unit, please review the remainder of this User's Guide for important information regarding safety considerations, as well as more detailed installation, configuration, and operation instructions.
3-4
4. Installation
4.1. Power Connection
Connect your DC power supply to the Circuit 1 Input Terminals as shown in Figure 4.1. Connect the power supply lines from your DC Powered device to the Output Terminals. Note that the RPC-4840N is available with two separate 40 amp circuits. In order for both circuits to function, power must be connected to both input connectors on the unit's back panel.
CAUTIONS:
This device should only be operated with the
type of power source indicated on the instrument nameplate. If you are not sure of the type of power service available, please contact your local power company.
Reliable earthing (grounding) of this unit must
be maintained. Particular attention should be given to supply connections when connecting to power strips, rather than directly to the branch circuit.
"Always On" Architecture: The RPC features "Always On"
architecture. This means that once the RPC is connected to your power supply, both circuits will always be set in the ON state, unless program commands are used to set the circuit(s) to the OFF state.
Note: In addition to supplying power to the device connected to Circuit 1, the Circuit 1 power input also provides power for the RPC control section.
Figure 4.1: RPC-4840N Block Diagram
4-1
Loading...
+ 33 hidden pages